Delta RTU-EN01
Delta RTU-EN01 – Modbus TCP Ethernet remote I/O module
The Delta RTU-EN01 is a remote I/O station that connects compatible right-side DVP-S expansion modules to a PLC, HMI or SCADA system over Modbus TCP. It acts as a Modbus TCP server (slave) on Ethernet and brings the signals from a remote cabinet together at one station.
Module capacity and communication ports
Delta specifies up to 16 digital modules and 256 digital I/O points, plus up to eight analog I/O modules. If the physical module order changes, recheck the digital input and output addresses and analog I/O mapping. Smart PLC functions provide local IF–THEN rules, timers, counters and a real-time clock.
The 24 V DC supply range is 20.4–28.8 V DC. The RJ45 Ethernet port supports 10/100 Mbit/s and Auto MDI/MDIX. Use a standard Cat5e patch cable for a direct Ethernet connection or connect through a switch. COM1 is an RS-232 configuration port. COM2 is an RS-485 port with SG, D− and D+ terminals.
In gateway mode, the RTU-EN01 forwards Modbus requests from Ethernet to Modbus ASCII or Modbus RTU devices on COM2. Match the serial mode, baud rate, parity, stop bits and station addresses to the connected devices. See the protocol comparison when choosing a Modbus TCP or EtherNet/IP driver.
Configuration software and cable
Use DCISoft to configure the RTU-EN01 network and I/O settings. Connect the PC to the same local network and use IP Search to find the station. In Overview, check its IP address, firmware version and right-side modules. The factory IP address is 192.168.1.5 with a 255.255.255.0 subnet mask. Use the actual assigned address on an installed station. Delta's HMI manual lists TCP port 502 for Modbus TCP clients.
For serial configuration, Delta's manual lists the DVPACAB230 and DVPACAB215 cables for the COM1 Mini-DIN RS-232 port. WPLSoft and ISPSoft are used for the host PLC project. On supported CPUs, the RTU Mapping table in ISPSoft maps PLC addresses to the remote station.
RX, RY and RCR addresses
RX represents digital inputs, RY represents digital outputs and RCR contains analog module control registers. For example, the first digital input, RX0, appears as raw address 0x0400 or six-digit reference 101025 in the Modbus table. Check which address format your client expects. RCR#0 maps to CR#0 on the first analog module. RCR#50 maps to CR#0 on the second. Use the attached module's CR table to find the actual measurement register.
Editor's Note
When buying used, inspect the full model label, RJ45 jack, RS-485 terminal block and right-side expansion connector.
On the bench, check the 24 V DC supply and Ethernet link first. Then compare the module order shown in DCISoft with the cabinet list.
Read a single RX input first and confirm the corresponding signal in the field. Put connected loads into a safe test state before testing outputs.
Digital outputs turn off when the RTU-EN01 changes from RUN to STOP. Check the connected loads before changing the switch position in a production cabinet.
Before replacing the module, record the IP settings, serial station list, RX/RY/RCR mapping and Smart PLC rules.
Related models and PDF files
Delta DVP remote I/O modules · RTU-485 · RTU-DNET · RTU-PD01 · DVPEN01-SL
Used Delta Automation · Delta PLC · Delta DVP PLC series · Delta DVP PLC PDF files
Operation manual · RTU-EN01 Operation Manual, Rev.01 (English PDF)