Siemens 6ES5 302-3KA11 — IM 302 Serial Expansion Interface, 1000 m
6ES5 302-3KA11 is an IM 302 serial expansion interface installed on the central-controller side of a Siemens SIMATIC S5 system. Siemens specifies it for distributed expansion connections up to 1000 m. This model in the S5 interface module range connects the central controller to remote expansion racks.
The matching interface is 6ES5 311-3KA11, with a 723-series connecting cable. The IM 311-3KA11 belongs on the expansion-unit side; the IM 302-3KA11 belongs on the central side. In a SIMATIC S5 arrangement, CC means central controller and EU means expansion unit. Select the S5 connecting cable together with the interface pair and rack configuration.
Central-controller and expansion-unit compatibility
In Table 3-4 of the S5-115U manual, the exact 302-3KA11 order code is listed with central controllers 110S/B, 130K/W, 135U, 150K/S/U and 155U. The expansion side uses EG2 — ER 701-2 or EG3 — ER 701-3. Verify the central-controller family, EU type and matching interface together.
1000 m distance and cable arrangement
1000 m is the manufacturer’s upper distance for this connection arrangement. Check the installed cable type, route, shield connections and connectors. On long runs, inspect grounding and shielding as well as cable joints and damaged ends. Work from the 723 cable specification; a connector fitting physically does not establish compatibility.
Restart condition for S5-150K/S/U
The Siemens table includes a specific condition for 150K/S/U: a cold restart must be prevented by the STP statement in OB22. Review the existing startup behaviour and PLC program against the relevant CPU manual. Back up the current program before making changes with the programming software; this footnote must not be treated as a general setting for other CPU families.
I/O checks and fault isolation
During troubleshooting, check the central interface, 723 cable, remote IM 311 and EU power supply in sequence. Use the S5 system structure to compare the physical arrangement with the program’s address allocation. Several modules dropping out together also calls for inspection of their shared connection and supply.
Test the connection using digital inputs, digital outputs and, where installed, analog modules permitted by the actual configuration. Confirm separately that an input appears at the correct program address and that an output command reaches the intended channel. Perform output checks under safe machine test conditions.
Comparison with other S5 interfaces
The IM 301-3 — 6ES5 301-3AB13 and IM 310 — 6ES5 310-3AB11 form a different interface pair. Likewise, the IM 304 — 6ES5 304-3UA11 and IM 314 — 6ES5 314-3UA11 must be assessed as their own pairing. Their cable and distance specifications must not be transferred to the 302-3KA11.
The 6ES5 312-3AB31 — IM 312-3 is a different expansion-side model for a centralized arrangement. The defining selection points for 302-3KA11 are its central-side role, the IM 311-3KA11 counterpart and the 723 cable arrangement. A generic “S5 expansion module” description is insufficient to establish interchangeability.
Editor’s note
Start by looking at the labels in both cabinets. IM 302 belongs at the central controller and IM 311 at the expansion unit. A photograph of each end, placed side by side, can save a needless ordering mix-up.
Give the long cable a little attention too. Has it been extended, trapped in a cabinet door or had its shield disconnected? A continuity reading alone tells only part of the story; in an older installation, the cable’s history can be as useful as the module label.
If every board in the remote rack disappears together, leave the working program alone while you check the rack supply, both interfaces and the shared cable. Narrowing down the fault first keeps a small repair from becoming a much longer afternoon.
Once the link is working, take a moment to check the actual data. Watch an input appear at the correct address and verify an output at the intended channel under controlled conditions. Correct data in both directions says more than a powered module sitting in its slot.
When buying a used Siemens IM 302, examine the full label, connectors and board condition. If possible, ask for a working test with a suitable IM 311 and cable. A pair seen exchanging real I/O data gives you a firmer basis for choosing than an untested board on its own.
OtomasyonAVM resources and PDFs
+ S5 interface modules · S5 racks and expansion units · S5 cables and connectors.
+ OtomasyonAVM Siemens S5 PDF archive. S5-115U Manual, §3.2.7, Table 3-4, p. 3-28 identifies the exact order code, CC/EU pairing, 1000 m limit, 723 cable and 150K/S/U footnote. The source is in English.
Related topics
+ IM 311-3KA11 matching interface · IM 301-3 · IM 310 · IM 314 · IM 312-3AB31.
Navigation
+ S5 interface modules · S5 racks · SIMATIC S5 · Siemens S5 PLC · Used Siemens.