Delta DVP Slim positioning modules

Delta DVP Slim positioning modules

Delta DVP Slim positioning modules send position and speed commands from a compatible PLC to a pulse-input servo or stepper drive. The single-axis DVP01PU-S mounts on the right of the CPU. The two-axis DVP02PU-SL mounts on the left of a suitable PLC CPU. In industrial automation applications such as cut-to-length control, indexing and material feeding, the drive input and CPU expansion side matter as much as the axis count.

Models · PLC compatibility · Software and cables · Pulse calculation · PDF files

DVP Slim positioning module models

ModelAxes and mountingPulse outputField connections
DVP01PU-S 1 axis · CPU right side 5 V differential · 10–200,000 pps External 24 V DC supply. DOG, PG0, LSP and LSN reference and limit inputs.
DVP02PU-SL 2 axes · CPU left side 5 V differential · up to 200 kHz One A/B/Z differential input group and five 24 V DC general-purpose inputs.

The DVP01PU-S suits single-axis tasks such as cut-to-length positioning and indexing. The DVP02PU-SL combines two pulse-controlled axes in one module. Two channels suit applications where a feed axis and a transfer axis move independently. If the axes must follow a shared path, select a motion control solution with documented interpolation support.

Which Delta PLCs are compatible?

Delta lists the DVP01PU-S in the right-side special module table for the DVP-SS2, DVP-SA2, DVP-SX2, DVP-SE and DVP-SE2. The DVP02PU-SL appears in the left-side expansion table for SA2, SX2, SE and SE2. The DVP28SA2 and DVP26SE have no left expansion port. For DVP-SV3/SX3, check the exact CPU part number, left-side connection and firmware in the hardware manual.

For the DVP02PU-E2, see DVP E2 modules. For the DVP01PU-H2, see the H2 model page. The suffix identifies the module family and connection to check against the CPU.

Drive, encoder and home connections

In a servo system, the module sends pulse commands to the servo drive, which controls the servo motor. A stepper motor axis uses a stepper drive with a suitable differential input. Match the drive’s 5 V differential command input and its Pulse/Direction or CW/CCW setting to the module’s high-speed pulse output.

On the DVP01PU-S, DOG is the near-home input, PG0 receives the zero marker, and LSP/LSN are the positive and negative limit switch inputs. The DVP02PU-SL has one A/B/Z input group. For an external encoder, check its line-driver output and the module’s high-speed counting limits. Chapter 14 of the Delta module manual specifies 200 kHz for A/B, 20 kHz for Z and 1 kHz for the five general inputs.

Programming software and cable

DVP01PU-S. Open the compatible Slim CPU project in WPLSoft or ISPSoft, depending on the CPU. Use COMMGR for the ISPSoft connection when required. The ladder program accesses module control registers (CRs) through FROM/TO. A 32-bit position or speed value occupies two consecutive registers. CR#5 sets the pulse output format. CR#38 reports operating status and CR#39 holds the error code.

DVP02PU-SL. Use the left-module identification and addressing method documented for your CPU. Supported SV3/SX3 projects use DIADesigner and the API14xx module instructions. For other CPUs, check the supported software and instructions against the exact model and firmware.

Choose the cable by CPU port. Delta specifies UC-PRG020-12A for DVP-SS2 COM1 RS-232 and UC-PRG015-01A for the DVP-SX2 Mini-USB port. If the PC has no RS-232 port, the first cable requires a suitable USB-to-RS-232 adapter. The programming communication port, the Modbus RS-485 link and the drive pulse pairs serve separate functions. Delta PLC cables.

Calculating pulse count and speed

Screw lead, mechanical transmission and the drive’s electronic gearing determine how many command pulses produce one millimetre of travel. At 200 pulses/mm, a move of 150 mm takes 30,000 pulses. A speed of 250 mm/s requires 50,000 pulses/s, or 50 kHz. Compare the calculated frequency with the module and drive limits, and check the commanded speed against the mechanical limits.

Editor’s Note

When buying used, ask for photos of the full nameplate, expansion connector and terminals. For S and SL modules, start by checking which side of the PLC the module fits.

On a DVP01PU-S bench test, check the 24 V DC module supply and the FP/RP terminals separately. Keep 24 V off the 5 V differential pulse terminals.

Start with a short, slow move. Verify the physical direction, then test DOG/PG0 homing and the LSP/LSN limits. Run homing twice and check whether the axis returns to the same physical point.

CPU in RUN and the axis stays still? Start troubleshooting with the drive READY/alarm indication, any active limit and the module status and error registers. Then check whether pulses reach the drive input.

If the axis sometimes stops in a different place, check the reference signal and mechanical backlash first. Route pulse pairs separately from the motor cable and check grounding and noise suppression against the drive manual.

Before removing the module, record the PLC program, module position, CR values written at startup and servo parameters. Use those records to compare the first test after fitting the replacement.

Related Delta products and topics

Delta DVP expansion modules · DVP01PU-H2 · Delta DVP E2 modules · Delta DVP-PM · Delta ASDA-A2 · Delta ASDA-B2

OtomasyonAVM PDF files

Visit the Delta DVP PLC PDF files page for series documentation. See Chapter 10 for DVP01PU-S wiring and control registers and Chapter 14 for DVP02PU-SL inputs and outputs.

External references

DVP01PU-S instruction sheet and CR table (PDF) · DVP module manual, Chapters 10 and 14 (2026) · Delta DVP & TP catalogue (PDF)

SS2 / SA2 / SX2 / SE / SE2 programming manual (PDF) · SV3 / SX3 programming manual, API14xx (PDF) · SV3 / SX3 hardware manual (PDF) · Delta PLC/HMI cable selection, Sections 1.4 and 1.6.1 (PDF)


Refine Search