6ES5 984-2UA11

Siemens 6ES5 984-2UA11 – OP 396 / PG 615 Adapter and Power Pack

Siemens 6ES5 984-2UA11 is an adapter and power-pack assembly with a 220/240 V AC, 50/60 Hz input. It powers the OP 396 operator panel and provides the appropriate serial printer connection. Siemens states that the adapter is identical to the one used with the PG 615 programmer. It supports operator and programming equipment within the SIMATIC S5 and Siemens HMI environment.

The assembly has two distinct tasks: generating the required DC supply rails and providing the serial interface connection. Assess the power pack and adapter together. It serves a different purpose from S5 rack power supplies and PLC rack supply modules; it does not occupy an I/O slot or receive an input/output address.

Mains input and the 2UB11 version

984-2UA11: 220 V AC, switchable to 240 V AC; tolerance +10% / −15%; frequency 50/60 Hz. The manual lists 984-2UB11 as the 110 V AC version, switchable to 120 V AC. These are separate mains variants. Do not assume automatic wide-range input without checking the label and voltage selection.

DC output rails and current ratings

Siemens specifies four rails: 5.1 V DC ±2% / 650 mA; +12 V DC ±5% / 120 mA; −12 V DC ±5% / 35 mA; and 24 V DC ±5% / 70 mA. Treat each voltage, polarity and current rating separately. These are supply rails for the assembly, not general-purpose outputs for powering an arbitrary printer.

TTY and V.24 / RS-232 connections

The PLC interface is active TTY. The printer interface supports active/passive TTY or selectable V.24 / RS-232C. Select TTY for a TTY printer and V.24 for an RS-232 printer. The S5 interface arrangement and connecting cables must match the electrical configuration.

For V.24, the adapter's 25-pin printer port assigns pin 2 to Ground, pin 5 to RxD/BUSY and pin 11 to TxD. A standard PC serial cable must therefore not be assumed suitable. A USB–RS232 converter alone does not establish the correct pin mapping, TTY conversion or required supply. Follow the complete cable diagram.

Where necessary, match the OP 396 printer parameters using COM 396. In addition to the selector position, the printer interface and communication settings must agree.

Applications with OP 396 and PG 615

The OP 396 manual requires the adapter and power pack for passive TTY printers, V.24 printers, PLC-to-panel distances exceeding 3 m, and connection to the S5-90U, S5-135U, S5-150U and S5-155U. Actual CPU compatibility also depends on the OP 396 operating-system submodule and application.

The PG 615 manual describes the assembly for offline program preparation, storing programs on memory submodules, printer connection and access to a passive AS 511 interface, with the appropriate hardware and software. For PLC programming and EPROM/memory submodule operations, follow the programmer's own module-selection and connection requirements.

Protection, environment and related codes

The power pack is IP20 and the adapter is IP40. The technical table gives approximately 1,100 g for the power pack and 200 g for the adapter. Adapter dimensions are 150 × 65 × 45 mm. The operating range is 0–45 °C, with storage/transport at −20 to +70 °C. Check grounding and connector retention during installation.

6ES5 984-1UA11 and 6ES5 984-1UB11 are different adapter order numbers within the 984 family. The connection arrangement used with an OP 393 also requires separate assessment. Neither the 984 family number nor a similar connector establishes interchangeability with 2UA11.

Editor's note

First establish what is included: the adapter alone, the power pack alone, or the complete assembly with cables. A missing component can prevent otherwise healthy equipment from being used.

Check the label and 220/240 V selection before applying mains power. Keep 2UA11 and 2UB11 distinct, and disconnect power before changing the voltage selection.

Do not judge the power pack from the 5.1 V rail alone. Check the other rails against their correct references and, where practical, examine voltage drop and ripple under a suitable test load.

If the panel works but the printer remains silent, check the TTY/V.24 selector, cable and printer-ready signal first. During fault finding, verify power delivery and data transfer separately.

The adapter's RS-232 pinout must not be treated as a standard PC serial port. Record the old cable's connections before removal; the same connector shape does not mean the same internal wiring.

When buying used Siemens equipment or a used power supply, request the complete 984-2UA11 label, checks on all four rails and a printer communication test with suitable equipment. The delivery record should identify every component included in the tested assembly.

OtomasyonAVM resources and PDFs

Browse the S5-115U PDF archive for family documents and About Siemens S5 PLC for system information. Detailed manufacturer descriptions of this assembly are in OP 396 chapter 12 and PG 615 section 2.2, linked below.

Related topics

+ 6ES5 396-0UA11 OP 396: operator panel used with this assembly.

+ 6ES5 615-0UA11 PG 615: the adapter's other documented application.

+ 6ES5 984-1UA11: a different 984 adapter; not an automatic substitute.

+ 6ES5 984-1UB11: another 984 connection version.

Browse Siemens equipment

Siemens S5 PLC · Siemens HMI · S5 cables · S5 interfaces · S5 additional modules · Used Siemens equipment

Manufacturer documents and external references

+ Siemens OP 396 Operating Instructions – EWA 4NEB 810 1288-02a, English: chapter 12, printed pages 12-1–12-6; PDF pages 57–62. Exact order number, supply rails, interface selection and printer port.

+ Siemens PG 615 Handbuch – 6ES5 998-0UR11, German: section 2.2, printed page 2-18 onward. PG 615 adapter functions and electrical specifications; appendix C lists the exact 984-2UA11 order number.