Toshiba VF-PS1 Fault codes 2

Toshiba VF-PS1 Fault Codes 2 – Short Circuit, Overheating and Overload Faults

This section covers the OCA1, OCA2, OCA3, OCL, OCr, OH, OH2, OL1, OL2 and OLr fault codes used on Toshiba VF-PS1 variable frequency drives. These faults are mainly related to the inverter output stage, motor and motor wiring, dynamic braking circuit, cooling system and overload conditions.

Repeated short-circuit, overcurrent or overheating faults should not simply be cleared and ignored. The circuit or operating condition indicated by the fault code should be checked before the drive is returned to service. For parameter details and commissioning information, refer to the Toshiba VF-PS1 User Manual.

OCA1: U Phase Short Circuit

The OCA1 fault indicates an abnormal condition in the U-phase section of the inverter main power circuit.

Possible cause:
Main circuit components associated with the U phase are faulty.

Solution:
Because this fault is associated with the inverter power stage, contact technical service.

OCA2: V Phase Short Circuit

OCA2 belongs to the same fault group as OCA1, but identifies a problem in the V-phase main circuit section.

Possible cause:
Main circuit components associated with the V phase are faulty.

Solution:
Contact technical service.

OCA3: W Phase Short Circuit

The OCA3 code indicates an abnormal condition in the W-phase section of the inverter main circuit. OCA1, OCA2 and OCA3 therefore represent the same basic fault group separated by output phase.

Possible cause:
Main circuit components associated with the W phase are faulty.

Solution:
Contact technical service.

OCL: Overcurrent at Startup on the Load Side

The OCL fault indicates that the VF-PS1 has detected abnormally high current on the motor side during startup. The cause may be in the motor, motor cable or the inverter output circuit.

Possible causes:
Insulation failure at the main circuit output or a motor fault.
Motor impedance is too low.
The inverter driver circuit board is damaged.

Checks and solutions:
Check the motor cables and wiring for insulation faults.
Check the startup short-circuit detection setting using parameter F613.
If the OCL fault occurs even when the motor is disconnected from the inverter, the inverter itself may be faulty. In this case, contact technical service.

For an OCL fault, an important first step is to determine whether the problem is on the motor/wiring side or inside the inverter.

OCr: Overcurrent in the Dynamic Braking Element

This fault applies to VF-PS1 models rated 200 V / 55 kW and above or 400 V / 90 kW and above. It is associated with the dynamic or regenerative braking circuit.

Possible causes:
The PB-PC circuit is short-circuited.
A braking resistor with a resistance below the minimum allowable value has been connected.
Parameter Pb is set to 1 or 2, but the regenerative braking circuit is not connected or the braking resistor circuit is open.

Checks and solutions:
Check the braking resistor and its wiring.
Check whether the regenerative braking circuit is connected correctly.
Check the Pb parameter setting according to the braking configuration.
If the resistor and wiring are correct but the fault remains, contact technical service.

OH: Overheating

The OH fault indicates that the internal temperature of the VF-PS1 has exceeded the permitted operating level, or that a problem exists in the temperature-detection system. The cause is not always high ambient temperature; the cooling fan and airflow around the inverter should also be checked.

Possible causes:
The cooling fan is not rotating.
The ambient temperature is too high.
The ventilation path is blocked.
A heat-generating device has been installed too close to the inverter.
The internal thermistor connection is open.

Checks and solutions:
Allow the inverter to cool sufficiently before restarting it.
Check the cooling fan and replace it if it is not operating.
Make sure the air inlet and outlet paths are not blocked.
Ensure that sufficient ventilation space is available around the inverter.
Do not install heat-generating equipment directly next to the drive.
If cooling conditions are normal but the OH fault remains, contact technical service for inspection of the thermistor and internal circuitry.

OH2: Thermal Shutdown Command from an External Device

OH and OH2 should not be treated as the same fault. OH indicates an overheating condition detected by the inverter itself, while OH2 is generated when an external thermal protection or control signal commands the inverter to stop.

Possible causes:
A signal has been applied to the PTG control input terminal.
A thermal shutdown command has been issued by an external control device using input-terminal function 46 or 47.

Checks and solutions:
Check whether the motor is overheating.
Check whether the motor current exceeds its rated value.
Check the external thermal protection circuit and the corresponding input signal.

OL1: Inverter Overload

With an OL1 fault, the overloaded component is the inverter rather than the motor. Excessively rapid acceleration, excessive DC braking or a load that continuously exceeds the inverter capacity can cause this fault.

Possible causes:
Acceleration is too rapid.
The DC braking amount is too high.
The V/f setting is incorrect.
The motor has been restarted shortly after stopping.
The load is too large.

Checks and solutions:
Increase the acceleration time using the ACC setting.
Reduce the DC braking amount F251 and DC braking time F252.
Check the V/f parameter settings.
Check the UuS (automatic restart) and UuC (regenerative power transition control) functions.
If the load continuously exceeds the drive capacity, a larger-capacity inverter may be required.

OL2: Motor Overload

OL2 is directly related to the motor load and motor thermal operating conditions. It should therefore be distinguished from OL1: OL1 is inverter overload, while OL2 is motor overload.

Possible causes:
The V/f parameter setting is incorrect.
The motor is locked.
The motor is operating continuously at low speed.
The motor is overloaded during operation.

Checks and solutions:
Check the V/f parameter settings.
Check whether the motor rotates freely and inspect the connected machine load.
Check the OL1 setting and adjust F605 according to the motor's allowable overload at low speed.
Reduce the DC braking amount F251 and DC braking time F252.

OLr: Dynamic Braking Resistor Overload

The OLr fault indicates that the dynamic braking resistor is being subjected to excessive load. During rapid deceleration, regenerative energy from the motor may exceed the thermal or power capacity of the braking resistor.

Possible causes:
Deceleration is too rapid.
The dynamic braking duty is too high.

Checks and solutions:
Increase the deceleration time using the dEC setting.
Check the capacity of the dynamic braking resistor.
If necessary, increase the braking resistor capacity and check the PBR capacity parameter PbC.

Difference Between OL1, OL2 and OLr

OL1 indicates inverter overload, OL2 indicates motor overload and OLr indicates dynamic braking resistor overload. Although all three belong to the overload group, the component being protected and the troubleshooting procedure are different.

Toshiba VF-PS1 Fault Codes

• VF-PS1 Fault Codes – Main Index
• VF-PS1 Fault Codes 1 – nOFF, rtry, Err1, Clr, EoFF, HiLd, OFF, PrF, CFF, OC1, OC2, OC3
• VF-PS1 Fault Codes 2 – OCA1, OCA2, OCA3, OCL, OCr, OH, OH2, OL1, OL2, OLr
• VF-PS1 Fault Codes 3 – OP1, OP2, OP3, OL, UC, UP1, E, EEP1, EEP2, EEP3, EF1, EPH0
• VF-PS1 Fault Codes 4 – EPH1, Err2, Err3, Err4, Err5, Err6, Err7, Err8, Etn, Etn1, Etn2, Etn3, EtyP, E-10
• VF-PS1 Fault Codes 5 – E-11, E-12, E-13, E-17, E-18, E-19, E-20, E-21, E-22, E-23, E-24, E-25, E-26, E-29, SOUt, PrF

VF-PS1 Technical Pages

• Toshiba VF-PS1 AC Drive Main Page
• Toshiba VF-PS1 User Manual and Technical Documentation
• Toshiba Drives and Automation Main Page
• AC Drives (VFD) Main Category