6ES5 944-7UA22
Siemens 6ES5 944-7UA22 – CPU 944A, 96 KB RAM and Two Serial Interfaces
Siemens 6ES5 944-7UA22 is a CPU 944A central processing module for SIMATIC S5-115U systems. It provides 96 KB of internal user RAM and two serial interfaces. This S5 CPU executes the STEP 5 program while supporting PG, operator device and suitable serial communication connections. Assess the second interface’s functions against the fitted operating system module.
Differences from related CPU numbers
6ES5 944-7UA12 has one serial interface; 944-7UA22 has two. 6ES5 944-7UB11 and 6ES5 944-7UB21 belong to the CPU 944B family. The shared 944 designation does not establish identical specifications or system modules. Record the full order number, revision and operating system module when selecting a replacement.
User memory and EPROM
When selecting S5 memory modules, distinguish internal RAM from a nonvolatile program copy. CPU 944 executes the program in internal RAM; EPROM/EEPROM contents are copied into RAM. Fitting a memory submodule such as 6ES5 375-0LA41 does not add its capacity to the working RAM. Check the submodule capacity and whether its program is current.
SI1 and SI2 connections
The serial connections use 15-pin, 20 mA TTY current loop interfaces. Select the S5 connecting cable and interface converter for this electrical arrangement. Identify SI1 and SI2 from their markings and record which port serves the existing PG or operator connection before disconnecting it. A matching connector alone does not establish RS-232 compatibility.
For industrial communication, the SI2 protocol is particularly important: the manual specifies an ASCII driver with operating system module 816-1AA11 and 3964(R) with 816-1AA21. Read this module number when replacing S5 communication equipment. Simultaneous PG operations across both ports can also be restricted; successful reading through a port does not establish that every write function is available.
Supply and system installation
The CPU draws 0.65 A typical from the internal 5 V supply. Siemens application hardware for this exact CPU includes the 6ES5 951-7LD12 power supply and 6ES5 700-2LA11 central rack. Include other module loads when checking the existing S5 rack and supply arrangement. CPU program resources include 128 timers and 128 counters; these are not physical input/output channels.
Use with an external communications processor
Siemens uses this CPU with a 6ES5 544-3UA11 CP 544 in its S5–S7-1500 serial communication example. Connection and protocol settings in that example apply to CP 544 and must not be transferred directly to the CPU’s SI2 port. Record the CPU program, communications processor and partner device settings separately.
Commissioning and program preservation
Prepare a backup of the STEP 5 project and required data blocks before PLC programming. During PLC debugging, assess RUN/STOP status, fault indicators, PG diagnostics and interface behaviour together. For Siemens S5 PLC maintenance, keep the memory module, operating system module and CPU order numbers in the same service record. Plan program preservation before clearing memory or working on the battery.
Editor’s Note
When buying used Siemens equipment, check the 7UA22 label and both ports. Do not accept the single-interface version as the same item. Request a photograph of the operating system module as well; that small component can determine communication functions.
Reading through SI2 without being able to write does not automatically indicate a faulty connector. The operating system version and PG activity on the other port can restrict functions. Compare the selected port and module number with the manual before diagnosing a hardware fault.
An installed EPROM does not establish that it contains the latest program. Working RAM may hold more recent changes. Back up the program and machine-specific data blocks before removal, and identify the current copy by date and machine name.
Test both ports separately with the correct cable. Place the machine in an appropriate state before disconnecting an HMI or communication link, and label its original connection. Afterwards, verify operator device operation as well as PG access.
Confirm whether the CPU, operating system module and EPROM are included. Parts may have been exchanged between housings, so appearance alone is insufficient. Complete testing in a suitable setup with program execution, data access and restart checks.
OtomasyonAVM resources and PDFs
+ S5-115 PDF files. Use the manual covering CPU 941A–944A for this model; do not transfer CPU 944B ratings directly.
Related topics
+ 6ES5 944-7UA12 · 6ES5 944-7UB11 · 6ES5 944-7UB21 · 6ES5 375-0LA41 · 6ES5 544-3UA11
Browse SIMATIC S5
+ S5 CPU models · S5 memory modules · S5 connecting cables · S5 communications modules · Siemens SIMATIC S5
Siemens and external references
+ Siemens S5-115U CPU 941/942/943/944 Gerätehandbuch – 6ES5 998-0UF12, Edition 03. Section 15.2.3, PDF page 469: exact 944-7UA22 specifications; Table 4.2: SI2 functions and operating system requirements. German-language manual.
+ Siemens Serial Communication between SIMATIC S5 and S7-1500 – 109748699. Application using 944-7UA22 and CP 544; assess separately from the CPU’s integrated interfaces.