6ES5 946-3UA11

Siemens 6ES5 946-3UA11 – SIMATIC S5-155U CPU 946

Siemens 6ES5 946-3UA11 is a CPU 946 central processor module for the SIMATIC S5-155U system. The Siemens manual lists this exact code under the CPU 946/947 family. When maintaining Siemens S5 and SIMATIC S5 equipment, record the complete 3UA11 suffix, version and accompanying hardware.

CPU 946 and CPU 947 operate together and cannot function individually. CPU 946 handles processing, while CPU 947 provides memory and interface functions. Check the label on the accompanying 6ES5 947-3UA11 module. A replacement quotation should clearly identify whether it covers an individual module or the processor assembly.

Order Number and Version Differences

Assess later references such as 6ES5 946-3UA21, 6ES5 946-3UA22 and 6ES5 946-3UA23 separately. The manual’s hardware design section explicitly identifies these later codes. A shared family name alone is insufficient to establish identical jumper settings, electrical ratings or replacement procedures.

6ES5 946-3UR21 is a CPU 946R reference for the S5-155H. Use the installed system’s labels and hardware list when distinguishing UA and UR versions. Front-panel appearance alone is insufficient for selecting a suitable spare.

Rack, Supply and Connection Checks

CPU 946 is double-width in the classic S5-155U arrangement. Check the existing S5 rack and chassis together with the S5 power supply. Photographing module positions before removal helps prevent incorrect placement or an incomplete processor assembly during reinstallation.

Inspect rear connectors, guide rails and locking parts, and record the condition of S5 cables and connectors and S5 interface modules. Investigate suspected supply or connection faults against the relevant drawings. Verify documentation for the exact hardware version before applying settings from a neighboring model.

Program, Memory and Communication

Preserve the STEP 5 program and system settings. Record installed S5 memory modules and secure an up-to-date backup before PLC programming or debugging. Any stated memory capacity should identify whether it applies to the CPU 946/947 assembly and which additional memory hardware is included.

Assess existing S5 communication modules, the programmer connection and cables separately. If a 6ES5 923-3UC11 coordinator is installed, document the rack’s operating arrangement before changing processor hardware. Keep the settings for single-processor and multiprocessor installations clearly identified.

A proposed change involving references such as 6ES5 947-3UA21 or 6ES5 948-3UA11 requires assessment of the program, hardware and versions together. See the Siemens S5 PLC overview for system background. Supply label photographs, fault symptoms and details of the installed assembly when sourcing a spare.

Editor’s Note

Treat 946 and 947 as a processor assembly when sourcing parts. If you are buying only the 946 module, provide the supplier with the installed 947 order number and version.

Read the complete 3UA11 suffix from the actual unit. Request clear photographs of its label, front panel and rear connectors rather than relying on a generic CPU 946 image.

Secure the current program backup and photograph the rack before removal. An isolated module on the bench cannot establish the condition of the complete PLC assembly.

If the system will not enter RUN, check the supply, memory, accompanying 947 and connections in sequence. A poor contact can resemble a more expensive processor fault.

Do not transfer jumpers blindly when changing hardware versions. Compare the documentation for the complete order numbers first; clear records make subsequent maintenance much easier.

Documentation and PDF Archive

Browse further S5 documentation in our S5-115 PDF archive. The Siemens manual pages below identify the exact order number and explain the CPU 946/947 assembly.

Related Topics and Nearby Models

6ES5 947-3UA11 · 6ES5 946-3UA21 · 6ES5 946-3UA22 · 6ES5 946-3UA23. These links support assembly and version comparison; verify replacement suitability against the installed hardware.

Siemens S5 Navigation

Used Siemens products · Siemens S5 main page · S5 function modules · Racks and chassis · Memory modules · Communication modules

External References

Siemens S5-155U CPU 946/947 Manual – 6ES5 998-0UM22, Release 07: PDF page 3, documentation assignment for the exact order number.

Siemens central-controller hardware description: PDF pages 70–72, assembly structure and joint operation requirement.