6ES5 777-0BB00

Siemens 6ES5 777-0BB00 – SINEC L1 BT 777-0 Bus Terminal

Siemens 6ES5 777-0BB00 is a BT 777-0 bus terminal connecting Siemens S5 controllers to a SINEC L1 local area network. The model-specific Siemens data sheet specifies a 1 m connecting cable and a distance of up to 2.5 km. In SIMATIC S5 installations, it provides the physical signal connection between the station's communications hardware and the network cable.

The terminal converts the controller's 20 mA TTY current-loop signals to RS-485 levels on the bus. When reviewing S5 interface modules, distinguish the electrical layer from the communications protocol. Similar cables and connectors do not make a general-purpose RS-485 converter a suitable replacement.

1 m connecting cable and 2.5 km bus section

1 m describes the cable to the PLC/CP. 2.5 km is the maximum section length between two active terminals with the appropriate bus cable. The manufacturer distinguishes short-distance SIMATIC cable from the shielded twisted-pair cables used for longer sections. When choosing S5 connection accessories, assess cable type and routing together with the terminal order number.

5 V supply and the S5-90U distinction

The BT 777 has a nominal 5 V DC supply; the manual lists current consumption of 0.3 A, typically 0.25 A. In a normal CPU/CP arrangement, the interface may supply the terminal; the need for an external supply depends on the connected system. Do not apply 24 V directly.

When connected to an S5-90U, the 0BB00 requires an external supply: C = +5 V and D = reference/0 V. The manual specifies 5.0–5.3 V and 0.3 A. The terminal's external 5 V supply must also switch off when the S5-90U loses power; otherwise network operation can be blocked. For other S5 CPU connections, follow the applicable system wiring diagram.

CP 530, station addressing and data exchange

SINEC L1 operates at 9600 bit/s with one master and up to 30 slaves. The BT 777 provides signal interfacing; the CP 530 performs the master function. Compact processor reference pages include 6ES5 530-3LA11 and 6ES5 530-3LA12; block-type pages include 6ES5 530-7LA11 and 6ES5 530-7LA12. Check the complete CPU/CP revision separately.

No I/O byte address is assigned to the BT 777 itself. Slave numbers, polling lists, send/receive areas and coordination information are defined in the CPU/CP configuration. A communications fault therefore calls for checks of both the physical network and the data exchange in the PLC program, together with the CP state.

Mounting, reference potential and version selection

The terminal can mount on a 35 mm rail or on a flat surface using the housing's fixing holes. It uses a 15-pin connector toward the controller and screw terminals for the incoming and outgoing bus. For the 0B.00 terminal family, the difference between adjacent station reference potentials must not exceed 5 V. Assess shielding and the grounding arrangement together with this requirement.

6ES5 777-0BB01 is a different order number: compare BREAK recognition and, particularly, the S5-90U supply arrangement. 6ES5 777-0BC00 is the 2 m connecting-cable option for a 2.5 km section. 6ES5 777-1BC00 is intended for a 4 km section and has different isolation characteristics. Housing appearance alone does not establish interchangeability.

Editor's note

Read the last two digits on the label carefully. Both 0BB00 and 0BB01 terminals may appear in a Siemens S5 installation. Similar housings do not mean that every CPU supplies them in the same way.

When testing this terminal on an S5-90U, start with the external 5 V supply. Measure at the terminal as well as at the power supply, and check voltage drop through the cable and connections. Also verify what happens to that supply when the CPU switches off.

For intermittent communications, monitor the CPU/CP state and remote station during PLC troubleshooting. Record the existing slave address and network settings before swapping hardware. Changing hardware and configuration together makes fault isolation harder.

When inspecting S5 modules and accessories, remember that this is an active signal device rather than a passive terminal box. Applying 24 V as a quick test or connecting an arbitrary serial cable can damage a working spare.

For a used unit, examine the cable entry, connector pins, screw terminals and rail clip. De-energized continuity checks can reveal mechanical faults, but they do not prove communications performance. Complete the assessment by sending and receiving data in a compatible SINEC L1 arrangement.

For a link between distant cabinets, take reference-potential differences seriously. Do not assign the isolation properties of a different optically isolated terminal to the 0BB00. A sound terminal still needs the correct supply and network wiring.

OtomasyonAVM resources and PDFs

Review About Siemens S5 PLC, S5 communications modules and S5 cables and connectors together.

+ OtomasyonAVM S5 PDF archive: Use the SINEC L1 / CP 530 manual alongside the relevant CPU documentation.

+ S5-90U PDF files: Section 14.1 of the S5-90U/S5-95U manual is important for the supply distinction between 0BB00 and 0BB01. The manufacturer documents below are in English.

Related topics

+ 6ES5 777-0BB01: Other 1 m cable version with BREAK recognition; compare supply requirements separately.

+ 6ES5 777-0BC00: 2 m connecting cable and 2.5 km bus section.

+ 6ES5 777-1BC00: BT 777-1 option for a 4 km bus section.

+ 6ES5 530-7LA11: SINEC L1 CP 530 communications processor.

Browse SIMATIC S5

S5 accessories · S5 communications modules · SIMATIC S5 · Siemens S5 PLC · Used Siemens equipment

Siemens and external references

+ Siemens SINEC L1 / CP 530 Manual — 6ES5 998-7LA21, English: Printed pages 1-5–1-9 and 4-4; signal conversion, supply, potential differences, cabling and exact order number.

+ Siemens S5-90U/S5-95U System Manual — EWA 4NEB 812 6115-02b, English: §14.1, printed page 14-2; external 5 V supply and coordinated shutdown for the S5-90U.

+ Siemens 6ES5777-0BB00 data sheet, English, 27 September 2019: Third-party archive copy of the manufacturer document; confirms the 1 m cable and 2.5 km model description.