Delta AS218RX-A

Delta AS218RX-A Relay Output PLC

Delta AS218RX-A is a 24 V DC PLC CPU in the Delta AS200 series. It has 8 digital inputs, 6 relay outputs, a 64K-step program capacity and built-in 2 analog inputs and 2 analog outputs. In a pump panel, it can read pressure or level, switch a contactor through a relay output and send a drive speed reference through an analog output.

Digital inputs, relay outputs and model selection

Inputs X0.0–X0.7 accept 24 V DC signals. Wire the S/S common for the output type of the field sensors. Relay outputs Y0.0–Y0.5 are arranged in groups of three with commons C0 and C1. Delta specifies a resistive-load limit of 2 A per output and 6 A per common. For coils and contactors, check the relay life curve and the load suppression circuit.

The AS218PX-A uses PNP transistor outputs, and the AS218TX-A uses NPN transistor outputs. Consider these models when the application requires built-in high-speed pulse output. The AS228R-A provides 16 digital inputs and 12 relay outputs. If the existing AS218RX-A project uses its analog channels, allow for analog expansion when selecting the AS228R-A.

Analog input and output ranges

The built-in analog channels have 12-bit resolution. Inputs support ±10 V or ±20 mA. Outputs support ±10 V or 0–20 mA. For a 4–20 mA transmitter, select current input and scale 4 mA and 20 mA to the lower and upper measurement limits in the program. For more channels, choose suitable AS analog measurement modules by signal type.

Programming and expansion

Create the PLC project in Delta ISPSoft and manage the connection through COMMGR. Use the PLC IP address for Ethernet. USB requires a Mini USB-B data cable, the Delta USB driver and the USB (Virtual COM) setting. Delta lists UC-PRG015-01A and UC-PRG030-01A as PLC programming cables. The CPU also has two RS-485 ports and built-in CANopen. Check the project and firmware versions when configuring the CANopen network with CANopen Builder.

Up to 32 compatible AS expansion modules can be installed to the right of the CPU. Check I/O addresses when adding AS digital modules. When choosing an AS-PS02 or another suitable AS power supply, add up the current draw of the CPU and modules.

Editor’s Note

When buying used, confirm the AS218RX-A label and check that the analog terminal block is present.

If the old CPU is accessible, save the project, IP address and analog scaling before replacement.

Even if the relay clicks, test each contact with a suitable bench load.

Test the current input at 4 and 20 mA. The program values should match the two ends of the transmitter span.

If an analog output feeds a drive, check the output range and the drive reference source before enabling automatic operation.

Related topics

Delta AS PLC series · Delta AS300 · Delta DOP-100 panels · Delta PLC software

Delta PLC and HMI manuals · Delta PLC category · Second-hand Delta products

External references

AS218 instruction sheet (includes EN and TR) · AS hardware and operation manual (EN) · AS Series catalogue (EN) · ISPSoft user manual (EN)