6ES5 420-8MA11

6ES5 420-8MA11 – SIMATIC S5 4-Channel 24 V DC Digital Input Module

Siemens 6ES5 420-8MA11 is a 4-channel, 24 V DC digital input module without galvanic isolation for S5-90U, S5-95U and S5-100U controllers, and ET 100U/ET 200U distributed I/O systems. Within the S5 digital input module range, this Siemens S5 module serves small groups of signals sharing a common reference.

It transfers the states of pushbuttons, limit switches, compatible sensors and contactor auxiliary contacts to the PLC. Assess the four physical inputs, channel indicators and the red F LED indicating loss of the L+ supply together during field checks.

Input voltage and sensor outputs

Rated input voltage is 24 V DC. The specified levels are 0–5 V for logic 0 and 13–33 V for logic 1. Do not use the intervening range as a stable operating level. Check the power supply and NPN/PNP sensor output against these thresholds and the M reference.

Active input current at 24 V is typically 7 mA. Two-wire BERO proximity switches can be connected; the manual specifies a 1.5 mA residual-current value. When connecting an inductive sensor or photocell, verify that off-state leakage does not leave the input at logic 1.

L+, M and channel connections

The manufacturer’s diagram assigns terminal 1 to L+ and terminal 2 to M. The terminal pairs are 3–4 for channel 0, 5–6 for channel 1, 7–8 for channel 2 and 9–10 for channel 3. In the illustrated contact circuit, 3/5/7/9 distribute L+, while 4/6/8/10 are the signal inputs. Match S5 connection hardware to the terminal numbering printed on the module.

The module is non-isolated, so assess the field reference and the system’s potential arrangement together. Distinguish M from protective grounding. If all inputs are affected, inspect the shared connections before testing individual channels.

Input delay and cable length

Inherent delay is typically 2.5 ms for 0→1 and 5 ms for 1→0; the times depend on voltage. Consider the PLC program and scan time when assessing short pulses. During troubleshooting, follow the contact state, channel indicator and program input bit together.

The manufacturer specifies a maximum unshielded cable length of 100 m. Also assess voltage drop, cable routing and switching interference. An unloaded voltage measurement alone does not establish that a long signal circuit will operate correctly.

Addressing and channel numbering

In a local S5-100U configuration, the digital address is determined by the module slot and channel number. For example, channel 2 in slot 3 is I3.2, or E3.2 in German notation. Match the module’s position in the SIMATIC S5 installation to the machine configuration.

The paired front markings .0/.4, .1/.5, .2/.6 and .3/.7 do not indicate eight physical inputs. The four channels use .0–.3 in the S5-100U; ET installations require checking the station’s addressing scheme. Use the actual address list for S5-90U and other CPU configurations as well.

Bus unit, supply and mechanical checks

The module plugs onto a bus unit carrying the fixed field wiring. Inspect the terminal block, coding element and rear contacts during replacement. Typical consumption from the internal +9 V supply is 16 mA; typical power loss is 0.8 W, and approximate weight is 205 g.

Differences from related modules

6ES5 421-8MA12 has eight inputs, while 6ES5 422-8MA11 has sixteen. Check the 422’s addressing arrangement separately. A higher channel count does not establish compatibility with the existing slot assignment and program.

When comparing 6ES5 430-8MB11 or 6ES5 431-8MA11, assess isolation, voltage range, channel count and terminal arrangement together. The defining features of the 420-8MA11 are four channels, 24 V DC and a shared-reference input circuit.

Editor’s note

Start with the full label on this S5 module: 420-8MA11, four inputs, 24 V DC. The additional .4–.7 markings can be misleading at first glance. Follow the four physical channels rather than assuming there are eight.

If the red F indicator is lit, check the L+ supply first. Before condemning the module, inspect the supply at terminals 1 and 2, the wiring and terminal contacts. Channel testing can lead you astray while a supply fault remains unresolved.

Read the front diagram before wiring contacts to 3–4, 5–6, 7–8 and 9–10. Do not infer terminal functions from old wire colours. Photograph the wiring before removal so the L+ distribution points and signal inputs remain clearly identified.

If a two-wire sensor is off but the input bit remains on, check before replacing it. Assess leakage current and the voltage remaining at the module input together. A sensor indicator or a single meter reading cannot establish that the complete circuit is correct.

When buying a used Siemens module, ask for all four channels to be tested in both switching states. Inspect the bus-unit contacts, terminal screws and locking mechanism too. Isolate power before replacement; understanding the connections first makes even a small input-module repair easier.

OtomasyonAVM resources and PDFs

+ S5 digital input modules · S5-90U main page · S5 cables and connection hardware.

+ S5-90U / S5-95U PDF files. The exact 420-8MA11 circuit and specification table appear on printed page 15-13 / PDF page 377 of the English system manual.

+ Shared PDF archive for other S5 systems. The same module appears on 14-16 / PDF 366 in the S5-100U manual and 2-14 / PDF 28 in the ET 100U manual.

Related topics

+ 421-8MA12 · 422-8MA11 · 430-8MB11 · 431-8MA11.

+ NPN versus PNP · PLC troubleshooting · S5 digital output modules.

Browse SIMATIC S5

S5 digital inputs · S5-90U · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand main page.

Siemens and external references

+ Siemens S5-90U/S5-95U System Manual, EWA 4NEB 812 6115-02b, Edition 03, English; 15-13: exact 420-8MA11 circuit, input levels, delays and consumption.

+ Siemens S5-100U System Manual, EWA 4NEB 812 6120-02b, Edition 04, English; 14-16: exact module specifications; 3-14: four-channel wiring; chapter 6: addressing.

+ Siemens ET 100U Distributed I/Os Manual, EWA 4NEB 812 6040-02a, English; 2-14: 420-8MA11 specifications and 4DI designation for ET 100U.