6ES5 246-4UA31

Siemens 6ES5 246-4UA31 SIMATIC S5 IP 246I incremental positioning module

The 6ES5 246-4UA31 is the IP 246I in the SIMATIC S5 positioning module family. It reads incremental encoder feedback and sends analog speed references to external drives for closed-loop positioning of two independent axes. The 4UA31 requires forced ventilation.

Encoder inputs and wiring

Axis 1 uses X4 and axis 2 uses X5 for encoder feedback. Both axes must use the same signal type. 5 V RS-422 differential inputs use A, B, R and their complements, with a maximum counting frequency of 500 kHz. 24 V inputs use A, B and R, with a maximum of 50 kHz. R is the once-per-revolution reference pulse.

The X4/X5 connectors have identical pin assignments. For A/B/R, use pins 1/4/2 on the 5 V differential inputs or pins 14/15/13 on the 24 V inputs. On the 5 V inputs, /A, /B and /R use pins 8/10/9, respectively. Check the encoder cable against section 3.3 of the manual. Match X18 and X20 to the signal level and X17 to the module or external encoder supply.

Outputs, rack and power supply

Each axis has one ±10 V / 2 mA analog speed output, four digital inputs and two digital outputs. PR signals that the axis has reached position. FUM provides the drive enable signal. Trace the speed reference from the IP 246 on the cabinet drawing. The system may also contain a separate S5 analog I/O card.

Siemens notes that the analog output can retain 2–3 V if L+ is lost. Have qualified personnel safely disable the drive before taking measurements.

Siemens lists the 4UA31 for CP slots in ventilated S5-135U, S5-150U and S5-155U systems. Check rack airflow and the capacity of the installed supply. The PS 955-3LF12 is one power supply used in this rack family. The module draws about 1 A from the 5 V system bus excluding encoder power. Front-panel L+ requires 20–30 V DC.

The 4UA41 is the incremental version for non-ventilated S5-115 installations. The 4UB11 and 4UB21 are absolute encoder versions. If the installation also uses an IP 247, IP 266, IP 267, IP 240 or IP 241, mark which card each axis connects to on the cabinet drawing.

Editor’s note

1. Record the setup before replacing the module. Use COM 246 to back up machine data and traversing programs. Record the module address and EPROM revision. After a qualified technician isolates rack and encoder power, label X4 and X5 by axis.

2. Start at X4 or X5 if the position count stays fixed. Check encoder power and the A/B signals on the affected axis. For 5 V differential encoders, check both sides of each signal pair. If both axes fail to count, compare the shared X17, X18 and X20 settings with the wiring diagram.

3. Check direction and distance separately. Under safe commissioning conditions, have a qualified technician make a short move and verify that the displayed position changes in the correct direction. If the direction is correct but the distance is wrong, check the encoder pulses per revolution and the scaling in the machine data.

4. If the axis counts but fails to home, check the R pulse. The incremental axis needs to be referenced after power-up. If mode 5 reference point approach is used, check the BERO precontact transition and then the R pulse. This separates a referencing fault from a counting fault.

5. Ask for a test of both axes when buying used. Request photos of the order label and EPROM. Ask for a test record covering position counting, the R pulse and analog speed output on both X4 and X5 axes.

To offer an IP 246I for sale, send its full order number, quantity, condition, label photo and asking price to otomasyonavm@gmail.com.

Siemens PDF documentation

+ IP 246 complete manual (EN)

+ Incremental encoder jumpers and X4/X5 wiring, section 3.3 (EN)

+ Mode 5 and reference point approach, section 3.4 (EN)

+ IP 246 complete manual (DE)