Delta DVP04DA-E2

Delta DVP04DA-E2 – 4-Channel Analog Output Module

Delta DVP04DA-E2 is a four-channel, 14-bit analog output module used with DVP-ES2/EX2 PLC systems. It converts commands from the host CPU into voltage or current outputs. Within an analog I/O system it generates commands, whereas DVP04AD-E2 acquires measurements. It is a special expansion unit among PLC input and output modules.

Do not confuse its E2 enclosure and expansion connection with H/H2/H3 or slim S modules. The 2025 DVP module manual lists this model in the DVP-E family; for ES3/EX3 migration, verify the host CPU’s hardware support, firmware and module-access method.

Output ranges and digital scaling

Select each channel independently: Mode 0: −10…+10 V; Mode 1: 0–20 mA; Mode 2: 4–20 mA. For digital-to-analog conversion, normal commands are −32000…+32000 for voltage and 0…32000 for current. Data uses 16-bit two’s-complement words; this format does not change the 14-bit hardware resolution into 16-bit resolution.

Standard curves give −32000/0/32000 → −10/0/+10 V; 0/16000/32000 → 0/10/20 mA, or 4/12/20 mA in 4–20 mA mode. Analog voltage or analog current selection must match receiver range and wiring. In 0–10 V and 4–20 mA applications, a zero command in 4–20 mA mode produces 4 mA. For 0–10 V, use the positive 0…32000 command range within Mode 0.

Terminals and load limits

Take a voltage analog signal from VOn–AG, or current from IOn–AG. Do not bridge VO and IO on this output module. In analog signal applications, the drive or controller analog input must use the same signal type. FE is for shielding/grounding; do not substitute it arbitrarily for AG.

The sheet specifies 1 kΩ–2 MΩ load impedance and 5 mA maximum output current for voltage. Observe both limits: at 10 V full scale, the load must be at least 2 kΩ to stay within 5 mA. This minimum follows from Ohm’s law. The permitted total current-output load is 0–500 Ω, including cable resistance.

Analog and digital circuit sections are isolated, but analog channels are not isolated from one another. Receivers at different ground potentials may need external isolation. Voltage-output short-circuit protection does not permit prolonged short-circuit operation.

Supply, response and expansion

External supply is 24 V DC, 20.4–28.8 V DC; maximum DVP04DA-E2 consumption is 3 W; operating temperature is 0–55 °C. Size the power supply for all connected loads. Terminals are removable with a 5 mm pitch.

Specified response is 400 µs/channel. PLC scanning, command transfer and receiver filtering also affect overall timing. Special modules are numbered 0–7 by distance from the CPU, sharing a maximum of eight special modules. This module occupies no digital X/Y points.

Programming software and cable

Program the DVP-ES2/EX2 host with WPLSoft or ISPSoft. In a ladder diagram, TO writes modes and output values; FROM reads identity, firmware and error registers. DVP04DA-E2 does not run an independent PLC user program.

Connect the computer to the host CPU. For the ES2/EX2 COM1 RS-232, 8-pin mini-DIN port, DVPACAB230 is a suitable option. A computer without a serial port needs a USB-to-RS-232 adapter and its driver. For ISPSoft, select the correct COM port in COMMGR, set it to START and select that driver in ISPSoft. For another CPU generation, match software and cable to that host’s port.

CR registers and instruction examples

CR#0 = H0081 identifies DVP04DA-E2; CR#1 reports firmware. CR#2, #3, #4 and #5 select CH1–CH4 modes respectively. Each channel has a separate register, unlike the grouped mode bits used by H-series modules. The default mode is 0.

For the first special module, TO K0 K2 K2 K1 selects 4–20 mA for CH1 only. Configure CH2–CH4 through their own mode registers. CR#16–#19 contain the four output commands; TO K0 K16 D100 K4 writes D100–D103 to CH1–CH4. Replace K0 with the actual special-module index. The output-write example affects all four channels; prepare appropriate initial values in a test setup disconnected from the process.

With ES2 direct MOV access, module 0 uses D9900–D9903 for CH1–CH4; module 1 uses D9910–D9913, with a ten-register stride for subsequent modules. For example, MOV K16000 D9900 commands 12 mA when module 0 CH1 uses Mode 2. Do not assume these addresses apply to another CPU generation, or write conflicting commands to the same output from different program sections.

Saving settings, calibration and diagnostics

CR#28–#31 adjust OFFSET; CR#34–#37 adjust GAIN. Mode 2 does not support OFFSET/GAIN adjustment. Changing the output mode restores the related calibration defaults. CR#40 controls setting-change protection; CR#41 saves retentive settings. Write H5678 to CR#41 to retain parameters marked O in the manual. Do not repeat this on every scan; output command registers are non-retentive.

FROM K0 K43 D120 K1 reads error status. CR#43: b0 supply error, b2 upper/lower bound violation, b9 mode-setting error, b11 bound-setting error, b12 setting-change prohibition and b13 communication failure with the next module. Multiple bits can be active. CR#118 concerns output behaviour under low supply voltage. Check its existing setting and actual behaviour during CPU STOP and power recovery.

Control applications and technical files

In PLC-based PID control, the host performs the PID calculation and DVP04DA-E2 sends the resulting command to the field device. Feedback arrives through a separate measuring channel. Display setpoint, measured value, output percentage and diagnostics together on an HMI.

The host PLC can process commands received through Modbus ASCII or RTU. This does not imply that DVP04DA-E2 has an independent RS-485 port. Reduce electromagnetic interference by separating analog cables from motor wiring and following the manufacturer’s shielding and grounding diagram. Use Delta DVP PLC files for the model sheet and detailed module manual.

Editor's Note

Read the output mode and command together. A command of 16000 means 10 mA in 0–20 mA mode and 12 mA in 4–20 mA mode. Incorrect receiver scaling can resemble a faulty module.

Test every channel of a used module at low, middle and high commands. Measure voltage in parallel and current with a suitable series connection. Stay within the 5 mA voltage-output limit; do not test 10 V into 1 kΩ.

A suitable test circuit with a precision 250 Ω resistor gives 1/3/5 V at 4/12/20 mA. The resistor dissipates 0.1 W at 20 mA: use a suitable tolerance and at least a 0.25 W rating, while staying within the total 500 Ω load limit.

Back up calibration and the working program before changing modes. A mode change can restore OFFSET/GAIN defaults. After saving settings, power-cycle and verify them; do not keep issuing CR#41 save commands cyclically.

For one faulty channel, disconnect field wiring and test with a suitable dummy load. If all channels are affected, inspect supply, AG and program commands first. After repair, check warm-up, CPU STOP and power recovery; a lit POWER indicator alone does not establish correct operation.

Related topics and navigation

DVP04DA-E2 main page · DVP-E2 modules · DVP02DA-E2 · DVP expansion modules · DVP PLC series · DVP PLC files

External manufacturer documents

Delta DVP02DA-E2 / DVP04DA-E2 Instruction Sheet, 2021, EN/中文 · Delta DVP Series Module Manual, 2025, Chapter 3, EN · WPLSoft / ISPSoft FAQ