6ES5 752-0AA23

Siemens 6ES5 752-0AA23 — V.24/V.28 RS-232C Interface Submodule

6ES5 752-0AA23 is a V.24/V.28 (RS-232C) serial interface submodule for the CP 524 and CPU 928B in the Siemens SIMATIC S5 family. It has a 25-pin female D-sub connector. This V.24 version in the S5 interface module range permits transmission rates up to 19,200 bit/s and uses RS-232 voltage signalling.

It provides the physical serial interface on equipment such as the 6ES5 524-3UA15 CP 524 or 6ES5 928-3UB21 CPU 928B. The host CPU or communications processor implements the communications task and protocol. The 0AA23 is not a standalone communications processor or an external converter.

Connector, cable and line length

The principal pins are 2: TxD output, 3: RxD input, 7: GND, and 1: shield. Control signals include 4: RTS, 5: CTS, 6: DSR, 8: DCD, and 20: DTR. When selecting S5 cables and connectors, compare the pin functions at both devices. A CPU-to-CPU link and a CPU-to-modem link may require different wiring.

Siemens specifies a maximum V.24 cable length of 16 m. Shielded cable, metal connector housings and suitable grounding are important. Consider the differences between RS-232, RS-422 and RS-485; a longer distance specified for another interface must not be applied to this module.

The jumper detail specific to 0AA23

An important point when comparing it with the 6ES5 752-0AA22 is that bridge 6 has no function on the 0AA23. Siemens states that received signals may also lie in the positive voltage region, corresponding to the general diagram’s 2–3 bridge setting. Do not troubleshoot this version by copying another module’s J6 configuration.

In the general V.24 arrangement, J3/J5 select data polarity, while J9 selects the fixed CTS condition or CTS from pin 5. The required setup depends on the partner and driver. Record the existing jumpers and check the wiring diagram before changing their positions.

Protocol and software configuration

With an appropriate host and software, the V.24 submodule family supports RK 512, 3964/3964R and the open driver. Match the PLC program, configuration software and partner settings. In a CP 524 application, the baud rate and character frame selected through COM 525 are part of the configuration.

Both ends must agree on baud rate, data bits, parity, stop bits and protocol. During troubleshooting, check more than TxD/RxD continuity: if the application waits for CTS, a control-line or jumper issue may prevent transmission. The RS-232 electrical interface and the communications protocol are separate considerations.

Differences between related 752 modules

The 6ES5 752-0AA12 is the 20 mA TTY option, while the 6ES5 752-0AA43 provides RS-422/RS-485. Their electrical connections differ from V.24/V.28. A shared family name does not establish that the existing cable and host configuration can remain unchanged.

The 6ES5 752-0AA53 is a PG interface, and the 6ES5 752-0AA62 is the SINEC L1 option. The 6ES5 752-0LA52 is a separate PG module for CPU 945. Match the complete order code, host device and communications task together.

Installation and checks on the machine

For submodule replacement in a SIMATIC S5 CPU, switch off the PLC supply and follow the manual’s removal and installation sequence. Check the two fixing screws, front socket and board connection. Within the Siemens S5 system, this small board provides the host’s serial interface; diagnose the complete connection before attributing every communications problem to it.

Editor’s note

Start with the simple checks: does TxD reach the partner’s RxD, and is signal ground connected correctly? A plugged-in connector does not prove correct wiring. Putting both device diagrams side by side often gets you further than immediately changing the board.

Keep the inactive J6 on this version in mind. A jumper photograph from another V.24 board is not a setup instruction for your 0AA23. Record the original arrangement first; there is no benefit in losing a working setting while searching for a different fault.

If data travels in one direction but not the other, use that as a useful clue. Check the transmitter, receiver and control lines separately. One working direction does not prove the whole board is healthy, but it helps narrow down where to look next.

When buying used Siemens equipment, inspect more than the label. Look closely at the 25-pin socket, fixing points and board connection. Where possible, ask for a bidirectional test in the intended host. A message sent and received correctly tells you considerably more than “we powered it up.”

For intermittent failures, give the installation a fair check before setting the module aside. Look at cable routing, shielding, connector tightness and partner settings. Establish a result with a short, sound cable first, then bring the longer installation back into the test one step at a time.

OtomasyonAVM resources and PDFs

+ Review the S5 interface modules and S5 cables and connectors pages together when choosing the submodule and connection hardware.

+ OtomasyonAVM S5 PDF archive and system manuals. In the S5-135U/155U system manual, use section 5.11.3 V.24 Submodule, the 0AA23-specific bridge note and the connector table.

Related topics

+ 6ES5 752-0AA22: another V.24 version · 6ES5 752-0AA12: TTY · 6ES5 752-0AA43: RS-422/RS-485 · CP 524 communications processor.

Browse SIMATIC S5

+ S5 interface modules · S5 cables and connectors · SIMATIC S5 · Siemens S5 PLCs · Siemens second-hand equipment.

Siemens and external references

+ Siemens S5-135U/155U System Manual — English; C79000-G8576-C199-07, Edition 07; pp. 5-99–5-105: V.24 interface, pins, jumpers and connection examples.

+ Same manual, p. 5-102: bridge 6 has no function on 0AA23; p. 5-122: transmission rate and line length.

+ Siemens 6ES5752-0AA23 data sheet — German, 10 December 2020; V.24/V.28 identity for CP 524 and CPU 928B; manufacturer document hosted in a third-party archive.

+ Siemens COM 525, Volume 1 — German; 6ES5 998-1DB11, Edition 08; CP 524 connections and transmission parameters.