6ES5 788-8MA11
Siemens 6ES5 788-8MA11 – 8-Channel Input/Output Simulator Module
Siemens 6ES5 788-8MA11 is a 788 input/output simulator module for Siemens S5 systems. It is intended for S5-90U, S5-95U, S5-100U, ET 100U and ET 200U installations. Depending on the selected direction, it generates eight digital input signals using switches or displays eight digital output states on LEDs. This SIMATIC S5 accessory supports program testing and troubleshooting.
Within the S5 accessory and function module ranges, the 788 serves as a test instrument. It does not provide eight field inputs and eight load-driving outputs simultaneously. A rear selector determines its direction. It draws power from the 9 V system bus and requires no external 24 V field supply. The manual specifies 30 mA current consumption, 0.3 W typical power loss and 190 g weight.
Generating inputs and displaying outputs
In IN mode, the eight front switches generate 0 or 1 signals for channels .0–.7. In OUT mode, the module displays the states of eight PLC output bits. Testing in place of an S5 digital input module supplies signals to the program; testing in place of an S5 digital output module shows the program's output commands.
Yellow function LEDs indicate the selected direction, while green LEDs show channel states. During PLC programming and debugging, follow the switch position, input bit, logic result and output indication together. The module cannot simulate interrupt inputs. An illuminated output LED also does not establish that the original field output can drive its load correctly.
Bus mounting and separation from field wiring
The simulator plugs into a bus unit like an ordinary I/O module. It has no mechanical coding key, allowing it to replace a digital module without changing the bus unit's coding element. There is no electrical connection to the field terminal block. Rather than measuring signals arriving through S5 cables and connectors, it tests logic signals through the system bus. Check bus connections and interface modules before starting the test.
The S5-90U page, S5 CPU family directory and S5 module groups can help identify the installation; compatibility must follow the manufacturer's system scope stated above. The 9 V bus rating does not mean that an external 9 V or 24 V supply should be connected to the simulator. Do not connect sensors, relay coils or other field loads to it.
Addressing and the limits of the test
The 788 is addressed like an eight-channel digital module. In an S5-100U, the address relates to its digital module position; monitor bits .0–.7 in the correct byte. When testing in place of an input module such as 6ES5 420-8MA11 or an output module such as 6ES5 441-8MA11, also check the original channel count. One eight-channel test does not validate every channel of a larger combined input/output module.
Check the supply and bus connections first, then monitor the relevant bits using STATUS / STATUS VAR in STEP 5. If the expected logic behavior is obtained with the simulator, investigate the removed module, field wiring and loads separately. The 6ES5 330-8MA11 diagnostic module is a different tool for examining bus voltage and signals; it does not perform the 788's switch-operated input simulation.
Editor's note
Before buying one, be clear about the test you need. It is useful for feeding inputs into a Siemens S5 program on the bench and watching the result. It will not replace a failed output module and energize a contactor: its output indicators are not power outputs.
If moving a switch produces no visible change in the program, check the rear IN/OUT selector and monitored address before blaming the simulator. Follow the PLC input, program and output sequence in order. Watching the wrong byte can make working hardware appear faulty.
Do not confuse it with 6ES5 788-8MK11. The 8MK11 is a different simulator attached to the S5-90U's front terminals; the 8MA11 plugs into a bus unit. Compare the complete order number and mounting arrangement when purchasing.
For a used unit, test all eight switches in both positions. Watch the corresponding bit and LED together. If a bit changes unpredictably when the lever is moved slightly, investigate contact wear. Lights on the front panel alone are not enough to establish proper operation.
In OUT mode, test the eight bits individually and together. Check the address and program command before treating a dark LED as a hardware fault. Correct results on the simulator do not validate the original field module's output transistors, short-circuit protection or wiring.
Before testing on a machine, identify what the remaining outputs can move and establish a controlled test arrangement. A simulated input can make the program operate another output elsewhere. This module helps isolate faults; it still needs a sound test sequence.
OtomasyonAVM resources and PDFs
Use About Siemens S5 PLC and the S5 accessory section to review related systems and test equipment.
+ S5-90U PDF files: Simulator module information within the S5-90U/S5-95U system documentation.
+ Shared S5 PDF archive: Archive page for S5-100U and other S5 documentation. The manufacturer manuals linked below are in English.
Related topics
+ 6ES5 788-8MK11: Different simulator attached to S5-90U front terminals.
+ 6ES5 330-8MA11: I/O bus diagnostic module.
+ S5 digital input modules and S5 digital output modules: Modules that handle actual field signals.
Browse SIMATIC S5
S5 accessories · S5-90U · SIMATIC S5 · Siemens S5 PLC · Used Siemens equipment
Siemens and external references
+ Siemens S5-100U System Manual — EWA 4NEB 812 6120-02b, English: §15.3, printed pages 15-7–15-8; specifications, operation, mounting and addressing.
+ Siemens S5-90U/S5-95U System Manual — EWA 4NEB 812 6115-02b, English: §16.3.2, printed pages 16-8–16-9.
+ Siemens 6ES5788-8MA11 product data sheet, German, 20 July 2020: Third-party archive copy of the manufacturer document; confirms S5-90U/95U/100U and ET 100U/200U scope.