Toshiba VF-PS1 Fault codes 5
Toshiba VF-PS1 Fault Codes 5 – Encoder, CPU, I/O and Control Circuit Faults
This section covers the E-11, E-12, E-13, E-17, E-18, E-19, E-20, E-21, E-22, E-23, E-24, E-25, E-26, E-29, SOUt and PrF fault codes used on Toshiba VF-PS1 variable frequency drives. These faults are mainly related to terminal inputs, encoder feedback, internal CPU communication, optional I/O cards, control-power backup and PM motor operation.
Several codes in this group are closely related but do not represent the same condition. For example, E-12, E-13 and E-25 may all involve encoder feedback, while E-19, E-21 and E-26 refer to different CPU or internal control functions.
E-11: Sequence Error
E-11 indicates that the VF-PS1 has not received the required sequence or input-terminal condition expected by the control logic.
Possible causes:
The required system signal has not been applied to the input terminals.
Input-terminal function 130 or 131 has not been assigned.
Checks and solutions:
Check whether the machine-control sequence is operating correctly.
Assign the appropriate input terminal to function 130 or 131.
E-12: Encoder Error
E-12 indicates that the inverter cannot correctly receive the encoder feedback signal. The encoder wiring and A/B-phase connections should be checked first.
Possible causes:
The encoder circuit is disconnected.
The encoder is not connected correctly.
Checks and solutions:
Check the encoder cable and connections.
Make sure the encoder is connected correctly.
Check whether parameter F376 corresponds to the encoder phase-A and phase-B connections.
E-13: Speed Error – Overspeed
E-13 indicates that the speed-feedback condition has moved outside the expected operating range and the drive has detected an overspeed condition. The encoder circuit is the first area to inspect according to this fault information.
Possible cause:
Encoder or encoder-feedback error.
Solution:
Check the encoder connection and make sure the encoder is wired correctly.
E-17: Key Malfunction Alarm
E-17 is displayed when the same key on the operation panel remains pressed continuously for more than 20 seconds.
Possible cause:
A key has remained continuously pressed for more than 20 seconds.
Solution:
Check the operation panel and the mechanical condition of its keys.
E-18: Terminal Input Error
E-18 indicates a problem on the terminal-input or terminal-control-board side of the VF-PS1.
Possible causes:
The VI/II input-signal cable is disconnected.
The terminal control card is not correctly installed.
Checks and solutions:
Check the VI/II input signal and wiring.
Insert the terminal control card correctly into the inverter.
Check the P24 terminal for a short circuit to CC or CCA.
E-19: CPU2 Communication Error
E-19 indicates that an error has occurred during internal communication with CPU2.
Possible cause:
An internal CPU2 communication error has occurred.
Solution:
Contact technical service.
E-20: V/f Control Error
E-20 indicates that the inverter has detected an internal control error during V/f motor control.
Possible cause:
An internal control error has occurred.
Solution:
Contact technical service.
E-21: CPU1 Error
E-21 indicates a software-related error in the CPU1 control section of the inverter.
Possible cause:
A software error has occurred in the control CPU.
Solution:
Contact technical service.
E-22: Abnormal Logic Input Voltage
E-22 indicates that the voltage applied to a logic input terminal is outside the expected operating condition.
Possible cause:
Abnormal voltage has been applied to the logic input terminal.
Solution:
Check the signal and voltage connected to the logic input terminal.
E-23: Option 1 Error
E-23 is associated with Expansion I/O Card 1 installed in the VF-PS1.
Possible cause:
Expansion I/O Card 1 is faulty.
Solution:
Contact technical service.
E-24: Option 2 Error
E-24 belongs to the same option-card fault group but refers to Expansion I/O Card 2.
Possible cause:
Expansion I/O Card 2 is faulty.
Solution:
Contact technical service.
E-25: Position Hold Error
E-25 indicates that an unacceptable position deviation has occurred during position-hold control. Encoder feedback and creep speed are particularly important when this fault appears.
Possible causes:
A deviation error occurred during position-hold control.
The creep speed is too high.
Checks and solutions:
Check the encoder connection.
Adjust the proportional P gain using parameter F362.
Reduce the creep speed.
Relationship Between E-12, E-13 and E-25
E-12 is directly related to encoder wiring and feedback, E-13 indicates an overspeed condition associated with encoder feedback, and E-25 indicates excessive deviation during position-hold control. Checking the encoder circuit is common to these faults, but the operating condition that generates each code is different.
E-26: CPU2 Error
E-26 indicates a fault in the motor-control CPU2 or its associated driver circuitry.
Possible causes:
The motor-control CPU is faulty.
The inverter driver circuit board is damaged.
Solution:
Contact technical service.
Difference Between E-19, E-21 and E-26
E-19 indicates a CPU2 communication error, E-21 indicates a CPU1 software fault, while E-26 points to the motor-control CPU2 or its associated driver circuitry.
E-29: Control Power Backup Low Voltage Error
E-29 indicates that the VF-PS1 has detected insufficient control voltage between +SU and CC, or that the control-power backup configuration is incorrect.
Possible causes:
The control voltage between +SU and CC terminals is too low.
Control power is not being supplied through the +SU and CC terminals.
Parameter F647 is not set correctly.
Checks and solutions:
Check that the voltage between +SU and CC is 20 VDC or higher.
If the control-power backup device is not used, set F647 to 0.
To reset the inverter after an E-29 trip, turn the inverter off and then back on.
The causes and checks for E-29 are similar to the CFF control-power backup undervoltage condition described in Fault Codes 1, although the displayed code is different.
SOUt: Step Loss – PM Motors Only
SOUt is specific to PM motor applications and indicates that the motor has failed to follow the expected operating condition.
Possible causes:
The motor shaft is locked.
One output phase is open.
A shock load has been applied.
Checks and solutions:
Release the motor shaft from the mechanical lock.
Check the connection cables and output phases between the inverter and motor.
PrF: Power Cutoff Circuit Error
In this fault group, PrF indicates a power-cutoff circuit error associated with the inverter's internal power-cutoff circuitry.
Possible cause:
A fault has occurred in the power-cutoff circuit.
Solution:
Contact technical service.
Important Note About the PrF Code
The VF-PS1 fault information also uses PrF in another section for the condition “PWR signal is off.” On this page, however, PrF means “Power Cutoff Circuit Error.” The surrounding fault group and description must therefore be considered when interpreting the code.
Toshiba VF-PS1 Fault Codes
• VF-PS1 Fault Codes – Main Index
• VF-PS1 Fault Codes 1 – nOFF, rtry, Err1, Clr, EoFF, HiLd, OFF, PrF, CFF, OC1, OC2, OC3
• VF-PS1 Fault Codes 2 – OCA1, OCA2, OCA3, OCL, OCr, OH, OH2, OL1, OL2, OLr
• VF-PS1 Fault Codes 3 – OP1, OP2, OP3, OL, UC, UP1, E, EEP1, EEP2, EEP3, EF1, EPH0
• VF-PS1 Fault Codes 4 – EPH1, Err2, Err3, Err4, Err5, Err6, Err7, Err8, Etn, Etn1, Etn2, Etn3, EtyP, E-10
• VF-PS1 Fault Codes 5 – E-11, E-12, E-13, E-17, E-18, E-19, E-20, E-21, E-22, E-23, E-24, E-25, E-26, E-29, SOUt, PrF
VF-PS1 Technical Pages
• Toshiba VF-PS1 AC Drive Main Page
• Toshiba VF-PS1 User Manual and Technical Documentation
• Toshiba Drives and Automation Main Page