6ES5 920-3UA11

Siemens 6ES5 920-3UA11 – CPU 920 M Processor for S5-135U

Siemens 6ES5 920-3UA11 is the CPU 920 M processor for S5-135U in the SIMATIC S5 family. This S5 processor serves measurement-data processing, arithmetic, sorting and statistics. Its distinguishing feature is the M processor environment programmed in BASIC, C or assembler. Siemens’ cabinet heat-load list specifies 11 W power dissipation for the exact 3UA11 number.

During programming and maintenance, identify the installed language environment, application files and system-software version together. Select the software tools for the actual M processor application. Family support for BASIC/C/assembler does not mean that every board has all these environments installed simultaneously.

M, S and R processor roles

Siemens describes CPU 920 for measurement and computing tasks. The CPU 921 S processor focuses on binary signals, while the CPU 922 R processor focuses on word processing and closed-loop control. A conventional STEP 5 block backup alone should not be treated as a complete M processor application backup. Preserve source files, development tools and the runtime environment.

Memory submodule and backup

Record the exact memory hardware number, capacity and contents. The Siemens family manual lists a 64 KB battery-backed RAM 377 module among the memory options usable with CPU 920. This does not establish that every installed CPU 920 has that module. Check the module battery and the chassis backup arrangement separately.

System compatibility and coordinator

Family documentation describes CPU 920 in single-processor installations and systems with up to four CPUs; it also lists the CPU 920 family for S5-155U. Check the chassis and revision requirements separately when replacing 3UA11. In a multiprocessor system, record the settings and CPU data exchange associated with the installed COR 923A or COR 923C coordinator.

Installation and heat load

CPU 920 occupies one CPU slot in the family layout. Mark its rack position and the accompanying system modules before removal. The documented 11 W figure is power dissipation; it does not independently specify maximum supply current. Assess the power supply, fans and cabinet airflow together.

Programming connection and communications

Select the cable for the actual PG/terminal and interface hardware. Verify port type, electrical level and software settings together for the communications connection. Record the functions of installed CP modules separately from the processor’s own connections.

Distinguishing 3UA11 and 3UA12

6ES5 920-3UA12 is a separate order number. The shared CPU 920 name is insufficient for a replacement decision. Compare hardware revision, installed memory, system software and application runtime. Do not assign another CPU model’s memory or current ratings to this board.

Diagnostics and commissioning records

During fault investigation, record operating indicators, coordinator state and the application-loading stage together. For S5 maintenance, establish a restorable application backup before an overall reset or memory replacement. Complete verification by checking calculated values and data exchange with other CPUs as well as the RUN indication.

Editor’s Note

When buying a used Siemens CPU 920, obtain a clear view of 920-3UA11 and its revision. Identify the M processor requirements before selecting a board from its S5 branding alone. Establish whether memory and application accessories are included.

The application files can be as valuable as the hardware. Preserve BASIC/C/assembler sources, load files and tool versions. A running application does not automatically mean that a reproducible backup exists.

Before removing a RAM module, check its battery and data-retention conditions. Photograph the label and secure the contents. Do not risk the working machine’s only copy on the assumption that it can be restored later.

Assess the other CPUs in a coordinated system. Record the M processor’s task and the data it exchanges. For a connection problem, check cable, interface and software settings in sequence.

Record more than “working” after testing. Identify the chassis, memory and application used, with separate results for loading, computation and data exchange. If exact memory or current ratings are unavailable, do not substitute figures from a neighbouring processor model.

OtomasyonAVM resources and PDFs

+ SIMATIC S5 CPU models · S5 memory modules · Shared SIMATIC S5 PDF archive – S5-115 PDF files

Related topics

+ 6ES5 920-3UA12 · 6ES5 921-3UA11 · 6ES5 922-3UA11 · 6ES5 923-3UC11 COR 923C

Browse SIMATIC S5

+ Siemens SIMATIC S5 · S5 CPU models · S5 memory modules · S5 racks and chassis · Used Siemens equipment

Siemens and external references

+ Siemens S5-135U CPU 921/922 Manual – 6ES5 998-0UL22, Release 01 (English). Central-controller and multiprocessor chapters: CPU 920 M processor role, languages, slot allocation and coordination. RAM 377 chapter: battery-backed memory. This is family documentation rather than a complete CPU 920 hardware manual.

+ Siemens S5-150U Handbuch – installation and cabinet heat-load section (German). “Verlustleistung von Baugruppen”, B85452/2, printed page 21: 11 W dissipation for the 6ES5 920-3UA11 M processor.