6ES5 923-3UC11
Siemens 6ES5 923-3UC11 – S5-135U/155U 923C coordinator module
Siemens 6ES5 923-3UC11 is a 923C coordinator module for SIMATIC S5-135U and S5-155U. In a Siemens S5 PLC system, it coordinates access to the shared S5 bus by two to four CPUs, provides interprocessor data exchange and central programmer access. It is not a CPU that executes the user program.
Its three main functions are bus arbitration, mailbox/IPC memory and PG multiplexing. In a suitable multiprocessor arrangement, each CPU executes its own program while the coordinator assigns access to the common bus.
CPU coordination and I/O assignments
The manual describes operation with processors such as CPU 922, CPU 928B and a suitable S5-155U CPU 946 / CPU 947 assembly. CPU count and programmer-access target count are different: arbitration covers two to four CPUs, while PG MUX accesses the serial interfaces of up to eight modules.
Assess digital-input, digital-output and analog I/O assignments together with the relevant CPU programs and address lists. A STEP 5 programming backup should preserve the multiprocessor configuration alongside CPU blocks.
Mailbox and IPC memory
The IPC flag area occupies F200H–F2FFH, providing 256 bytes / 2048 bits. The manual describes masking this area in 32-byte groups. If a CP uses the same IPC area, configure the corresponding coordinator group to avoid overlapping use.
The mailbox also contains four 1 KB page frames for exchanging data blocks. Their page numbers FCH, FDH, FEH and FFH are fixed and must not be assigned to other CP/IP modules in the same system. This memory is not additional user-program RAM for the CPUs.
PG multiplexer and serial connection
The front panel has a 15-pin TTY programmer connection; the manual specifies a serial rate of 9600 bit/s. Use the appropriate S5 programming cable. The multiplexer reaches the selected module's serial interface through the backplane connections.
A module being accessed through PG MUX must not simultaneously use its own front programmer connector. Check the interface arrangement and communication processors together. Eight PG targets do not mean eight CPUs operating simultaneously in multiprocessing.
DIP switches and address example
In the C349-06 manual, S1 sets coordination/CPU count, S2 sets the PG base address and S3 enables PG MUX targets. These settings are not field-I/O start addresses. Check PG target addresses and physical slot assignments against the drawing for the installed rack.
Example: with PG base address 10, the eight target positions correspond to addresses 10–17. Mask unused slots and modules that will use their own front connections as appropriate. Do not copy old switch positions into a changed rack arrangement without checking them.
Supply and hardware-version distinction
The older C349-06 specification lists 5 V ±5% and 24 V +25%/−15% supplies, drawing typically 1.1 A at 5 V and 60 mA at 24 V. The Siemens-published CSA document dated 11 September 2001 separately lists a “redesign” version of this order number rated at 5 V / 0.5 A. Select consumption data after verifying the hardware version.
The older manual gives dimensions of 20.32 × 233.4 × 160 mm and an approximate weight of 0.3 kg. Assess the PLC power-supply budget together with auxiliary modules and grounding requirements.
923A comparison and fault indicators
6ES5 923-3UA11 identifies the 923A coordinator. The 923C's PG MUX and additional mailbox functions mean the two models must not be treated as automatically equivalent. Further system information is available in About Siemens S5 PLC.
BUS FAULT indicators identify CPUs holding the bus beyond the permitted duration, while IF FAULT concerns the serial interface. The manual's default 2 ms bus-lock monitoring time is not the PLC program scan time. A bus fault can stop several CPUs.
Editor's note
Do not buy this board as a CPU. First record how many CPUs are installed, their slots and whether programmer access runs through the coordinator.
Photograph S1, S2, S3 and the jumpers before replacement. Even an identical-order-number spare can leave you without the working configuration if the original settings were not recorded.
If the PG reaches one CPU but not another, check the target address, S3 mask, slot assignment and any connection at the module's front socket before condemning the processor.
Record CPs using IPC areas too. Enabling the same flag area on two devices or assigning FC–FF pages to another module can disrupt data exchange.
During fault finding, distinguish BUS FAULT from IF FAULT. Replacing the coordinator alone may not resolve a CPU holding the bus or a serial-connection problem.
When buying used Siemens equipment, request the hardware version and a test record from a suitable multiprocessor rack. Verify PG MUX access and IPC exchange, and disconnect rack power before removing or inserting modules.
OtomasyonAVM resources
Browse the 6ES5 923-3UC11 model page, S5 CPU family, interface modules and used Siemens equipment. The older operating instructions and the CSA document identifying the redesign version are linked separately below.
Related topics and models
+ 6ES5 923-3UA11: 923A coordinator; do not assume identical functions to 923C.
+ 6ES5 922-3UA11: CPU 922 for suitable 135U multiprocessor arrangements.
+ 6ES5 928-3UB21: CPU 928B; check coordination and programmer-access arrangements.
+ 6ES5 946-3UA21: the processing section of a 946/947 assembly; the complete assembly counts as one CPU.
Other S5 equipment
Siemens S5 PLC · CPUs · Interfaces · Cables · Communication · Racks · Used Siemens equipment
Manufacturer documents and external references
+ Siemens S5-155U CPU 946/947 Manual – Part 6, 923C Coordinator Instructions, English: C79000-B8576-C349-06. PDF pages 185–198; specifications on 190, DIP settings on 192–194, IPC area on 195 and connector assignments on 198.
+ CSA Certificate 1232105 – Siemens SIMATIC S5, 11 September 2001, English: PDF page 13 separately lists the classic 923C and “Coordinator 923 C (redesign)” current ratings.