Delta AS218TX-A

Delta AS218TX-A AS200 PLC with NPN outputs

The Delta AS218TX-A is a compact 24 V DC PLC CPU in the Delta AS200 family. It has a 64K-step program capacity and 18 built-in I/O points, including 8 digital inputs, 6 NPN transistor outputs, 2 analog inputs and 2 analog outputs.

Digital and analog I/O

The supply range is 20.4–28.8 V DC. The 24 V DC inputs are addressed X0.0–X0.7 and the NPN outputs Y0.0–Y0.5. An active NPN output sinks load current to 0 V. For 5–30 V DC resistive loads, the limits are 0.5 A per output and 1.5 A total per common. When wiring an inductive sensor, check that the S/S input common matches the sensor type.

The analog channels have 12-bit resolution. Inputs support ±10 V or ±20 mA. Outputs support ±10 V or 0–20 mA. For example, read a 4–20 mA pressure transmitter on a current input and scale 4 mA and 20 mA to the lower and upper measurement values. See the analog signal guide for wiring and scaling background.

Programming, cable and communications

Use ISPSoft for the project and COMMGR for the PC connection. Connect through a USB-to-Mini USB data cable or RJ45 Ethernet. The CPU also has two RS-485 ports, CANopen and a microSD slot. See Delta PLC software for version and driver information.

Related models and expansion

The AS218PX-A has PNP transistor outputs, and the AS218RX-A has relay outputs. The AS228T-A, AS228P-A and AS228R-A offer 16 inputs and 12 outputs in NPN, PNP and relay versions respectively. The AS228 models lack the AS218’s built-in analog channels.

For additional channels, see the AS expansion modules, including digital I/O and analog measurement modules.

Editor’s Note

When buying used, read the full label first. The TX-A suffix identifies the NPN version.

With power off, check the removable DIO and AIO terminals for burning, looseness or missing blocks.

Before replacing a CPU, back up the old PLC program, module order and network settings.

On the bench, test both output groups, C0 and C1, separately with a suitable DC test load.

Apply a known current or voltage to the analog input and measure the analog output. Compare the readings with the scaling in the program.

Related topics

Delta AS PLC series · Delta PLC accessories

Delta PLC · Used Delta equipment · Delta PLC and HMI manuals

External references

Delta AS Hardware and Operation Manual (EN) · AS218 wiring sheet (EN section, distributor copy)