Delta DVP02TKL-S is a temperature control module with two universal sensor inputs and two analog outputs, managed through RS-485. Its local PID control function evaluates measurements and drives outputs; an external PLC or supervisory system communicates over Modbus. It belongs to the DVP Slim temperature module family.

The L version provides analog outputs: Each channel can be configured for 0–10 V, 0–20 mA or 4–20 mA. Distinguish it from the relay-output DVP02TKR-S and transistor-output DVP02TKN-S. An analog output commands a suitable power controller; it is not a contact that directly switches heater power.

Inputs, measurement ranges and supply

CH1 and CH2 inputs: 0–5 V, 0–10 V, 0–20 mA, 4–20 mA, 0–50 mV and −100…+100 mV, plus RTD and thermocouple measurement. Select the sensor mode separately for each channel; an incorrect mode can produce a wrong reading despite correct wiring.

RTD options: Pt100, JPt100, Pt1000, Cu50/Cu100, Ni100/Ni120/Ni1000 and LG-Ni1000. Thermocouple options: J, type K, R, S, T, E, N, B, U, L, TXK, C and PL II. Match the actual probe characteristic when selecting a thermocouple type.

Example temperature ranges: Pt100/Pt1000 −200…+600 °C; J −100…+1200 °C; K −200…+1300 °C. Temperature data uses 0.1-degree units; for example, 253 represents 25.3 °C. Interpret negative values as signed data. Display increments and total measurement accuracy are different specifications.

Supply: External 24 V DC; the documented range is 20.4–28.8 V and maximum consumption 2.4 W. Use a suitable 24 V power supply. Analog and digital circuits are isolated; the analog channels are not isolated from each other.

Analog outputs and wiring

OUT1 and OUT2: 12-bit hardware resolution. Permitted voltage-output load is 1 kΩ–2 MΩ; current-output load must not exceed 550 Ω in total. Include cable and other series components, as well as receiver input resistance, in the loop calculation.

Use VO–AG for voltage and IO–AG for current output. The configured mode must match the wiring. VO and IO on one channel are not two independent output channels. A voltage signal and a current loop require different receiver connections.

Connect voltage/thermocouple inputs to the channel's L+ and L− terminals. For current input, bridge L+ to I+ and connect the signal return to L−. For a three-wire Pt100/JPt100/Pt1000, connect the single element end to L+ and the two wires at the other end to L− and I−. Verify thermocouple polarity and the appropriate extension cable.

Follow the manufacturer diagram for SLD shielding and grounding. Route sensor and analog I/O cables separately from power cables. Do not apply external supply voltage to an RTD input.

TKSoft, COMMGR and connection cable

Configure the module using TKSoft / TK Wizard. Create a serial connection in COMMGR, select its driver and station in TKSoft, then use Scan to discover the module. The interface provides sensor, PID, output-mode and communication settings.

PC connection: Use a suitable USB-to-RS-485 converter and D+/D− terminal wiring. Factory communication defaults are 9600 bit/s, 7E1, Modbus ASCII, station 1. Match ASCII/RTU selection and serial format at both ends. A used module may retain different settings.

If an external DVP PLC acts as master, its CPU-supported programming tool may be WPLSoft or ISPSoft. TKSoft configures the temperature module; the external CPU's Ladder application is a separate project. Compatible DVP02TU-S extensions can connect to the right side of the TK series.

Modbus addresses and channel settings

Direct TK addresses: H0000 contains the model code, H044F for DVP02TKL-S. H0001 reports firmware. H0002/H0003 contain CH1/CH2 measured values (PV), H0004/H0005 their setpoints (SV), and H0006/H0007 their run/stop settings.

Sensor type: H000B for CH1 and H00EB for CH2; examples are 5 = Pt100, 7 = Pt1000, 9 = K thermocouple and 3 = 4–20 mA. Analog output mode: H0025 for CH1 and H0105 for CH2; 0 = 0–10 V, 1 = 0–20 mA, 2 = 4–20 mA. Output monitoring values are available at H0028/H0108 over 0–4000.

These are hexadecimal register addresses for RS-485/Modbus access. Check the master's 4xxxx notation and zero/one-based addressing. Do not treat a TU-series page-dependent CR number as a direct TK address. During normal PID operation, H0004/H0005 represent process setpoints, not raw analog-output commands.

PID and practical applications

In an automation application, PV is the measurement, SV the target and MV the control output. Check feedback direction, heating/cooling selection and output limits. Keep process conditions stable during automatic tuning. Do not assign the relay versions' independent digital alarm-output features to the L version.

When commanding a power controller with 4–20 mA, match its minimum/maximum power scaling to the module output. Incorrect analog input scaling can undermine control even with correct PID settings. If the system also uses PLC-based PID, prevent two independent loops from simultaneously controlling the same power output.

Related modules

DVP02TKR-S is the relay-output TK option; DVP02TKN-S uses NPN transistor outputs. DVP02TUL-S is an analog-output TU model and DVP02TUR-S a relay-output TU model. Compare TK/TU connection arrangements and R/N/L output technology together; equal input counts do not establish interchangeability.

Editor's Note

Check the L on the label. Replacing an expected relay card with an analog-output version changes the control arrangement even if the field cable runs to the same equipment.

Test both inputs with a known signal when inspecting a used unit. Match the RTD simulator, thermocouple calibrator or current source to the selected input mode; one good channel does not verify the other.

Measure each analog output separately with a suitable load. Measure voltage in parallel and current in series with the loop; never connect an ammeter directly across a voltage source.

Verify output direction and limits before energizing a heater during testing. Do not assume a used card's existing PID settings suit the new process.

For communication dropouts, check station address, serial format, polarity and supply. Perform short-circuit checks with power isolated; inspect the relevant fuse and terminal contacts. Back up parameters before restoring factory settings.

For a used-unit sale, state quantity, label photographs, working/faulty condition and input/output test results. Sales require an invoice; no returns; workshop testing is available. Sellers can send details to otomasyonavm@gmail.com.

PDF documents and related topics

For wiring, PID and address tables, visit our Delta DVP PLC files page first. In the 2026 DVP module manual, use section 9.1.4 for specifications, 9.5 for registers/TKSoft and 9.6.4 for wiring. Select the rows specific to the analog-output L version.

Related topics and navigation: Delta and used models | Delta PLC | DVP series | Expansion modules | Slim temperature modules | DVP02TKL-S model page

External references

Delta DVP Series Module Manual – 6 January 2026, English