Delta VFD-M Fault Codes 2

Delta VFD-M Fault Codes, Page 2 covers overheating, overload, serial communications and external control faults. Record the letters and decimal points exactly as displayed. Parameter references on this page use the ME14 / SW V3.04 English manual.

Delta VFD-M drives in an industrial cabinet, from OtomasyonAVM

Fault code index

oH · oL / oL1 / oL2 · PHL · cF1 / cF2 · cE1 · EF / bb · GFF / HPF / cF3 · cFA / FbE / codE

Fault codes, page 1 · Delta VFD-M manuals

oH — Drive overheating

The keypad displays oH. The troubleshooting flowchart uses the heading OH1. Review cabinet temperature, airflow, fan condition where fitted and the drive’s carrier frequency. If it trips only during a long production run, record the load and how long it had been running. Check the specified ventilation and mounting conditions before restarting.

oH entry · p. 133 · Overheating flowchart · p. 125

oL / oL1 / oL2 — Drive overload, thermal protection and over-torque

oL indicates drive overload. oL1 relates to electronic motor thermal protection. Compare the motor nameplate current with Pr.52. For oL2, the manual points to Pr.60–Pr.62 for over-torque detection. Use the actual machine load and current at the time of the trip when reviewing the current limit and drive rating.

Overload table · p. 133 · Turkish fault table · p. 17

PHL — Input phase loss

Confirm the input supply type on the nameplate. For a three-phase input unit, review supply events, fuses, contactor history and connections. Note whether other equipment stopped at the same time. Leave cabinet measurements and connection checks to qualified personnel.

PHL entry · p. 135 · Input phase loss flowchart · p. 126

cF1 / cF2 — Internal memory write and read faults

cF1 means the drive could not write to internal memory. cF2 means it could not read it. Record whether the fault appeared at power-up or while saving settings. Give service personnel the last working parameter backup if available. A factory reset changes settings and should be considered only when the machine’s settings and commissioning conditions are documented.

Internal memory entries · p. 134 · Turkish fault table · p. 18

cE1 — Serial communication fault

Start with the most recent work on the RS-485 wiring, PLC or HMI. Match the controller and drive at Pr.88 for address, Pr.89 for baud rate and Pr.92 for protocol. Check the Modbus ASCII or RTU mode and serial frame. If trips coincide with a contactor switching, review EMC and input filtering as well as control cable routing.

cE1 entry · p. 134 · RS-485 parameters · pp. 93–95

EF / bb — External fault and Base Block

EF comes from the external fault input. bb indicates external Base Block. Both can turn off the drive output. Use the control wiring diagram to find the relay, field device or PLC output that sent the signal. Leave input wiring intact and follow the machine’s approved safety circuit and isolation procedure.

EF and bb entries · p. 134

GFF / HPF / cF3 — Output ground fault and hardware diagnostics

GFF indicates a ground fault at the motor output. Leave protective earth connected. Have qualified personnel check motor and cable insulation with the motor circuit disconnected from the drive. The decimal point in HPF or cF3 can distinguish different hardware entries. Photograph the display and match it to the manual. Qualified service should assess the power stage if the fault recurs.

GFF entry · p. 134 · Hardware fault table · p. 135

cFA / FbE / codE — Ramps, feedback and software

cFA means automatic acceleration or deceleration failed. Record the load and the acceleration or deceleration ramp active when it tripped. FbE indicates a PID feedback fault. The manual points to Pr.116 for feedback source and Pr.123 for loss detection time. For a codE software protection fault, give service personnel the full code and drive model.

cFA entry · p. 134 · FbE and codE entries · p. 135

Motor will not run, speed stays fixed, or the display is blank

No RUN indication. Identify whether the keypad, terminals or communications issue the command. RUN active and speed stays fixed. Check the frequency reference, preset speed selection and upper frequency limit. Blank display. Record the drive and keypad model numbers together.

The motor stalls on acceleration. Check the nameplate, motor rated frequency, load movement and ramp record to narrow down the cause.

Troubleshooting by symptom · PDF pp. 126–130

Editor’s field notes

Take a photo before pressing RESET. On the VFD-M, the position of a decimal point can change the fault you are looking at.

Record Pr.73, Pr.74 and Pr.75 in order. Those are the last three faults. Add what the machine was doing at the time.

For oL2 on startup, find out whether the machine moves freely. Find out what changed in the load before raising a detection threshold.

If cE1 started after wiring work, compare the settings at both ends. For EF or bb, trace the signal that stopped the machine.

Clear the cause and verify that RUN is off before resetting. Before opening the cabinet, qualified personnel must isolate the supply and measure the DC bus to verify discharge.

Fault history · PDF p. 132 · Reset conditions · PDF p. 136

OtomasyonAVM PDF archive

Turkish quick guide · fault table, pp. 17–18 · English manual 1 · ME14, Chapter 6, pp. 132–136 · English manual 2 · Chapter 7, pp. 93–96 · English manual 3 · quick reference, pp. 17–18

Related topics

Common inverter faults · How an AC drive works · AC drive accessories

Regenerative energy · Braking resistors · Dynamic braking

Delta VFD-M navigation

Delta VFD-M manuals · Fault codes, page 1 · Delta manuals · Delta main page

Derell