Delta DVP48EC00T3
Delta DVP48EC00T3 · DVP-EC3 PLC with 28 Inputs and 20 Transistor Outputs
The Delta DVP48EC00T3 is a block-type PLC main unit in the DVP-EC3 family. It runs on 100–240 V AC. Its 48 I/O points comprise 28 digital inputs rated for 24 V DC and 20 NPN transistor outputs. Typical uses include sensor monitoring, sequencing and DC load control on conveyors, packaging lines and assembly machines.
Inputs, outputs and terminals
Inputs X0–X33 and outputs Y0–Y23 use octal addressing. X10 follows X7. When connecting an inductive sensor, photoelectric sensor or limit switch, check the PNP or NPN signal type and S/S input common against the panel schematic.
The NPN open-drain outputs switch DC control circuits. For a contactor or valve coil, check the output-group common, load supply, coil inrush current and transient suppression together. Use the terminal drawing for the 48-point T3 unit.
Pulse output and related Delta models
The model specifications list independent pulse outputs on Y0 and Y1 at up to 10 kHz. When connecting a servo drive or stepper motor drive, match the pulse format, electrical input type and required frequency. For encoder counting, check the input assignment and selected counter mode separately.
The DVP48EC00R3 has the same 28 inputs and 20 outputs with relay switching. The DVP40EC00T3 provides 24 inputs and 16 transistor outputs. The DVP60EC00T3 provides 36 inputs and 24 transistor outputs.
Programming software, 4K memory and connection cable
Use WPLSoft for PLC programming, ladder editing and online monitoring. The DVP48EC00T3 model listing specifies 4K program steps. The EC3-8K target in Delta’s newer programming manual applies to the listed CPUs with V8.60 or later. Before using ISPSoft, identify the CPU online, verify its supported target and configure the serial channel in COMMGR.
The PC connects to COM1, the 8-pin mini-DIN RS-232 port. For a USB-equipped computer, use the UC-PRG020-12A cable. Install the driver and select the COM number assigned by Windows. A PC with a physical RS-232 port can use the UC-MS020-01A cable.
The RS-485 interface on COM2 handles industrial communication with an HMI panel and other field devices. On a Modbus RTU link, match the station address, baud rate, parity and data format.
Editor’s Note
Start with the nameplate on a used unit. The 48EC00T3 and relay-output 48EC00R3 have the same I/O count. Photograph the output commons before removing the old PLC.
On the bench, first read the program through COM1 and record the CPU type detected by the software. Test field communication through COM2 separately.
If the output LED turns on without switching the load, check the group common and field supply first. Use a suitable DC test load to verify switching.
When Y0/Y1 are used for pulses, check signal level and waveform before connecting the drive. If counts become unstable while the motor runs, check cable routing, panel grounding and the EMC filter connection, if fitted.
Keep the PLC program, required retained data and serial settings in the same machine folder. When fitting a spare CPU, use those records to verify HMI addresses and the I/O sequence.