Toshiba VF-PS1 Fault codes 4

Toshiba VF-PS1 Fault Codes 4 – Phase, CPU, Communication and Auto-Tuning Faults

This section covers the EPH1, Err2, Err3, Err4, Err5, Err6, Err7, Err8, Etn, Etn1, Etn2, Etn3, EtyP and E-10 fault codes used on Toshiba VF-PS1 variable frequency drives. These faults are mainly related to the incoming power supply, internal control electronics, communication, optional units and motor auto-tuning.

Although the Err2–Err8 codes belong to the same general error group, they do not indicate the same failure. Some are related to internal RAM, ROM or CPU hardware, while others point to communication, current sensing or optional devices. The Etn-series codes also require different checks depending on which stage of motor tuning failed.

EPH1: Input Phase Error

EPH1 indicates that the VF-PS1 has detected a phase problem on the main circuit input side. Troubleshooting should therefore begin at the incoming R-S-T power supply rather than on the motor output side.

Possible cause:
A phase error has occurred in the main circuit input line.

Check and solution:
Check the main circuit input line and the R-S-T supply for a missing or abnormal phase condition.

Difference Between EPH1 and EPH0

EPH1 refers to an input-side phase fault, while EPH0 refers to a phase fault on the inverter output side. For EPH1, check the incoming supply; for EPH0, check the inverter-to-motor output circuit.

Err2: Main Unit RAM Error

Err2 indicates an internal problem with the control RAM used by the inverter control system.

Possible cause:
The control RAM is faulty.

Solution:
Because this is an internal control-electronics fault, contact technical service.

Err3: Main Unit ROM Error

Err3 indicates a problem with the inverter's internal control ROM.

Possible cause:
The control ROM is faulty.

Solution:
Contact technical service.

Err4: CPU Error

Err4 indicates that the VF-PS1 has detected an internal fault in the main control CPU.

Possible cause:
The control CPU is faulty.

Solution:
Contact technical service.

Err5: Communication Timeout Error

Err5 indicates that normal communication with an external control or communication device could not be maintained within the specified time.

Possible condition:
Normal communication has not been established for a specified period.

Checks and solutions:
Check the remote-control or communication device.
Check the communication cables and connectors.
Confirm that the external device is powered and operating correctly.

Err6: Gateway Sequence Error

Err6 indicates an internal problem associated with the inverter's main gateway section.

Possible cause:
The main gateway is faulty.

Solution:
Contact technical service.

Err7: Output Current Sensor Error

Err7 indicates a problem in the circuit used by the VF-PS1 to measure the main output current.

Possible cause:
The main output current sensor is faulty.

Solution:
Contact technical service.

Err8: Optional Unit Error

Err8 indicates a problem with one of the optional units or communication cards connected to the inverter rather than necessarily with the main inverter hardware.

Possible cause:
An optional device, such as a communication unit, has failed or is not connected correctly.

Checks and solutions:
Check the connections of the installed optional card or cards.
Make sure each option card is properly seated and connected.
Refer to the instructions for the relevant optional unit and troubleshoot according to the specified procedure (Section 6.36).

Difference Between Err2–Err8

Err2 indicates a RAM fault, Err3 a ROM fault, Err4 a CPU fault, Err5 a communication timeout, Err6 a gateway fault, Err7 an output-current sensor fault and Err8 an optional-unit fault. The common “Err” prefix does not mean that all of these codes require the same troubleshooting procedure.

Etn: Auto-Tuning Error

Etn is the general fault code indicating that the VF-PS1 could not successfully complete the motor auto-tuning process.

Possible causes:
The connected motor capacity is two ratings or more below the inverter capacity.
The connected motor is not a three-phase induction motor.
Tuning was performed while the motor was running.

Checks and solutions:
Make sure a motor is connected to the inverter.
Make sure the motor is completely stopped before tuning.
Perform auto-tuning again.
If the fault remains, use manual motor tuning.

Etn1 (F410): F410 Tuning Error

Etn1 indicates that the auto-tuning process could not determine the required setting associated with the F410 torque-boost parameter.

Possible causes:
Tuning for the torque boost specified by F410 could not be completed.
The connected motor capacity is two ratings or more below the inverter capacity.
The connected motor is not a three-phase induction motor.
Tuning was attempted without a motor connected.
The cable between the inverter and motor is longer than 30 m.
Tuning was performed while the motor was running.

Checks and solutions:
Confirm that the motor is connected correctly.
Make sure the motor is completely stopped.
Take the inverter-to-motor cable length into account.
Perform auto-tuning again.
If the fault remains, perform manual tuning.

Etn2 (F412): F412 Tuning Error

Etn2 indicates that the VF-PS1 could not correctly determine the F412 leakage-inductance value or a related F410 torque-boost setting during auto-tuning.

Possible causes:
Tuning for the leakage inductance specified by F412 could not be completed.
Tuning for the torque boost specified by F410 could not be completed.
The connected motor capacity is two ratings or more below the inverter capacity.
The connected motor is not a three-phase induction motor.
Tuning was attempted without a motor connected.
The inverter-to-motor cable is longer than 30 m.
Tuning was performed while the motor was running.

Checks and solutions:
Check the motor connection.
Make sure the motor is stopped.
Check the motor-cable length.
Repeat the auto-tuning procedure.
If the fault remains, use manual tuning.

Etn3: Motor Constant Setting Error

Etn3 is mainly associated with incorrect motor nameplate data or motor-constant settings. The first step should therefore be to compare the inverter parameters with the actual motor nameplate.

Motor data to check:
Base frequency (UL)
Base frequency voltage (UU)
Motor rated capacity (F405)
Motor rated current (F406)
Motor rated speed (F407)

Solution:
Check the motor nameplate and make sure all of the above values have been entered correctly in the VF-PS1.

Difference Between Etn, Etn1, Etn2 and Etn3

Etn is the general auto-tuning fault. Etn1 is specifically associated with the F410 torque-boost setting, Etn2 with F412 leakage inductance and related tuning values, while Etn3 points primarily to incorrect motor nameplate or motor-constant data. The same troubleshooting sequence should therefore not be applied blindly to every Etn-series code.

EtyP: Inverter Type Error

EtyP can occur when the inverter hardware configuration does not match the stored inverter-type information. This code is particularly relevant after replacement of a control board or main/driver circuit board.

Check:
Determine whether the circuit board or main/driver circuit board has recently been replaced.

Solution:
If the board has been replaced, enter 6 for the tYP parameter.

E-10: Analog Input Terminal Overvoltage

E-10 indicates that the voltage applied to an analog input terminal exceeds the permitted input range.

Possible cause:
Excessive voltage has been applied to the analog input.

Solution:
Check the analog input signal and make sure the applied voltage remains within the specified limits.

Toshiba VF-PS1 Fault Codes

• VF-PS1 Fault Codes – Main Index
• VF-PS1 Fault Codes 1 – nOFF, rtry, Err1, Clr, EoFF, HiLd, OFF, PrF, CFF, OC1, OC2, OC3
• VF-PS1 Fault Codes 2 – OCA1, OCA2, OCA3, OCL, OCr, OH, OH2, OL1, OL2, OLr
• VF-PS1 Fault Codes 3 – OP1, OP2, OP3, OL, UC, UP1, E, EEP1, EEP2, EEP3, EF1, EPH0
• VF-PS1 Fault Codes 4 – EPH1, Err2, Err3, Err4, Err5, Err6, Err7, Err8, Etn, Etn1, Etn2, Etn3, EtyP, E-10
• VF-PS1 Fault Codes 5 – E-11, E-12, E-13, E-17, E-18, E-19, E-20, E-21, E-22, E-23, E-24, E-25, E-26, E-29, SOUt, PrF

VF-PS1 Technical Pages

• Toshiba VF-PS1 AC Drive Main Page
• Toshiba VF-PS1 User Manual and Technical Documentation
• Toshiba Drives and Automation Main Page
• AC Drives (VFD) Main Category