Delta AS function cards

Delta AS function cards

Delta AS function cards add serial ports, industrial networking or analog channels to compatible AS300 CPU slots. Select the card by interface, protocol and available slot. See AS expansion modules for additional field I/O.

Serial communication cards

The AS-F232 adds point-to-point RS-232, the AS-F422 adds differential RS-422, and the AS-F485 adds RS-485. On a multi-station Modbus RTU network using AS-F485, check the station address, baud rate, parity and termination.

CANopen, Ethernet and PROFINET

The AS-FCOPM supports CANopen DS301 and connects compatible Delta remote I/O or servo systems. Use CANopen Builder to check nodes, data mapping and the EDS file on the CANopen network.

The AS-FEN02 provides Modbus TCP Client/Server and EtherNet/IP Adapter functions with two RJ45 ports on an AS300 CPU. The AS-FPFN02 operates as an IO Device on a PROFINET RT network. Match the protocol and the card’s network role to the other device on the Ethernet network.

Analog input and output cards

The AS-F2AD reads sensors through two analog inputs. The AS-F2DA provides two analog outputs to send references to drives or controllers. Both offer 0–10 V and 4–20 mA modes. Set the analog signal type and scaling in the project. See AS analog and measurement modules for more channels.

Slot and software compatibility

On AS300, serial and analog cards occupy one slot and can fit in Slot 1 or 2. AS-FCOPM fits in Slot 2. AS-FEN02 and AS-FPFN02 are selected in Slot 2 and occupy both slots.

If you use a card on an AS00SCM-A with a CPU such as AS200, check the supported COM or RTU mode and firmware in the card manual. Installing AS-FCOPM in Slot 2 of AS00SCM-A disables Slot 1. Select the card in its physical slot in ISPSoft HWCONFIG. Use COMMGR for the PC-to-PLC connection.

Editor’s Note

Read the full CPU and card model codes and check their firmware versions.

Check how many slots the card occupies, even if Slot 2 appears free.

Save the hardware and communication settings before replacing a card.

Choose the matching EDS file for CANopen or GSDML file for PROFINET.

For the first test, read one data area or measure one analog channel to verify scaling.

Related topics and PDFs

AS Series Operation Manual (EN, 2018 archive edition) · Delta PLC accessory PDFs

Delta AS PLC series · Delta PLC models