6ES5 470-7LA13

Siemens 6ES5 470-7LA13 SIMATIC S5 8-Channel ±10 V and 0–20 mA Analog Output Module

The Siemens 6ES5 470-7LA13 is an eight-channel, galvanically isolated analog output module for SIMATIC S5. Each channel provides ±10 V voltage and 0–20 mA current terminals. The module uses a 24 V DC field supply and a 46-pin front connector. The Siemens data sheet lists S5-115U/F, and the ST 50 ordering table covers the S5-115U/H/F family.

The module converts PLC output words into references for drives, proportional valves and other receiving devices. The QV voltage and QI current terminals on a channel follow the same output word. For example, connect a drive with a ±10 V reference input to QV, or a receiver with a 0–20 mA input to QI. All eight channels share the MANA reference.

Field supply, load and front connector

The L+ and L− terminals take the 24 V DC field supply. For resistive loads, use at least 3.3 kΩ on QV and no more than 300 Ω on QI. Siemens ST 50 lists a 1 ms conversion time for the 470-7L.13 family.

The 46-pin front connector options include the 490-7LB21 screw-terminal connector, 490-7LA11 crimp connector supplied with contacts and 490-7LA21 crimp connector supplied without contacts. Siemens also lists the 490-7LC11 spring-clamp connector. Use the ST 50 connector drawing for the exact order number when mapping the wiring.

Wiring QV, QI and the sense jumpers

Connect a voltage load between the channel’s QV terminal and MANA. Run S+ and S− to the respective load terminals to sense the voltage at the load. Connect a current load between the channel’s QI terminal and MANA.

Siemens Figure 10-28 calls for QV–S+ and S−–MANA jumpers on unused voltage outputs. This also applies to channels wired for current only. Leave unused QI terminals open.

STEP 5 addressing and scaling

The module occupies one slot, and its base address follows the rack and slot layout. Eight channels use two bytes per channel, for a total of 16 output bytes. The 12-bit two’s-complement value is left-justified in the word. At positive full scale, +1024 units correspond to +10 V on QV and 20 mA on QI.

What should you check on S5-115U, H and F systems?

On S5-115U systems with a CPU 944 or CPU 945, use the installed CR 700-2 central rack and ER 701-1 expansion rack layout to identify the slot and base address.

On an S5-115H system with a CPU 942H and ER 701-3H, redundant operation of the 470 analog outputs requires additional hardware circuitry. Section 4.4.1 of the H manual in the OtomasyonAVM S5-115 PDF archive describes the arrangement. For S5-115F systems with a CPU 942F, Siemens treats the 470-7LA family as a Type 18 analog output for non-safety functions.

How do the LA, LB and LC versions differ?

The 470-7LA11 and 470-7LA12 also use ±10 V and 0–20 mA. The 470-7LB11, 470-7LB12 and 470-7LB13 provide ±10 V voltage outputs. The 470-7LC11, 470-7LC12 and 470-7LC13 use 1–5 V and 4–20 mA. Match the order number, connector wiring and PLC scaling when choosing a spare.

Editor’s note

Look for 7LA13 on the label. In a project scaled for 0–20 mA, the LC series’ 4 mA lower limit shifts the receiving device’s zero reference.

Record the jumpers before removing the connector. Photograph the channel numbers, QV–S+ and S−–MANA jumpers, and each load return.

Check shared points when several channels drift. Start with the 24 V DC supply and MANA return. Then compare the PLC output words with the measured signals.

Trace the load and sense wiring when one channel drifts. On QV, check S+ and S−. On QI, check the total load resistance and the return path.

Verify the scale after replacement. With the field load disconnected, use a suitable test load to check zero and a known command within the range. Compare the reading with the programmed channel and output type.

OtomasyonAVM resources and PDFs

SIMATIC S5 analog input and output modules · SIMATIC S5 mounting racks

OtomasyonAVM SIMATIC S5-115 PDF manual archive · SIMATIC S5-115H system manual, analog I/O configuration (English PDF)

Related topics

470-7LA12 ±10 V and 0–20 mA · 470-7LB13 ±10 V · 470-7LC13 1–5 V and 4–20 mA

Browse SIMATIC S5

Siemens SIMATIC S5 · S5-115U CPU family · S5 analog modules

Siemens and other external references

Siemens S5 to S7-1500 migration guide, 6ES5 470-7LA13 model entry (English PDF)

Siemens ST 50, 470-7L.13 specifications and 46-pin connector (English PDF)

Siemens S5-115U system manual, Figure 10-28 wiring and jumpers (English PDF)

Siemens S5-115F system manual, Type 18 analog outputs (English PDF)