6ES5 777-1BC00
6ES5 777-1BC00 – BT 777-1 SINEC L1 Bus Terminal
Siemens 6ES5 777-1BC00 is a BT 777-1 bus terminal for SINEC L1 networks in SIMATIC S5 installations. It converts the controller or communications processor's 20 mA TTY signals to RS-485 signals on the bus. SINEC L1 operates at 9600 bit/s; with suitable cable, the segment between two active terminals can extend to 4 km.
The terminal provides the station's physical connection to the network. Within the S5 communication system, a CP 530 handles master coordination; the 6ES5 530-3LA12 CP 530, for example, is a separate communications processor. A SINEC L1 network supports one master and up to 30 slaves. Installing a BT 777-1 does not complete the CPU and CP configuration.
Segment distance and electrical isolation
The 4 km rating applies between two active BT 777-1 terminals. Siemens specifies up to 50 km total bus length for an appropriately designed network. Both limits depend on cable characteristics and active-terminal placement. When selecting S5 bus cables, use the specified four-core shielded construction and suitable twisted pairs for long distances; 4 km is not available with every cable type.
The 1BC00 version has optical isolation at its input. With normal PLC/CP power, the Siemens selection table specifies 500 V RMS between input and output and between input and power supply. This does not remove the need for correct shielding and grounding when working with S5 interface connections.
Bus and controller connections
The PLC/CP connection uses a 15-pin D-sub/Cannon connector. Bus conductors connect to screw terminals on both sides of the housing. The receiving pair from the left-hand neighbour connects to 1A–2A, while the transmitting pair to that neighbour uses 3A–4A. On the right, 1B–2B is the transmitting pair and 3B–4B the receiving pair.
0A and 0B are cable-screen terminals. Check pair direction and polarity against the cover diagram and Figure 1-14 in the Siemens manual. For the standard BT 777 arrangement, the manual states that separate bus terminators at the two end stations are unnecessary; do not add resistors based solely on generic RS-485 practice.
Power, mounting and station bypass
The specified supply is 5 V DC ±5%, with 0.3 A current consumption, typically 0.25 A. Normal station connections receive power through the PLC/CP. Externally powered bus-driver or repeater applications use C: +5 V and D: 0 V, with the relevant jumper arrangement defined in the manual. When checking S5 power supplies, verify the terminal's 5 V supply separately.
The housing measures 115 × 150 × 38 mm and can clip onto a 35 mm DIN rail or be screwed to a flat mounting surface. Although grouped with S5 modules, it connects to the station by cable rather than plugging into the PLC rack, as is common with S5 accessories.
An internal relay with four normally closed contacts bypasses the terminal electronics if the station connector is removed or terminal power is lost. Communication between the remaining stations can therefore continue. However, the combined cable distance between the remaining active terminals must be checked again; relay bypass alone is insufficient if the resulting segment exceeds 4 km.
Other BT 777 versions and system matching
For the 0B.00 group, including 6ES5 777-0BB00 and 6ES5 777-0BC00, Siemens specifies a 2.5 km segment limit. Do not transfer the 1BC00's 4 km and optical-isolation specifications to that group. Also retain the full suffix when comparing 6ES5 777-0BB01, 6ES5 777-0BC01 and 6ES5 777-1BC01; a similar housing does not establish interchangeability.
When reviewing the SIMATIC S5 CPU system and S5 CPU families, establish the station's master/slave role and intended port. SINEC L1 interface submodules such as 6ES5 752-0AA62 and 6ES5 752-0LA62 are separate parts selected for the applicable CPU and revision. The BT 777 terminal alone does not establish their CPU compatibility.
Editor’s Note
When buying used Siemens equipment, ask for more than a photograph of the housing. Check the 1BC00 label, wiring diagram inside the cover, connector and complete cable. Cracks or crushing at the cable outlet can cause problems even when the terminal looks tidy.
Separate power faults from communication faults. This terminal expects 5 V; finding 24 V elsewhere in the cabinet does not establish a correct supply here. Inspect connections with power isolated, then measure against the correct reference.
The bypass relay is part of the test. On a controlled short test network, check communication with the terminal powered and observe the remaining stations when its supply is removed. A clicking relay alone does not prove correct bypass operation.
Photograph the A/B sides and pair directions before disconnecting conductors. Cable colours may vary between installations. Trust the terminal numbers and wiring diagram rather than a remembered colour sequence.
For Siemens S5 fault tracing, establish communication with a known good short cable before introducing the long field cable. If the fault remains, check the CP configuration and station list as well. Avoid experimenting by disconnecting a production network; record the CPU, CP and cable used for each test.
OtomasyonAVM resources and PDFs
Browse S5 accessories for the terminal family, S5 communication modules for station-side equipment and S5 cables and connectors for the connection hardware.
+ Shared SIMATIC S5 PDF and system manual archive. The English Siemens SINEC L1 manual containing this exact order number and its connection tables is linked below.
Related topics
+ CP 530 communications processor and S5 interface modules.
+ Grounding and cable-screen connection principles.