6ES5 525-3UA11

The Siemens 6ES5 525-3UA11 is a CP 525 serial communications processor for SIMATIC S5 systems. Siemens lists it for links to PLCs, minicomputers and printers. This order number identifies the CP/M-86 version from the PG 675 generation. The front panel has two 25-pin D-Sub connections.

This S5 communications board handles point-to-point data exchange between the controller and external equipment. When selecting a spare, check the physical serial interface, the partner device’s protocol and the software used to create the CP project.

PG 675, S0/S1 and the COM 525 version

The S0/S1 notation in the data sheet refers to the STUDOS software environment on the PG 675. The 3UA11 communications project requires CP/M-86 COM 525. Siemens states that projects created in that environment cannot be edited in S5-DOS COM 525 or converted directly.

The 6ES5 525-3UA21 is listed for the S5-DOS environment. When buying a replacement, match the board’s order number to the existing project disk or archive. The CP 525 name covers more than one programming environment.

Serial connection and partner settings

Before selecting a D-Sub cable, identify the fitted interface and confirm the S5 cable pinout. V.24/RS-232, TTY current loop and other serial interfaces use different electrical connections. Record the baud rate, data bits, parity and stop bits from the working installation.

Siemens covers applications such as RK 512 and 3964(R) in the CP family documentation. For a 3UA11 in service, confirm the actual procedure in the existing CP/M-86 project. The CP 524 3UA13, CP 524 3UA15 and external-modem TK 858 link have their own hardware and cable documentation.

Restart behaviour in the S5-115U

Siemens names the 6ES5 525-3UA11 in the S5-115U communications chapter. For an S5-115U central rack using an event printer with group-disable bits or a 3975 display with bit set/reset commands, the manual describes clearing the enabled IPC flag area during RESTART. If a fault occurs only after a restart, review the CPU startup sequence and CP synchronisation together.

Editor’s note

Photograph the full order number and hardware revision. Make sure the 3UA11 suffix is visible. Boards with similar front-panel markings can belong to different COM 525 environments.

Keep the CP project as a separate backup. Retain the CP/M-86 COM 525 archive alongside the PLC program. Photograph the order number of any fitted memory submodule.

Label each cable by its destination. Record which one goes to the printer, computer or other PLC. Keep the pinout and serial settings with the cable record.

Observe the first startup separately. If communications work during normal operation but fail after power returns, check the restart logs. The existing IPC configuration matters in installations with an event printer or a 3975 display.

Ask how the spare was tested. When buying a used communications board, ask which interface and programming environment were used and whether memory and interface submodules are included.

OtomasyonAVM references and PDF archive

Browse the Siemens S5 PLC section for model pages and the OtomasyonAVM S5 PDF page for published series manuals. The 3UA11 data sheet and the Siemens CP/M-86 version note are linked under External references.

Related topics

To compare rack and processor order numbers, see the S5 rack index and the hardware pages for the S5-135U, S5-150U and S5-155U CPU 948.

Site navigation

Siemens Automation › Siemens S5 PLC › S5 communications modules

External references

Siemens 6ES5525-3UA11 data sheet (English PDF) · Exact order number, CP 525 product identification and PG 675 reference.

Siemens S5-R01V technical document (German PDF) · Section 3 explains the 3UA11 CP/M-86 programming environment and the project conversion limitation.

Siemens S5-115U system manual (English PDF) · Chapter 12 covers the 3UA11 RESTART and IPC flag note.