Siemens 6ES5 373-1AA81 SIMATIC S5 373 CMOS EPROM Memory Submodule, 128 KB

The Siemens 6ES5 373-1AA81 is a 128 KB CMOS EPROM 373 memory submodule for SIMATIC S5. Siemens lists this order number for the 6ES5 524-3UA15 CP 524 communications processor and the WF 470 display module. It stores communications jobs and message texts in the CP 524 and screen data in the WF 470. The Siemens EPROM table assigns it programming number 0463.

When replacing a CP 524, the EPROM carries the application that defines how the PLC exchanges data with connected equipment and which messages it prints. In a WF 470, the same EPROM model holds the machine’s screens and display text. Record the host module and project revision before preparing a spare.

CP 524 memory slot and COM 525

On the CP 524, one of the S5 communications processors, the 373 slot holds communications jobs and message texts configured offline in COM 525. When sourcing a spare for an S5-115U or S5-135U cabinet, check the processor order number as well as the rack label. The Siemens S5R006 driver note, for example, shows a separate CP 524-3UA13 configuration using the 32 KB 373-0AA41.

The separate 752 interface submodule determines the CP 524’s serial connection. Siemens ST 50 lists the 752-0AA12 for 20 mA TTY, the 752-0AA22 for V.24/V.28 (RS-232C) and the 752-0AA43 for RS-422A/RS-485.

When checking a link between two CPs, match the S5 cable to the installed interface. The 726-1BF00 is a 5 m cable for 20 mA links. The 726-8BC00 is a 2 m cable for V.24 links.

WF 470 memory slots and screen project

The WF 470 manual identifies X10, X20 and X30 as memory slots for screen and text data. Select PNUMMER 0463 in the screen generation software when preparing the 1AA81. The manual specifies screen generation software version 5.0 or later for programming CMOS EPROMs.

The WF 470 A and B require at least one RAM module for commissioning. The WF 470 C can use its built-in CMOS RAM. If the protocol option is used on a WF 470 B, check that a RAM module is installed for the message buffer.

Programming numbers for 1AA81 and 0AA81

The 373-1AA81 and 373-0AA81 both hold 128 KB. Siemens lists the 1AA81 as CMOS with 0463 and the 0AA81 as NMOS with 0163. The same WF 470 table gives 0414 for the 373-1AA41 32 KB CMOS, 0460 for the 373-1AA61 64 KB CMOS and 0060 for the 373-0AA61 64 KB NMOS.

Back up the module with a compatible PG or EPROM programmer before reprogramming it. UV-erase the EPROM if the contents need to change, run a blank check, program it and compare the readback with the source file. Programming documentation is available through the Siemens S5 manual index.

Editor’s note

Capture the original label. Photograph the 373-1AA81 order number and use the suffix to select the programming profile.

Record the host slot. Note the full CP 524 order number or the WF 470 variant, A, B or C, along with the slot occupied by the EPROM.

Back up the working EPROM first. Name the readback file with the machine ID and date. Keep the COM 525 or WF 470 project in the same backup folder if it is available.

Start with the symptom. If the CP 524 gives no serial response, check the 752 module and the cable. If WF 470 screens are missing, verify the project data and the slot.

Ask for a readback test on the spare. Check the full order number and test result when buying a used Siemens part. To sell a module, email its code, quantity, working condition, label photo and price to otomasyonavm@gmail.com.

OtomasyonAVM resources and PDFs

SIMATIC S5 memory modules · CP 524-3UA15 communications processor

OtomasyonAVM S5-115 PDF archive · SIMATIC S5 system manuals and STEP 5 programming documentation

Related topics

373-1AA41, 32 KB CMOS EPROM · 373-1AA61, 64 KB CMOS EPROM · S5 interface modules

Browse the S5 range

Siemens SIMATIC S5 › S5 memory modules

External references

Siemens WF 470 technical description, memory slots and programming numbers

Siemens ST 50 catalogue, CP 524 and 373 ordering data, p. 4/113

Siemens CP 524/CP 525 COM 525 manual, Volume 1 · Siemens S5R006 driver note, CP 524-3UA13 configuration (DE)