6ES5 373-1AA61
6ES5 373-1AA61 Siemens SIMATIC S5 64 KB CMOS EPROM Memory Submodule
The Siemens 6ES5 373-1AA61 is a 64 KB (65,536-byte) CMOS EPROM 373 memory submodule for SIMATIC S5 equipment. It retains its contents without power. Siemens lists it for driver and parameter storage on the CP 524 6ES5 524-3UA15 and for screen and text storage on the WF 470. The WF 470 software uses programming number 0460.
Two submodules with the same 1AA61 label can contain different projects. An EPROM removed from a CP 524 may hold a serial communications project, while one from a WF 470 may hold operator displays. Match the submodule order number, host module and project file when preparing a spare.
What does it store on a CP 524?
The Siemens ST 50 catalogue lists 32, 64 and 128 KB EPROM options for the CP 524 6ES5 524-3UA15. The 1AA61 is the 64 KB option in that table. Use the driver and parameters prepared in COM 525 for the installed application. Siemens’ special driver example uses PROM 525 to program the EPROM.
The CP 524 uses separate EPROM and serial interface submodules. The ST 50 table lists the 752-0AA12 for 20 mA TTY, the 752-0AA22 for V.24 and the 752-0AA43 for RS-422-A/RS-485. If the link fails, check the EPROM project, installed interface and serial cable separately.
Check the exact order number and driver package when servicing S5 communications processors. For example, Siemens’ S5R01E driver documentation lists the 373-0AA41 EPROM for the CP 524 6ES5 524-3UA13. Use the documentation for the installed CP and driver to select a spare.
Which programming number does the WF 470 use?
The WF 470 technical manual describes X10, X20 and X30 as memory slots for displays, text and associated project data. Siemens specifies PNUMMER 0460 for the 1AA61. CMOS EPROM programming is documented for version 5.0 and later of the WF 470 picture generation software.
Siemens requires at least one RAM module for initial commissioning of the WF 470 A and B. The WF 470 C has sufficient onboard CMOS RAM for this purpose. Record the installed WF 470 version and slot layout with the project backup.
How do you read, erase and program the EPROM?
Read and program the submodule offline using a compatible Siemens programming device or EPROM programmer. The programmer table lists the 1AA61 under 460, with a capacity of 64 KB or 32 K words. Select BYTE or WORD mode to match the target equipment and project file.
Before reusing an EPROM, read and save its existing contents. Use a suitable UV eraser, perform a blank check and verify the new contents by reading them back. Keep the EPROM readout separate from the CPU project in the PLC program archive and label it with the host order number.
How do the similar order numbers differ?
The 6ES5 373-0AA61 also holds 64 KB. It uses NMOS EPROM and programming number 0060 in the WF 470 table. The 1AA61 pairs CMOS EPROM with 0460. This module uses UV erasure, while Flash memory and EEPROM are erased electrically.
In the 373 CMOS EPROM range, the 1AA21 holds 16 KB, the 1AA41 holds 32 KB, and the 1AA81 holds 128 KB. Select capacity using the project size and the host module’s memory table.
A 355 memory carrier in an S5-155U rack with a CPU 946 or CPU 947 is a separate application. The reviewed 355 spare parts table specifies the 373-0AA61 for 32 K words. Use the carrier’s own ordering table for this configuration.
Editor’s note
Before removal, photograph the 6ES5 373-1AA61 label, the host module order number and the EPROM slot. Similar-looking EPROMs in the same cabinet can serve different functions.
Before UV-erasing a working EPROM, save its readout as a separate backup. Include the machine name, host module and project revision in the filename where available.
Record programmer number 460 and the selected BYTE or WORD mode. After writing, compare the readback with the source file.
When preparing an EPROM for a WF 470, check the picture generation software version. After installation, verify that the expected screens and texts can be called up.
When replacing a CP 524, match the serial interface submodule order number to the existing COM 525 project. Then verify the link with a known working peripheral.
OtomasyonAVM resources and PDFs
Siemens SIMATIC S5 PLC guide · S5 memory submodules · S5 communications processors
OtomasyonAVM SIMATIC S5 PDF archive
Related topics
373 series EPROMs · 64 KB NMOS 373-0AA61 · 32 KB CMOS 373-1AA41 · 128 KB CMOS 373-1AA81
Browse SIMATIC S5
Used Siemens SIMATIC S5 equipment › SIMATIC S5 › S5 memory submodules
Siemens documentation and external references
Siemens ST 50 SIMATIC S5 catalogue · p. 4/113, CP 524 and 373-1AA61 ordering data
Siemens WF 470 technical manual · Section 2.5.5, memory slots, 64 KB and PNUMMER 0460
Siemens CP 524 Open Driver manual · EPROM programming example using PROM 525
Siemens S5R01E special driver documentation · CP 524-3UA13 and 373-0AA41 example, German PDF
Siemens S5-155U CPU 946/947 manual · 355 memory carrier spare parts table
IBHsoftec SIMATIC EPROM programmer table · 1AA61 programming number 460, BYTE/WORD modes and capacity