6ES7 135-4GB01-0AB0
Siemens Main Menu › SIMATIC S7 › ET 200 Modules
Siemens 6ES7 135-4GB01-0AB0 — ET 200S 2AO I ST Analog Current Output Module
6ES7 135-4GB01-0AB0 is a two-channel 2AO I ST analog current output module for ET 200S, part of the Siemens ET 200 family. Selectable output ranges are 4–20 mA and ±20 mA. Applications may include sending references to drives, valve positioners or analog signal controllers with suitable current inputs. Verify the receiving device’s input specification before selection.
Resolution, supply and load limit
Resolution: 13 bits for 4–20 mA; 13 bits plus sign for ±20 mA. Width: 15 mm. Supply: 24 V DC from the power module. Maximum cycle time for all channels: 1.5 ms. When checking ET 200 power supply modules, include the supply to the potential group containing this electronic module.
Maximum permissible load resistance is 500 Ω. Include both receiver input resistance and cable resistance in the assessment. The two output channels are not galvanically isolated from each other. Review connections to devices with different ground references and assess whether the project requires additional signal isolation.
Terminal selection and output wiring
Compatible base examples include TM-E15S24-01 / 6ES7193-4CB20-0AA0 and TM-E15C24-01 / 6ES7193-4CB30-0AA0. When selecting ET 200 terminal blocks, match screw or spring connections to the installation. The general assignment is 1: QI0, 3: MANA; 5: QI1, 7: MANA. Match channel labels to the schematic before changing module connections and terminal arrangements.
Five checks before selection
1. System and order code: Confirm that the installation uses ET 200S within the ET 200 system architecture. Matching channel counts alone does not establish interchangeability between analog modules.
2. Signal and scaling: Match the range selected in the SIMATIC S7 hardware configuration to the receiver. In the 4–20 mA range, 0 represents 4 mA and 27648 represents 20 mA. A zero command does not mean zero physical current.
3. Communication and stopping: Check the configured output response when the ET 200 communication interface or CPU stops. Establish how retaining the last value or changing to another value would affect the process.
4. Supply and field wiring: Review power distribution and potential groups, the 24 V industrial power supply and cable shielding together. Do not test an output by applying an external voltage to it.
5. Functional testing: With the machine in a safe state, test each channel separately. Compare commanded current, measured current and receiver response. Check the scaling of any analog input modules used for feedback; output commands and process measurements may represent different quantities.
Editor’s Note
If a valve or drive responds unexpectedly, first compare the command, selected current range and receiver input settings. Incorrect scaling can make a healthy module appear faulty. Record the existing parameters before replacement, then verify operation at low, middle and high reference points under controlled conditions.
PDF manual and wiring information: Visit the Siemens ET 200 manuals and PDF documents page. In 2AO I ST, A5E01076949-01, 04/2007, pages 7–10 cover connections and technical data, page 11 covers parameters, and pages 16–19 cover value representation and connection information.
Related Topics
Analog Signal Control · Terminal Blocks · Power Supply Modules · Analog Input Modules
Otomasyon AVM
Siemens Main Menu ·
SIMATIC S7 ·
ET 200 Modules ·
ET 200 PDF Manuals ·
PLC and HMI