6ES5 925-5AA12

Siemens 6ES5 925-5AA12 — CPU 925 central processor board for S5-150A

Siemens 6ES5 925-5AA12 is the CPU 925 / 925-5 central processor board used in the S5-150A central controller. This Siemens S5 product forms part of a three-board central processing unit. It belongs to the SIMATIC S5 processor group and should be assessed as part of that assembly.

The S5-150A central processing arrangement uses the 925 board, 6ES5 926-5AA12 and a suitable 927 board together. When assessing versions such as 6ES5 927-5BA12 or 6ES5 927-5BA13, record the complete numbers and revisions of the entire board set.

System compatibility and similar order numbers

The 5AA12 suffix identifies the relevant S5-150A hardware. 6ES5 925-3KA12 belongs to the S5-150K arrangement, while 6ES5 925-3SA11 is a different version for S5-150S/U. Compare the central controller, processor-board set and memory arrangement before choosing a replacement.

Photograph the S5 rack layout before removal. The internal supply is 5 V; check the S5 power supply and backplane connections against the system drawings. The supply’s mains or 24 V input rating is not the voltage to apply directly to the processor board.

925 jumpers: 10 ms and 100 ms

Siemens’ jumper table for 6ES5 925-5AA12 provides two timer-value updating arrangements: 100 ms with 21/7–10 closed and 21/8–9 open, or 10 ms with 21/8–9 closed and 21/7–10 open. These numbers identify jumper positions on the board.

These values are not the program scan time. The board also uses a jumper to enable or inhibit the WECK time interrupt. Photograph the existing arrangement and consult the drawing for the actual board revision before changing anything. Distinguish test points from selectable operating settings.

Program memory and STEP 5 project

S5-150A uses separate RAM/EPROM memory hardware for program storage; the system manual describes the 340 and 350 memory boards. Check the S5 memory boards, fitted submodules and program contents separately from the CPU. Do not infer memory capacity from the 925 order number.

For PLC programming work, retain the STEP 5 blocks, data blocks and project files together. When using ladder or function block diagram representations, verify that the symbols and comments match the version of the program read from the controller.

PG connection, addresses and peripheral modules

Assess programmer communication through the system’s separate PG interface. Record the 6ES5 511-5AA12 PG interface and the S5 programming cable separately in the maintenance file. Also record port and protocol details for installed communication boards independently of the CPU label.

The S5-150A system manual specifies addressing resources of 1024 inputs, 1024 outputs, 2048 flags, 128 timers and 128 counters. These are not physical terminals on the CPU 925 board. Determine actual wiring and address assignments from the installed digital input, digital output and analog modules.

Include expansion units connected through S5 interface modules in the inspection. Keeping rack position, cable labels and program addresses together helps prevent tracing the wrong channel after replacement.

Operating controls and diagnostics

The Betrieb/Stop switch is on the 926 board; operating and STOP indicators are on the 927 board. Assess system behaviour using the complete assembly. Record the switch position, indicators and power-supply condition together.

For PLC debugging, read and preserve accessible U-Stack and B-Stack information before intervention. Secure the program backup before an overall reset or memory replacement. A useful test record identifies whether PG access, program reading, memory checks and application testing were completed.

Editor’s note

When buying this board used, establish more than whether someone calls it a working 925. In S5 maintenance, the useful spare is the version that suits the existing 150A assembly. Keep photographs of the companion 926 and 927 labels in the same file.

Do not copy jumpers from another board without checking the configuration. Record the original settings and compare them with the correct drawing. In particular, do not change the 10/100 ms arrangement under the impression that it sets program execution speed.

Establish whether the memory hardware is included, the program can be read and a backup exists. A clean-looking board does not establish that the machine program is available. Investigate missing memory separately from a defective processor board.

Inspect ageing connectors, corrosion and evidence of previous repairs. Do not insert or remove the board under power. If it will not seat correctly, check the guide and connector rather than forcing it into position.

If the processor assembly remains in STOP, assess the switch, 927 indicators, supply and accessible PG information together. Record which finding points toward which component before assigning the fault to the 925.

For a bench test, record the central controller, companion processor boards, memory and PG interface used. Establish what “tested” covers: program reading, operation and testing with the actual application are separate checks. Leave untested functions clearly identified.

OtomasyonAVM resources and documentation

+ 6ES5 925-5AA12 model page · Second-hand Siemens S5 models · About Siemens S5 PLCs.

The S5-150A operating manual and the 925 jumper table are linked in the Siemens references below.

Related topics and models

+ 6ES5 926-5AA12 and 6ES5 927-5BA13: related boards to examine when assessing the central processing assembly.

+ 6ES5 925-3KA12 and 6ES5 925-3SA11: comparison with other 150-series hardware. Do not assume direct interchangeability.

Browse SIMATIC S5

SIMATIC S5 processors · S5 memory boards · S5 interfaces · S5 cables · Second-hand Siemens products

Siemens and external references

+ Siemens System 8 commissioning checklist and instructions, Part I/2 — German PDF. Printed page 5-14: jumper arrangements for 6ES5 925-5AA12, 926 and 927 boards.

+ Siemens S5-150A Zentralgerät operating instructions — C79000-B8500-C227-2, German; ManualsLib copy. System architecture, technical resources, operating controls and jumper drawings.

+ Siemens ST 53.1985 catalogue — German; manufacturer PDF hosted by ADEGIS. S5-150A architecture, PG connection and central-board order numbers.