Delta Servo Braking Resistors
Delta Servo Braking Resistors
A Delta servo braking resistor dissipates energy returned to the servo drive when the motor decelerates or a load drives the motor. As this energy raises the DC bus voltage, the drive’s braking circuit switches in the resistor. To select a braking resistor, check the exact drive code, minimum allowed resistance and regenerative braking duty cycle together.
Delta part numbers and ratings
BR400W040 · 400 W / 40 Ω
BR1K0W020 · 1 kW / 20 Ω
BR1K5W005 · 1.5 kW / 5 Ω
These part numbers appear in the ASDA-A2 accessory catalog. Check resistance against the drive’s braking circuit limits and wattage against the resistor’s thermal duty. Once motor and drive selection is complete, verify the external resistor in the manual for that drive.
Minimum resistance for 400 W drives
ASDA-A2, 220 V · 30 Ω
ASDA-B2, 220 V · 60 Ω
ASDA-A3, 220 V · 60 Ω
ASDA-A3, 400 V · 80 Ω
The 40 Ω BR400W040 is below the minimum for the 400 W B2 and both A3 examples. Once the resistance meets the minimum, check the manual’s other requirements for external resistors and its installation drawing. A parallel connection lowers the equivalent resistance. Two 40 Ω resistors in parallel, for example, have an equivalent resistance of 20 Ω.
Size the resistor for the machine’s duty cycle. Load inertia and transmission, speed before stopping, deceleration time and stops per minute determine thermal load. For a vertical axis driven by its load, include the braking torque applied throughout descent. With a linear motor, use moving mass and linear speed in the calculation. Check the energy of an individual braking pulse and installation cooling conditions as well as average power.
AL002, AL005 and resistor parameters
AL002 · Overvoltage. Record whether the alarm occurs at power-up or during rapid deceleration. Check supply conditions for a power-up fault. During deceleration, review the stop profile and regenerative circuit along with the supply.
AL005 · Regeneration error. Follow the troubleshooting sequence in the drive manual and compare the external resistor connection, resistance and wattage ratings, and drive settings. A2 and B2 use P1-52 for resistance and P1-53 for capacity. The A3 manual labels these parameters P1.052 and P1.053.
B2 AL002 and AL005 diagnostics · A3 AL002 diagnostics · A3 AL005 diagnostics
Delta catalogs and selection tables
ASDA-A2 catalog · resistor part numbers (EN) · Printed page 70.
ASDA-A2 manual · resistor selection (EN) · Section 2.8.
ASDA-B2 manual · resistor selection (EN) · Section 2.8. The BR400W040 drawing is on printed page 2-20.
ASDA-A3 manual · 220 V and 400 V tables (EN) · Printed page 2-26.
Delta servo PDF archive · Delta VFD braking resistor tables
Editor’s Note
Ask for both labels when buying used. Record the resistor part number, resistance and wattage alongside the complete drive code. During bench inspection, look for cracks, discolored terminals, damaged leads and loose mounting feet. Before measuring the resistor or touching terminals, isolate power safely and verify DC bus discharge as described in the manual.
Find out why the old resistor was replaced. Before fitting the same part after a failure, check the mounting surface, cabinet airflow and any increase in production speed. Compare the first cycle with a cycle after the cabinet has warmed up. If the alarm begins after several minutes, check stop frequency and heat buildup.
Use the wiring diagram for the exact drive. Refer to that model’s drawing for the internal resistor jumper, external resistor terminals and mounting conditions. If the fault occurs alongside other signal problems, compare the alarm with the feedback trace. Consider signal noise when reviewing cable routing.
Use the last successful stop as a reference for AL002. Compare the speed, stopping time and carried load at the alarm with the last fault-free cycle. If mechanical vibration changed during stopping, check the coupling, load and motion profile. Identify what changed before adjusting the resistor value or servo gain.
Check the holding brake separately on vertical axes. The motor’s electromagnetic brake holds the load at standstill. The regenerative circuit handles energy returned to the drive during descent. Secure the vertical load mechanically before service.