Delta DVP30EC00T3

Delta DVP30EC00T3 Transistor Output PLC

The Delta DVP30EC00T3 is a DVP-EC3 PLC CPU with 18 digital inputs and 12 NPN transistor outputs. It runs on 100–240 V AC. Its fixed I/O suits compact packaging machines, product counters and conveyor automation.

24 V DC inputs and high-speed counting

The 18 inputs at X0–X21 use octal addressing. X7 is followed by X10, and X17 by X20. An inductive proximity sensor can detect metal parts, a photoelectric sensor can detect passing products, and a limit switch can report end of travel. Wire the S/S input common to match the 24 V DC sensor’s PNP or NPN output.

The instruction sheet lists input limits of 20 kHz for X0–X3, 10 kHz for X4–X17 and 60 Hz for X20–X21. When using a high-speed counter, check the limit for the selected input and counting mode. For A/B counting, check the encoder output type, phase order and input filter together.

NPN outputs and Y0/Y1 pulse function

Outputs Y0–Y13 are split into two groups. UP0/ZP0 serves Y0–Y7, and UP1/ZP1 serves Y10–Y13. The UP/ZP circuit requires an external 24 V DC supply. Delta specifies 0.5 A per output and 4 A per ZP for resistive loads. For a valve coil or interposing relay, check the applicable load rating and coil suppression.

Delta’s catalogue specifies two independent pulse outputs on Y0 and Y1, at up to 10 kHz, for suitable transistor units at V8.00 and later. For position control, check the pulse input circuitry, pulse format and frequency required by the servo drive or stepper motor drive.

WPLSoft, ISPSoft and the programming cable

Use WPLSoft for PLC programming, program readout and live Ladder monitoring. Earlier EC3 units are listed at 4K steps. For V8.60 and later, Delta specifies the EC3-8K target in ISPSoft and a capacity of 7,920 steps. Set up the ISPSoft serial connection in COMMGR.

Use the PLC’s 8-pin Mini-DIN COM1 (RS-232) port for programming. On a USB PC, install the driver for the UC-PRG020-12A programming cable and select the COM number assigned by Windows. A PC with a DB9 RS-232 port can use the UC-MS020-01A.

COM2 RS-485 can connect to an operator panel or drive. On a Modbus link, match the station address, baud rate, parity and ASCII/RTU format. Route pulse and serial cables away from motor wiring to reduce electrical interference.

Editor’s Note

When buying used, check the full DVP30EC00T3 code on the label. If the CPU is accessible, record its version. The 4K and 8K distinction matters when transferring a project.

If the old PLC still runs, back up the program, required retained values and serial port settings first.

If an entire output group is inactive, start by checking the 24 V DC supply and polarity at its UP/ZP pair.

If the count drops at higher speeds, inspect the X input assignment and filter setting. Keep machine movement safely inhibited while measuring Y0/Y1 pulses.

Check output switching with a suitable test load. Before reinstalling the unit, verify the L/N supply, S/S common and cabinet grounding against the wiring diagram.

Related models and topics

The DVP30EC00R3 has the same 18+12 I/O count with relay outputs. Among the transistor models, the DVP24EC00T3 has 12 inputs and 12 outputs, the DVP32EC00T3 has 16 inputs and 16 outputs, and the DVP40EC00T3 has 24 inputs and 16 outputs. Count the required inputs and outputs separately when selecting a CPU.

RS-232, RS-422 and RS-485 compared · Delta DVP PLC series · Used Delta equipment