6ES5 246-4UB11

Siemens 6ES5 246-4UB11 SIMATIC S5 IP 246A absolute positioning module

The 6ES5 246-4UB11 is the IP 246A in the SIMATIC S5 positioning module family. It reads absolute position on two independent axes and provides an analog speed reference to the external drive for each axis. Siemens specifies forced ventilation for the 4UB11.

Encoder and drive interface

Each axis uses a 24 V parallel absolute encoder with up to 20 bits of Gray or Gray Excess-X code. Axis 1 uses X4 and axis 2 uses X5. Use the same output polarity on both axes. Match the sourcing or sinking encoder type to the X17 jumper setting in the manual. Check the connectors and S5 connecting cable against the pin table in Hardware Section 3.4.1.

Each axis has one ±10 V / 2 mA analog speed reference. In a system with separate S5 analog I/O cards, trace the speed command to its source on the cabinet drawing. There are four digital inputs and two digital outputs per axis. Siemens identifies PR as the position-reached output and FUM as the drive enable signal.

Rack, supply and version selection

Siemens lists the 4UB11 for ventilated S5-135U, S5-150U and S5-155U installations. Check airflow through the rack and the capacity of the installed power supply. The PS 955-3LF12 is one power supply used in this rack family. The table for the 4UB series specifies about 0.85 A from the 5 V system bus and a 20–30 V front-panel L+ supply. The 0.85 A figure excludes the encoder supply.

The 6ES5 246-4UB21 is the absolute encoder version for non-ventilated operation. The 4UA31 and 4UA41 are incremental encoder versions. For the IP 247, IP 266, IP 267, IP 240 and IP 241, use the relevant manual to check wiring and functions. On the IP 246A, COM 246 can back up machine data and traversing programs. Siemens assigns operation and monitoring to FB164 and parameter assignment to FB165.

Editor’s note

1. Back up the configuration before removal. Save the COM 246 project data, module address and EPROM label. After qualified personnel isolate power, label the X4 and X5 plugs by axis.

2. If position jumps, trace the Gray signals. If only one axis is affected, start at its X4 or X5 plug. Compare encoder polarity, the X17 jumper, pin order and configured resolution with the wiring and machine data.

3. If both axes drop out, check the shared supply. Siemens notes that the analog output can retain 2–3 V if L+ is lost. Have qualified personnel safely disable the drive before checking the L+ supply and FUM circuit.

4. If the fault returns as the rack warms up, check ventilation. Have the fan and airflow across the modules inspected. Correct fan or airflow problems before returning the module to service.

5. Ask for a two-axis test on a used module. Request photos of the 4UB11 label, EPROM and X4/X5 sockets. Ask for a test record showing Gray position readings and analog speed output on both axes.

To offer an IP 246A for sale, send its full order number, quantity, condition, label photo and asking price to otomasyonavm@gmail.com.

Siemens PDF documentation

+ IP 246 complete manual, release 04 (EN)

+ IP 246 hardware specifications, pp. 8–9 (EN)

+ IP 246A X4/X5 pin assignments, section 3.4.1 (EN)

+ IP 246 complete manual, release 04 (DE)

+ OtomasyonAVM S5 PDF archive

Related topics

+ Siemens S5 PLC overview

+ SIMATIC S5 CPU models

Second-hand Siemens navigation

+ SIMATIC S5 positioning modules

+ SIMATIC S5

+ Second-hand Siemens