6ES5 373-0AA81
Siemens SIMATIC S5 6ES5 373-0AA81 128 KB NMOS EPROM Memory Submodule
The Siemens 6ES5 373-0AA81 is a long-format NMOS EPROM in the 373 memory submodule family for SIMATIC S5. It stores 128 KB, equivalent to 64 K 16-bit words. In an S5-155U, it fits the 6ES5 355-3UA11 memory carrier to expand user program storage for a CPU 946 or CPU 947.
The WF 470 display module uses the same EPROM to store screens and text. The 373-0AA41 holds 32 KB and the 373-0AA61 holds 64 KB. The 373-1AA81 also holds 128 KB, and uses CMOS EPROM. Siemens lists it as 0463 in the WF 470 programming table.
355 carrier and CPU compatibility
Siemens lists up to three long-format memory submodules per 355 carrier. In an S5-155H, the same carrier provides user program memory for the CPU 946R and CPU 947R. Record the carrier slot and the position of each submodule before removal.
Check the CPU family and suffix together when selecting memory. For older CPU 928 installations in the S5-135U, Siemens specifies short-format 376 EPROMs. The 374 series Flash EPROM cards used with the CPU 948 belong to a separate memory family. Match the carrier and CPU as well as the physical format.
WF 470 sockets and programming number
Siemens lists the 373-0AA81 in the X10, X20 and X30 memory sockets of the WF 470 with programming number 0163. The same table gives separate numbers for the 32 KB CMOS 373-1AA41 and 64 KB CMOS 373-1AA61. The WF 470 A and B require at least one RAM submodule for commissioning. The WF 470 C has built-in CMOS RAM for this purpose.
Reading and programming the EPROM
Use a SIMATIC S5 programming device with the appropriate module socket or a compatible EPROM programmer. The Siemens STEP 5 EPROM/EEPROM example selects 163 and WORD for the 373-0AA81. The 355 carrier manual calls this word mode WORD/FIELD. The WF 470 picture generation software uses programming number 0163.
Read the EPROM into a file before changing it and compare the programmed contents with the source afterward. For an online CPU backup, check the S5 PG cable and connectors separately. This UV-erasable EPROM retains its contents without power and uses a different erase process from Flash and EEPROM memory.
Editor’s note
Check the 373-0AA81 label and the 128 KB capacity together. The 1AA81 has the same capacity and a different programmer setting.
Record the 355 carrier and CPU codes or the WF 470 version and X10/X20/X30 socket. Isolate the chassis supply before removing the submodule.
On a used unit, keep the EPROM contents and any backup from the running system in separate files. Verify that the EPROM copy can be read before UV erasure.
If the CPU stays in STOP after a memory change, check the carrier slot, submodule order and STOP indicator. Siemens notes that a startup fault may cause INITFAULT to flash on the CPU 947.
When buying a used unit, ask for a read test using programming number 163 and a photo of the label. If you need a blank module, ask for a programmer blank check.
OtomasyonAVM resources and PDFs
+ SIMATIC S5 memory submodules · Siemens SIMATIC S5 PLC overview
+ SIMATIC S5 PDF archive · S5-115U manuals
Related topics
+ 6ES5 373-0AA41 32 KB EPROM · 6ES5 373-0AA61 64 KB EPROM · 6ES5 373-1AA81 128 KB CMOS EPROM
S5 navigation
+ S5 memory cards · SIMATIC S5 · Siemens S5 PLC
External references
+ Siemens S5-155U CPU 946/947 manual · 355 carrier and 373-0AA81
+ Siemens WF 470 Technical Description · Memory sockets and programming numbers
+ Siemens STEP 5 manual · 373-0AA81 programming example (DE)