6ES5 373-1AA41
Siemens 6ES5 373-1AA41 SIMATIC S5 32 KB CMOS EPROM Memory Submodule
The Siemens 6ES5 373-1AA41 is a UV-erasable 373-series CMOS EPROM submodule for SIMATIC S5, with 32 KB (16 Kwords) of storage. Its programming number is 414. Siemens lists this exact order number in the accessory table for the CP 524-3UA15 and in the memory socket table for the WF 470.
In a CP 524-3UA15, this EPROM stores communications jobs or message texts prepared in COM 525. In a WF 470, it holds configured displays and text. The host device and its project determine what goes on the module.
Which settings apply to each host?
The Siemens ST 50 catalog lists the 1AA41 as the 32 KB EPROM option for the CP 524 communications processor. It lists the 752-0AA12 TTY, 752-0AA22 V.24 and 752-0AA43 RS-422-A/RS-485 interfaces separately. When replacing a CP, record both the memory contents and the fitted serial interface.
The WF 470 manual lists the submodule for memory sockets X10, X20 or X30. Use picture generation software V5.0 or later and select PNUMMER 0414. The WF 470 A and B also require at least one RAM module for startup. The built-in CMOS RAM is sufficient on the WF 470 C.
How does the 1AA41 differ from related order numbers?
The 6ES5 373-0AA41 also holds 32 KB. The Siemens WF 470 table assigns 0014 to the NMOS 0AA41 and 0414 to the CMOS 1AA41. For a related device such as the CP 524-3UA13, check the memory list in the manual for that CP.
The 373-1AA21, 373-1AA61 and 373-1AA81 are CMOS variants with 16 KB, 64 KB and 128 KB respectively. The 375-0LA21 belongs to a different submodule family. Check capacity, socket type and programming number separately.
How do you program and verify the EPROM?
The IBHsoftec S5 EPROMMER table lists programming number 414 and BYTE and WORD modes for the 1AA41. Select the organization required by the target device and software. Back up the COM 525 project for the CP or the display project for the WF. Keep the associated STEP 5 project for the PLC as well.
Before reusing an EPROM, clear it with a suitable UV eraser and run the programmer’s blank check. Electrical erasure is a separate method used by Flash or EEPROM. After programming, read back the EPROM and compare it with the source file.
Use the appropriate S5 connection cable, such as the 734-2 PG cable, for an online connection to a supported device. Program the EPROM in a supported programming socket or with the appropriate adapter.
Editor’s note
Photograph the label. The 0AA41 and 1AA41 have the same capacity. Mark the backup with the full order number and the programming number used.
Read the old EPROM before erasing it. If the project file is missing, this module may hold the only surviving copy. Save the readback with the machine name and date.
Isolate power before inserting or removing the submodule. Check its orientation against the socket markings. Label CP and WF submodules with the host and socket they came from.
Test the function that uses the module. On a CP 524, verify that a real communications job completes. On a WF 470, open the displays and text the machine uses.
Keep the replacement record with the backup. Record the module order number, host revision, programming settings and verification result in the S5 PLC maintenance log.
OtomasyonAVM resources and PDFs
SIMATIC S5 memory submodules · Siemens S5 hardware and STEP 5 guide
OtomasyonAVM S5 system manuals and PDF archive
Related topics
373-0AA41 32 KB NMOS EPROM · 373-1AA61 64 KB CMOS EPROM · 373-1AA81 128 KB CMOS EPROM · CP 524-3UA15 communications processor
S5 navigation
Siemens S5 PLC · SIMATIC S5 · S5 memory cards
External references
Siemens 6ES5 373-1AA41 data sheet (English PDF)
Siemens WF 470 technical description, memory sockets and PNUMMER table, Section 2.5.5 (English PDF)
Siemens ST 50 catalog, CP 524-3UA15 accessory table, page 4/113 (English PDF)