Delta AS04DA-A

Delta AS04DA-A 4-channel analog output module

The Delta AS04DA-A is a four-channel analog output module in the Delta AS analog and measurement module range. It converts PLC commands into analog signals for drive speed references, proportional valve commands or recorders. It provides 12-bit hardware resolution and 2 ms per channel conversion time. The external supply is 24 V DC, with a range of 20.4–28.8 V DC.

Output ranges and terminals

Each channel is individually configurable. Voltage modes are ±10 V, 0–10 V, ±5 V, 0–5 V and 1–5 V. Current modes are 0–20 mA and 4–20 mA. On the removable terminal block, VO1–VO4 are voltage outputs, IO1–IO4 are current outputs and AG is the analog reference. Total load resistance in current mode must stay at or below 550 Ω.

The analog and digital circuits are isolated from each other. Analog channels share the same isolation domain, so check the signal reference when connecting devices at different potentials. Route shielded signal cables separately from power wiring and follow Delta’s diagram for SLD. See Delta AS power supplies and PLC accessories for panel planning.

ISPSoft, channel setup and scaling

The unit connects alongside other AS expansion modules in an AS200 or AS300 system. In ISPSoft, use HWCONFIG to set the module position, CH1–CH4 output modes and data format. Connect the PC to the CPU using COMMGR and a suitable Delta PLC cable. See Delta PLC software for software documentation.

With nominal integer scaling, commands of 0, 16,000 and 32,000 give 0, 5 and 10 V in 0–10 V mode and 4, 12 and 20 mA in 4–20 mA mode. In ±10 V mode, −32,000, 0 and +32,000 correspond to −10, 0 and +10 V. When selecting 0–10 V or 4–20 mA, match the receiver input to the PLC scale. For 4–20 mA calibration, Delta specifies mode 9 with firmware V1.02 or later.

Editor’s Note

On the bench, check the full label first. The AS04DA-A sends outputs and the AS04AD-A reads inputs.
With power off, inspect 24V, 0V and the removable terminal block. Select VO or IO according to the channel mode.
Use a test setup disconnected from the machine. Check each channel with a suitable meter at low, mid and full scale.
In 4–20 mA mode, expect about 12 mA at mid-scale. If it drops under load, check loop resistance and wiring.
Record the old module’s channel settings before removal. Before commissioning, check the output retention setting on a safe test setup.

Related topics and PDFs

The AS04AD-A provides four analog inputs. The AS06XA-A provides four analog inputs and two analog outputs. Eight-channel input options include the AS08AD-B voltage input module and the AS08AD-C current input module.

Delta PLC and HMI manuals · More Delta pages · Delta AS PLC series · Delta PLC main page · Used Delta equipment

External references

AS04DA-A installation and wiring sheet (PDF, EN and TR included) · Delta AS Module Manual, Chapter 4 (PDF, EN) · Delta AS Hardware and Operation Manual (PDF, EN)