6ES7 135-4FB01-0AB0 — Siemens ET 200S 2AO U ST Analog Voltage Output Module

6ES7 135-4FB01-0AB0 is the ET 200S 2AO U ST analog voltage output module in the Siemens SIMATIC product family. It provides two outputs in a 15 mm width. In ET 200 distributed I/O systems, it can supply analog references to compatible drives and controllers. Check the output range, receiving device input and wiring method together before selecting the module.

Five checks for selection and commissioning

1. Voltage range and resolution: Selectable ranges are ±10 V with 13 bits plus sign and 1–5 V with 12 bits. For a current reference, separately review the 6ES7 135-4GB01-0AB0 current output module. For acquiring measurements from field devices, consider ET 200 analog input modules. Similar order numbers do not make input, voltage output and current output modules interchangeable.

2. Terminal base and wiring: Compatible ET 200 terminal bases include TM-E15S24-01, 6ES7193-4CB20-0AA0 and TM-E15C24-01, 6ES7193-4CB30-0AA0. Two-wire and four-wire connections are supported; two-wire operation does not compensate for cable resistance. When choosing ET 200 connection components, check QV, S+, S− and MANA against the diagrams on manual pages 7–8. Identify conductors by terminal assignment rather than colour alone.

3. PLC value and scaling: The module occupies 4 bytes of output address space. Nominal values are −27648…+27648 for ±10 V and 0…27648 for 1–5 V. Check the Siemens S7 hardware configuration alongside the program scaling. In the 1–5 V range, a digital value of zero represents 1 V. Keep the ET 200 communication cycle separate from the module’s own cycle time when assessing response time.

4. Load and supply: The receiving input must present at least 1 kΩ; capacitive load is limited to 1 µF. The module receives 24 V DC from the power module, and its channels are not galvanically isolated from each other. Review the ET 200 power supply arrangement and station potential groups together with the field devices. Measure at both the module output and the receiving input; a difference may warrant checking the cable and reference connections.

5. STOP response and diagnostics: CPU/master STOP options include zero output, a substitute value or retaining the last value. Group diagnostics and short-circuit-to-M diagnostics are enabled by parameters and are disabled by default. Choose the STOP response to suit the machine’s operating requirements and record it during commissioning. Correct voltage in RUN alone does not complete this check.

Editor’s note

The short product description may state “less than 1 ms”. However, Siemens’ detailed specifications and the module manual give a maximum cycle time of 1.5 ms. Base timing calculations on the detailed specification, then separately account for the PLC scan, communication and receiving device response.

PDF and technical documentation