Delta DVP04AD-E2
Delta DVP04AD-E2 Analog Input Module
Delta DVP04AD-E2 is a four-channel voltage/current analog input module used with DVP-ES2 and DVP-EX2 systems. It converts field analog signals into numerical values for the PLC program. Applications include pressure sensors, 4–20 mA sensors and 0–10 V sensors; the input mode is selected separately for each channel.
The module requires an external 24 VDC supply within 20.4–28.8 VDC. Conversion time is 400 µs/channel; voltage input impedance is at least 1 MΩ and current input impedance is 250 Ω. The analog channels are not galvanically isolated from one another; consider field potential differences when planning connections.
Input ranges, resolution and digital scaling
Voltage modes: Mode 0 = −10…+10 V, Mode 1 = −5…+5 V, Mode 2 = 0…10 V, Mode 3 = 0…5 V. Match the analog voltage signal, wiring and channel setting.
Current modes: Mode 4 = −20…+20 mA, Mode 5 = 0…20 mA, Mode 6 = 4…20 mA. Select the correct analog current range; 0–10 V and 4–20 mA use different wiring and input modes.
The 16-bit data format differs from hardware resolution. Values are transferred as signed 16-bit two's-complement data. The manufacturer's table specifies 14-bit hardware resolution for ±10 V, ±5 V and ±20 mA, and 13-bit for 0–20 mA and 4–20 mA. Standard bipolar scaling is −32000…+32000; unipolar scaling is 0…32000.
Standard conversion examples: Mode 2: 0 / 5 / 10 V → 0 / 16000 / 32000. Mode 6: 4 / 12 / 20 mA → 0 / 16000 / 32000. Apply the sensor's engineering range separately. For a 4–20 mA sensor representing 0–10 bar, pressure = raw value × 10 / 32000. Use suitable arithmetic width to prevent multiplication overflow.
Specified overall accuracy is ±0.5% of full scale at 25°C and ±1% over 0–55°C. A large digital range alone does not establish measurement accuracy. Averaging and CPU scan time also affect the observed response.
Voltage and current wiring
Voltage input: For CH1, connect signal positive to V1+ and signal return to VI1−; leave I1+ unused. The corresponding pairs are V2+/VI2−, V3+/VI3− and V4+/VI4− for the other channels. The measured voltage must stay within the selected range.
Current input: Bridge the channel's Vn+ and In+ terminals. For CH1, join V1+ to I1+, connect the signal to this point and its return to VI1−. A typical two-wire 4–20 mA loop is +24 V → sensor +; sensor − → bridged V1+/I1+; VI1− → 0 V. Check the sensor's own documentation when completing the current loop.
Use an adequately rated 24 VDC power supply, shielded signal cable and appropriate grounding. Route signal cables away from motor power wiring. The channel return and the FE shield/earth terminal serve different purposes.
Programming software and programming cable
Create the CPU application with WPLSoft or ISPSoft supporting the actual CPU. ISPSoft uses a communication driver selected through COMMGR. Configure and read DVP04AD-E2 through FROM/TO instructions in the CPU's ladder program; the module does not receive a separate user program.
ES2/EX2 CPU COM1 connection: DVPACAB2A30 is a 3 m RS-232 programming cable with a 9-pin female D-Sub at the PC end and an 8-pin mini-DIN at the PLC end. A PC without RS-232 needs a suitable USB-to-RS-232 adapter and its driver. Select the assigned COM number in the software. The PLC programming cable connects to the CPU; analog terminals are not a programming port. RS-232, RS-422 and RS-485 cables are electrically different.
Control registers and short program example
CR#0: model code H0080; CR#1: firmware version; CR#2–CR#5: CH1–CH4 modes; CR#8–CR#11: averaging counts 1–100, default 10; CR#12–CR#15: averaged values; CR#20–CR#23: present values; CR#43: error status.
Example for special module number 0: On an initialisation pulse, TO K0 K2 K6 K1 sets CH1 only to 4–20 mA. FROM K0 K12 D100 K4 reads the four averaged channel values into D100–D103. Replace K0 if the special-module number differs. This example does not change the other three channel modes.
ES2 automatic mapping: With M1183 OFF, the first special module's channel values can be read through D9900–D9903; the second module's group starts at D9910. Modules are numbered 0–7 according to distance from the CPU and do not consume ordinary digital X/Y addresses.
Retaining settings: Write H5678 to CR#41 to save verified retentive parameters. Do not execute the save command continuously. Interpret CR#43 as a bit field; multiple faults may occur together. Confirm input mode and error status before sending scaled values to the HMI or a PID controller.
Editor's Note
For a used module, the POWER LED alone does not establish condition. Test every channel separately with a known signal source at low, middle and high points. For Mode 6, 4, 12 and 20 mA checks help separate mode, wiring and channel problems.
Before removing a module that does not read current, inspect the V+/I+ bridge. Repeated program changes will not replace a missing bridge. A multimeter measures loop current in series; voltage is measured in parallel across the appropriate terminals.
Remember that the channels are not isolated from each other. Do not casually join different ground potentials from separate machines. If the sensor signal is stable but the reading fluctuates, inspect shielding, supply quality and cable routing first.
In 4–20 mA mode, 4 mA represents zero process value; a raw reading of 0 alone does not prove a broken wire. Assess the lower-range behaviour, error registers and actual loop current together. A disabled channel may report 32767, which also needs to be recognised.
A Pt100 does not connect directly to this module; use a suitable temperature module or a transmitter with a compatible analog output. A potentiometer test circuit needs a reference voltage within the input range. Connecting an ordinary resistor alone does not generate a valid analog test signal.
Back up channel modes, averaging and any calibration values before replacement. The sensor's labelled range, PLC calculation and HMI units must agree. Verify the raw signal first, then convert to bar, metres or percent. After saving, cycle power and confirm that the settings remain.
PDF manuals and related topics
Document centre: Delta DVP PLC files. DVP Series Module Manual, 6 January 2026, Chapter 3 covers DVP04AD-E2 specifications, registers and wiring. Review it together with the CPU programming and cable documentation.
Related topics: DVP04AD-E2 main page · DVP-E2 modules · DVP expansion modules · DVP PLC series · Delta PLC · Delta main page.
External references
Delta DVP Series Module Manual — English, 6 January 2026, Chapter 3 · Delta ES2/EX2 programming manual — English · Delta ISPSoft / COMMGR connection guidance.