6ES5 304-3UA12
6ES5 304-3UA12 – SIMATIC S5 IM 304 Distributed Expansion Interface
Siemens 6ES5 304-3UA12 is an IM 304 interface module used for connections between a SIMATIC S5 central controller and remote expansion hardware. Among S5 interface modules, it serves a distributed-expansion role. Selection requires the complete order number, hardware revision and counterpart interface, alongside the Siemens S5 family name.
Siemens IM 304/IM 314 family documentation describes connections up to 600 m using 721 cable. The S5-135U/155U table lists 304-3UB11 at the central controller and 314-3UA11 at the expansion unit. The 600 m figure therefore belongs to that documented family arrangement; compatibility of 304-3UA12 with the actual SIMATIC S5 subrack and hardware revision requires separate verification.
Connecting cable and termination
The IM 304/314 family arrangement uses 6ES5 721 connecting cables. When selecting S5 cables and connectors, consider the complete cable code, pin assignments and route together. Apply the manual’s distance limit to the total cable path from the central controller to the final expansion unit on the relevant run.
The documented IM 304/314 arrangement requires a 6ES5 760-1AA11 terminator at the final IM 314. A missing terminator, broken cable or incorrect line setting can cause communication faults. Check termination and unused connections against the actual system diagram.
Subrack, supply and revision selection
The S5-135U/155U family table specifies an additional IM 306 for ER 701-2 and ER 701-3. When reviewing IM 306 options, use the complete subrack order number. Check the power supply and expansion-unit supply together with grounding and shield connections.
The 304-3UA11, 304-3UA12 and 304-3UB11 codes must be distinguished. Since a verified electrical data sheet for UA12 was not located, current consumption, power loss and weight from other versions are not presented here as UA12 ratings. Select slots and switch/jumper settings for the exact hardware revision as well.
Counterpart interfaces such as the IM 314R, 314-3UR11 depend on the system’s connection and operating arrangement. Membership of the same IM 304/314 family does not establish automatic suitability for redundant or safety applications.
Comparing other expansion solutions
The 301-3AB13 and 310-3AB11 form a different interface pair. The 308-3UA12 with 318-3UA11, and the 307-3UA11 fiber optic interface, are separate solutions too. Do not assess them as interchangeable without considering both the counterpart module and cable family.
Checking a connection fault
During troubleshooting, establish whether the fault affects one module or the whole expansion unit. Then check the expansion supply, cable, connector seating, termination and existing line settings. Verify the hardware connection before changing the program or addressing.
Editor’s note
With older S5 systems, start with a clear view of the label: the required code is 304-3UA12. Do not assume a UA11 or UB11 is identical. Check the hardware revision, counterpart interface and subrack together.
“It reaches 600 metres” is not enough to choose the part. The cable type, total run length and line settings matter as well. Trace the existing connection first so you know where each run goes.
If the entire expansion unit disappears, do not write off the main board immediately. Work through the supply, cable and terminator in order. Replacing a healthy part because of a missing terminator is an avoidable expense.
When buying a used Siemens part, request photographs of the label, front connectors and board settings. If it has been tested, ask which subrack and counterpart module were used. Knowing the test setup makes “it works” much more useful.
Record the jumpers, switch positions and cable locations before removing anything, and isolate power before working on it. Random setting changes can add another problem to the original fault. Preserve the existing arrangement first, then work through one change at a time.
OtomasyonAVM resources and PDFs
+ S5 interface and expansion modules.
+ S5 PDF archive: system and connection resources. The English Siemens documents below are IM 304/314 family references; they are not independent data sheets for UA12.
Related topics
+ 304-3UA11 · 304-3UB11 · 314-3UA11.
+ 760-1AA11 terminator · IM 306 interface options.
+ PLC expansion troubleshooting sequence.
Browse SIMATIC S5