Delta DVP Slim temperature modules
Delta DVP Slim Temperature Modules
Delta DVP Slim temperature modules monitor or control heating and cooling in ovens, extruders, injection moulds and packaging jaws. PT and TC models feed temperature readings to a compatible PLC system. TU and TK models have two universal inputs, built-in PID control and relay, NPN transistor or analogue outputs depending on the model. Start with the sensor type, the number of zones and the equipment the output will drive.
Models and selection guide
Select a model number to open its device page. A universal input can be configured for a supported RTD, thermocouple, current or voltage signal on each channel.
| Model | Inputs | Connection | Physical control outputs |
|---|---|---|---|
| DVP04PT-S | 4 RTD | Right side of compatible DVP CPU | None |
| DVP06PT-S | 6 RTD | Right side of compatible DVP CPU | None |
| DVP04TC-S | 4 thermocouples | Right side of compatible DVP CPU | None |
| DVP02TUR-S | 2 universal | Right side of compatible DVP CPU or TK | 4 relay |
| DVP02TUN-S | 2 universal | Right side of compatible DVP CPU or TK | 4 NPN transistor |
| DVP02TUL-S | 2 universal | Right side of compatible DVP CPU or TK | 2 analogue |
| DVP02TKR-S | 2 universal | RS-485 remote control | 4 relay |
| DVP02TKN-S | 2 universal | RS-485 remote control | 4 NPN transistor |
| DVP02TKL-S | 2 universal | RS-485 remote control | 2 analogue |
Choosing between Pt100, thermocouple and 4–20 mA
RTD measurement. Use the DVP04PT-S for four Pt100 points or the DVP06PT-S for six. Delta lists Pt1000, Ni100 and Ni1000 support on the DVP04PT-S from V4.06 onward. Where lead resistance affects the reading, wire a three-wire RTD as shown in the module diagram. If the probe type is unclear, review the difference between a Pt100 and a thermocouple.
Thermocouple measurement. The DVP04TC-S reads four channels of type J, type K, R, S or T thermocouples. Match each channel setting to the probe label. Check the thermocouple standards and polarity when selecting extension wire. One DVP04TC-S can monitor four oven zones while the PLC controls each zone separately.
Transmitter measurement. If the field transmitter sends temperature as 4–20 mA or 0–10 V, select the matching TU/TK input mode or a compatible analogue input module such as the DVP04AD-S. Scale the analogue signal in the PLC using the lower and upper temperature values on the transmitter label.
Choosing an output for heating or cooling
The TU and TK families work as temperature controllers. The PV is the measured value and the SV is the setpoint. The PID output responds to both. Choose R when the control circuit needs a relay contact, N for time-proportional switching through a compatible DC-input SSR, or L for a power controller or proportional valve with a 0–10 V, 0–20 mA or 4–20 mA command input. Select the heater SSR or contactor for the load current and switching frequency. If the process overshoots, check the temperature PID settings and the probe location together.
PLC software, cables and temperature registers
Check module compatibility for CPUs such as the DVP-SS2 and DVP-SX2. Open the PLC program in WPLSoft or ISPSoft according to the CPU and project version. Set up the COMMGR driver for an ISPSoft connection. Match the Delta PLC programming cable to the CPU port. For example, the UC-PRG020-12A suits compatible 8-pin mini-DIN RS-232 CPU ports. RS-232 and RS-485 are distinct interfaces.
Check the 24 V DC supply, the module order on the CPU expansion bus and the control register map. On compatible CPUs, use TO to write settings and FROM to read values in ladder logic. If a DVP04TC-S Celsius register with a 0.1 °C scale returns 253, it represents 25.3 °C. Use a signed data type for negative values and display one decimal place. Show the channel fault status alongside temperature on the HMI or SCADA screen.
For an RS-485 connection through the TK, use a suitable USB-to-RS-485 converter and TKSoft with COMMGR on the PC. TKSoft can also detect TU modules connected to the right of the TK. When a PLC or HMI reads data over Modbus over RS-485, check the TK station number, serial settings, RTU or ASCII mode and the register map. The first TU and the TK itself use different register base addresses.
Editor’s Notes
Ask to see the full nameplate. The DVP02TKR-S and DVP02TUR-S use the same output type. Trace the cables and side connector to see which unit provides the communications link and which one is the expansion.
If one channel drifts, start at the probe. For a thermocouple, check channel type, polarity and extension wire. For an RTD, test with a known-good probe or simulator of the same type. If the fault stays with the channel, inspect its terminal and input circuit.
If the reading jumps when a drive runs, check the spacing between sensor wiring and power cables, the shield connection and cabinet grounding. Trace the interference before increasing software averaging.
Test the outputs on a used unit. Apply a known signal to each input. Use a suitable test load for R and N outputs and a meter for the selected L output range. Inspect the removable terminal block and side connector.
Simulate a disconnected sensor before handover. Verify that the screen shows the fault and that the control output moves to its configured state. Record sensor types, setpoints, PID settings and any station number before swapping a module.
Related topics
See our guides to industrial communications and EMC filters for wiring and network topics. Related devices include DVP Slim analogue modules and the DVP08RT-S for legacy NTC installations.