Delta DVP06XA-SH
Delta DVP06XA-SH – 4 Analog Inputs and 2 Analog Outputs
Delta DVP06XA-SH is a DVP Slim specialty module with 4 analog inputs and 2 analog outputs. Delta’s Rev.28 Declaration of Conformity, dated 5 November 2024, lists the exact model as 4AD/2DA. The four analog inputs bring measurements into the PLC. The two analog outputs provide references for field devices.
Discontinuation and Delta’s recommended replacement
Delta’s notice lists 31 March 2025 as both the last order date and the end-of-production date. It recommends the DVP06XA-S2. Before replacing the module, compare the existing CPU code, terminal layout, power supply, channel ranges and program mapping. If the old and new cards use different raw scales, the same measurement can appear differently on the HMI.
Signals, terminals and scaling
The available documents do not confirm the SH version’s terminal layout, supply voltage, signal ranges, resolution, conversion time or control registers. Delta’s shared instruction sheet covers DVP06XA-S and DVP06XA-S2. Use the exact nameplate, cabinet wiring diagram and working PLC project to identify the installed SH connections.
A pressure sensor, for example, may use a 4–20 mA current or voltage signal. Record the transmitter’s signal type and measurement span before changing the channel setup. The PLC scales the raw A/D conversion value to units such as bar or percent. On the output side, match the receiving device’s expected reference to the analog I/O settings.
If a measurement fluctuates only when a motor starts, check grounding, shield connections and separation from power cables. For a stable but incorrect measurement, monitor the raw value and displayed value separately. This helps troubleshoot the field signal, channel setup and PLC scaling in sequence.
Programming software and cable
Open the PLC program through the host CPU. Use WPLSoft or a compatible ISPSoft version according to the CPU and project. For example, the DVP14SS211R/T CPU supports the UC-PRG020-12A cable on COM1 RS-232. This example describes programming access to the CPU. Verify SH expansion compatibility separately. For other CPUs, choose the programming cable by the exact model and port.
Related order codes
DVP06XA-S2 is Delta’s recommended replacement. DVP06XA-S is a separate model documented in the same installation sheet. DVP06XA-E2 and DVP06XA-H3 belong to different expansion families. The declaration lists DVP06AD-SH with six analog inputs. Compare the full order code and AI/AO layout when selecting a replacement.
Editor’s Note
Before removing a working SH module, photograph the label and terminal block. Back up the PLC project and any separate parameter records.
Record what each channel measures or controls along with its terminal number.
When moving to S2, compare power and signal terminals against the documentation for each model. A fitting connector only establishes mechanical fit.
Begin input testing with a known measurement. Check the raw count and the HMI engineering value separately.
Start output testing with a controlled test load. Verify the direction of the reference change before reconnecting the field device.