6ES5 498-1AA11

Siemens 6ES5 498-1AA11 SIMATIC S5 Four-Channel mV and Pt100 Range Card

The Siemens 6ES5 498-1AA11 is a four-channel through-connection range card for SIMATIC S5 460 and 465 analog input modules. It supports ±50 mV, ±500 mV and Pt100, depending on the host and its settings. The ±12.5 mV range uses the 50 mV setting with ×4 gain on hosts that support it, including the 460-4UA12 and 460-4UA13.

The card routes a low-level analog voltage signal or the Pt100 sense leads to the host inputs. The host module converts the signal to a digital value. If the reading is wrong after a replacement, check the card suffix, its four-channel group and the host’s range setting together.

Which 460 and 465 modules accept it?

For the S5-115U family, Siemens ST 50 lists the card with the 460-7LA13 and 465-7LA13 for ±50 mV, ±500 mV and Pt100. The catalog also lists the 460-7LA13 for the S5-115F. The S5-135U/155U system manual covers the 460-4UA13, 465-4UA12 and 465-4UA13. For earlier versions such as the 460-4UA11 and 465-4UA11, refer to the relevant peripheral module table.

The 460 has two range card slots and the 465 has four. Each card serves four inputs. The 465 provides 16 voltage or current inputs, or eight Pt100 inputs. On a 460-4UA13 in 500 mV mode, for example, CH0–CH3 can measure ±500 mV with a 1AA11 while CH4–CH7 measure ±10 V with a 498-1AA31.

How do Pt100 wiring and wire-break detection work?

Pt100 sensors and thermocouples use different wiring arrangements. In the 460-4UA13 Pt100 diagram, the host supplies 2.5 mA to the Pt100 sensors through IC+ and IC−. The channel measures voltage at M+ and M−. Wiring for unused inputs can differ between the full and low Pt100 ranges.

The 1AA11 allows hardware wire-break detection on host modules that support it. During PLC troubleshooting, check whether detection is enabled for the channel group and inspect the front connector jumpers. Siemens’ S5-135U/155U manual calls for shorting unused 465 inputs, while the earlier U Periphery manual allows unused inputs on the 465-4UA12 to remain open. Follow the wiring diagram for the installed host version and operating mode.

What changes across the 498 suffixes?

With the host in 500 mV mode, the 498-1AA21 is for ±1 V, the 498-1AA61 is for ±5 V and the 1AA31 is for ±10 V. For current signals, the 498-1AA41 is for ±20 mA, the 498-1AA51 for two-wire 4–20 mA and the 498-1AA71 for four-wire 4–20 mA. The similarly numbered 498-1AB11 is a contact suppression submodule for the 458 relay output module.

Editor’s note

Record both order numbers. Note the 498-1AA11 suffix and the full code of the 460 or 465 that holds it.

Mark the channel group. Record the signal assigned to each group before isolating power. Label the card slot during removal.

Record the gain setting. On a module using ±12.5 mV, photograph both the 50 mV selector position and the ×4 gain setting.

Identify the Pt100 terminals. Mark the excitation terminals, sense terminals and unused-channel jumpers separately at the front connector.

Check the first reading. Apply a known mV signal or use a suitable Pt100 simulator. Compare the raw value, then confirm that the PLC program uses scaling for the selected range.

OtomasyonAVM resources and PDFs

+ SIMATIC S5 analog input and output modules

+ SIMATIC S5-115 460-7LA13 analog input module · 465-7LA13 analog input module

+ OtomasyonAVM SIMATIC S5-115 PDF archive

+ SIMATIC S5-115H system manual, Figure 7-8, Pt100 wiring on the 465

Related topics

+ 6ES5 498-1AA21 ±1 V · 6ES5 498-1AA31 ±10 V · 6ES5 498-1AA41 ±20 mA

+ 6ES5 498-1AA51 two-wire 4–20 mA · 6ES5 498-1AA71 four-wire 4–20 mA

If you have a 6ES5 498-1AA11 to sell, send the label photo, quantity and test status to otomasyonavm@gmail.com.

Browse the S5 range

SIMATIC S5 analog modules · Siemens SIMATIC S5

Siemens and external references

+ Siemens 6ES5 498-1AA11 data sheet

+ Siemens S5-135U/155U system manual, 460 range and gain table, p. 9-33

+ Siemens S5-135U/155U system manual, 465 range card layout, p. 9-75

+ Siemens U Periphery manual, 465-4UA12 range cards and unused inputs, §5.5.3

+ Siemens ST 50 catalog, 460-7LA13 and 465-7LA13 ordering table, p. 3/47