How are time relay settings made and what do they include?
Hello, dear readers,
Setting a time relay involves more than turning a dial to a number. The operating function, time unit, time range, starting condition and reset behaviour must work together. Some devices allow only a few of these to be changed. First define which event should cause the output to change, and then set the duration.
For the basic principle, see how a time relay works; for the available functions, read time relay types. The sequence below is a general method. Function letters, menus and dial scales vary by model.
1. Identify the model and the required behaviour
Check the complete model code and supply voltage on the label, then obtain that model's connection diagram and timing chart. Devices in the same series can have different inputs, outputs or timing ranges. A simple time relay may have a fixed function, while a multifunction time relay may provide a function selector.
Write down the requirement clearly. Should the output activate fifteen seconds after a command? Should a fan continue running after the command disappears? Should on and off periods repeat? The same duration produces different results in different operating modes.
Follow the manufacturer's instructions before changing function, unit or range switches. Many models require these changes to be made with power removed. If work inside a panel is necessary, isolate the relevant circuits and verify the absence of voltage. A STOP command does not mean that electrical power has been disconnected.
2. Select the timing function
ON-delay waits after the starting condition before activating the output; see our on-delay timer guide. OFF-delay keeps the output active for a period after the control signal is removed; an off-delay timer performs a different task. A signal-controlled off-delay timer must remain powered during the delay.
In interval mode, the output remains active for a defined duration following the specified starting event. In flasher or cyclic mode, set the ON time, OFF time and, where supported, the initial output state. For example, five seconds on and twenty seconds off make a twenty-five-second cycle.
Function letters do not necessarily mean the same thing across manufacturers. Multifunction also does not mean that every function operates simultaneously. Compare menu selections on a programmable time relay with the corresponding timing chart.
3. Read the unit, range and time value together
ms means milliseconds, s seconds, min minutes and h hours. Choosing the wrong unit changes the meaning of the same number completely. The time range defines the available interval or scale multiplier; the main dial selects a value within it. On an analog time relay, do not read the dial number without checking the unit and range.
Use an appropriate range that covers the required duration and follows the manufacturer's recommendations. In particular, when error is specified as a percentage of full scale, setting a short duration at the bottom of an unnecessarily large range can impair the result. A larger range does not mean a more precise setting.
4. Check starting, retriggering and reset behaviour
Starting when power is applied and starting from a separate input signal are different arrangements. Check whether the signal input expects a dry contact or a particular voltage level. Do not guess which voltage to apply. Our guide to time relay input and output components helps explain this distinction.
A rising edge is a transition from inactive to active; a falling edge is the reverse. Not every timer offers edge selection. Whether a new signal restarts the time, is ignored or causes another response depends on the retriggering function. In circuits triggered by a PLC, also account for the input's required minimum signal duration.
A reset input, removal of the start signal and loss of supply do not have identical effects on every device. Observe the manufacturer's minimum reset time. A digital display or settings memory does not necessarily mean that elapsed time survives a power interruption. Retaining settings and retaining elapsed time are separate features.
5. Choosing a contact differs from setting an output mode
With an electromechanical relay output, COM identifies the common terminal, NO the normally open contact and NC the normally closed contact. On most timers, choosing NO or NC means connecting to the appropriate terminal. These are not universally interchangeable menu settings.
Some models allow one output to operate with a time delay and another instantaneously; use only the arrangements supported by the device. Timers with solid-state outputs have a different construction. When controlling larger loads, consider the difference between a relay and a contactor and select suitable contactors. Adjusting the duration does not change the output's load capacity.
6. Additional settings on digital, clock-based and star-delta timers
On a digital device, enter the duration and unit, confirm the selection as instructed and check it again on the operating display. Use a parameter lock if one is available. Check whether a duration changed during operation applies to the current cycle or the next one; do not assume identical behaviour across models.
On a device using an RTC or weekly time switch, check the current time, day, switching schedule and any daylight-saving settings. These differ from setting an elapsed duration after a trigger. Our guide to the difference between a time relay and a timer explains the distinction.
On a star-delta time relay, distinguish the time in star from the changeover delay. Whether the changeover interval is fixed or adjustable depends on the model. Verify the timing against the motor, load and starter arrangement.
7. Do not confuse resolution with actual timing accuracy
Setting resolution is the smallest increment that can be entered. Setting error is the difference between the selected value and the actual duration; repeatability describes how closely repeated measurements agree under the same conditions. A display with 0.01-second steps does not, by itself, establish an actual timing accuracy of ±0.01 seconds.
Check whether the tolerance refers to the set value or full scale (FS). For example, a tolerance of ±1% FS on a one-hundred-second full scale corresponds to ±1 second. Setting ten seconds does not make that tolerance ±0.1 seconds. This example calculates the stated tolerance; other specified conditions must also be considered when assessing total error.
8. Measure the result and record the settings
During a controlled test, measure from the actual starting event to the output's change of state. Repeat several cycles and test early signal removal, retriggering and behaviour after power interruption. A stopwatch helps with a rough check of intervals lasting seconds or minutes; verifying tight millisecond tolerances requires an appropriate measurement setup.
Record the model code, function, unit and range, selected duration, reset behaviour and measured result in the maintenance log. For unexpected results, see time relay fault diagnosis. A complete settings record is much more useful during later maintenance than “the dial was at five”.
For circuit selection, read time relay selection and installation; for connection principles, see creating a timing circuit; and for examples, explore circuits that use time relays. Any benefit from shortening a duration should be measured while maintaining the required process conditions, as discussed in improving automation processes with time relays.
Technical references: OMRON settings and operating functions · Reset and accuracy terminology · Finder triggering and reset diagrams