Delta RTU-PD01
Delta RTU-PD01 – PROFIBUS DP Remote I/O Communication Module
Delta RTU-PD01 connects compatible Delta DVP Slim modules to a PROFIBUS DP network as a remote I/O station. It operates as a DP slave and exchanges cyclic DPV0 data with the master. Local I/O modules attach to its right side. A separate serial port brings data from Modbus devices into the same DP station.
Power, communication and capacity
The module runs on 24 V DC (20.4–28.8 V DC) and consumes 2.5 W. Its PROFIBUS DP port uses a DB9 connector. It detects the bus rate automatically and supports up to 12 Mbit/s. Delta’s table specifies a 100 m segment at 12 Mbit/s. Use shielded PROFIBUS cable and a suitable PROFIBUS connector. Enable termination at both physical ends of the segment.
Delta specifies up to 16 digital I/O modules with 256 digital points and up to eight special I/O modules per station. The manual lists DVP08SM11N and DVP08SN11R among the supported digital modules, DVP04AD-S among analog modules, and DVP04TC-S among temperature modules. The exchange with the DP master is limited to 100 input bytes and 100 output bytes. Check both the total data size and exact module support when selecting the I/O stack.
GSD, configuration software and station address
Install DELA09B9.GSD in the DP master’s hardware catalogue. The RTU-PD01 product ID is 0x09B9. For the Siemens S7-300, Delta’s example uses STEP 7 HW Config → Options → Install GSD File. In a TIA Portal project with DP master support, use Options → Manage general station description files (GSD). Download the configuration to the DP master. Connect the PC to the master PLC’s programming interface and use the station’s DB9 port for the PROFIBUS cable.
The rotary switches use hexadecimal addressing, with a valid range of 1–125 (0x01–0x7D). For example, a master project address of 26 corresponds to 1A on the module. Switch off power before changing the address and then repower the unit. Match the I/O slots in the project to the physical order. See the PROFIBUS FAQ for addressing and bus checks.
Modbus devices on the RS-485 port
On the separate RS-485 Modbus port, the RTU-PD01 acts as a master and polls up to 16 Modbus slaves. Match Modbus RTU or Modbus ASCII mode, bit rate and serial framing across the devices. Define the read and write registers in the Modbus mapping in the master project. If a field device fails to respond, check the serial port settings and then its station address.
Editor’s Note
When buying second-hand, check the DB9 socket, rotary switches, right-side extension connector and RUN/STOP switch. Before removing a unit from a cabinet, photograph its address and I/O order and save the project.
Start with a single input module. When NET is green, confirm that the chosen input reaches the intended bit or byte in the master PLC.
If NET is steady red, check the DP cable and address match. If it flashes red, check that the address is within range and that the configured I/O order matches the hardware.
On loss of communication, Hold I/O data retains the last data and Clear I/O data clears it to zero. Choose the behaviour required for the machine and verify it before enabling loads.
If faults begin when a drive starts, inspect the cable shield, cabinet grounding and electromagnetic interference. If DP is working and Modbus data is missing, check the RS-485 LED and serial settings.
Related topics and modules
RTU-485 Modbus RS-485 · RTU-EN01 Ethernet · RTU-DNET DeviceNet · Siemens ET200 PROFIBUS and PROFINET interfaces
Delta DVP remote I/O modules · Delta DVP expansion modules · Delta DVP PLC series · Second-hand Delta models · Delta DVP PLC PDF files
External references