Delta AS-FPFN02
Delta AS-FPFN02 PROFINET Function Card
Delta AS-FPFN02 is a dual-RJ45 AS function card that connects compatible Delta AS hardware to a PROFINET RT network as an IO Device. It exchanges line status, process values and commands cyclically with a PROFINET IO Controller such as a Siemens S7-1500.
CPU, COM and RTU Modes
CPU mode · Install the card in the function card slot of a Delta AS300 CPU. For models such as the AS332T-A and AS332P-A, minimum firmware is V1.08 for the CPU and V1.00 for the card. Map PROFINET data to the CPU’s D registers.
COM mode · Install the card in an AS00SCM-A mounted to the right of an AS100, AS200 or AS300 CPU. Minimum firmware is V2.02 for the card, V2.08 for AS00SCM-A and V1.14 for the CPU. PROFINET access is limited to the data exchange area between the AS00SCM-A and the CPU.
RTU mode · Use AS00SCM-A and AS expansion modules as a PROFINET remote I/O station. Minimum firmware is V2.00 for the card and V2.06 for AS00SCM-A. Add the station’s digital I/O modules to the project in their physical installation order.
GSDML, Ports and Diagnostics
X1 and X2 are switched 10/100BASE-TX ports. Delta specifies CAT5e network cable for runs of up to 100 m per link. For a Siemens controller, import the GSDML definition for the selected mode into TIA Portal. Match the station name on the card to the project and check I/O lengths, data direction and address assignments.
On the Delta side, verify the hardware and data areas in ISPSoft or a supported version of DIADesigner. For an ISPSoft PC-to-PLC connection, check COMMGR settings. A solid red BF indicates that the PROFINET connection has not been established. For solid red SF, check the topology and RTU module arrangement.
OtomasyonAVM documentation · Delta PLC and HMI manuals.
Editor’s Note
When buying a used card, ask for a firmware screenshot and a label photo.
V1.00 hardware does not support direct upgrades to V2.00. Choose a card with suitable firmware for RTU or COM mode.
Record the station name and data mapping before removing the original card.
When tracing a link fault, check the X1/X2 link LEDs and the BF indicator together.
Use a known test value to verify data direction and addresses during commissioning.
Related Topics
Review AS-FEN02 for EtherNet/IP and Modbus TCP, AS-FCOPM for CANopen and AS-F485 for RS-485. Match the card to the system protocol.
Delta AS PLC series · Delta PLC accessories · Delta PLC models · Second-hand Delta automation
External references · Delta AS Module Manual, section 10.2.8 · Delta AS Hardware and Operation Manual · Delta Download Center and GSDML