6ES5 500-7AA12
Siemens 6ES5 500-7AA12 — S5-110A Parallel PG Programmer Interface
6ES5 500-7AA12 is a parallel programmer interface module connecting an S5-110A PLC to PG 630/630C, PG 631 and PG 670/670C programmers in the Siemens SIMATIC S5 family. This model in the S5 interface module range has a 50-way programmer connection. Siemens specifies 0.4 A internal current consumption at 5 V DC and an approximate weight of 0.45 kg. Its role within the S5-90/110 module group is programming and commissioning older S5-110A installations.
The interface connects through the CPU’s memory-submodule socket, on S5-110A processors such as the CPU 900-7AD11. It allows the program held in the programmer’s RAM to be tested and corrected online, with signal status and the result of logic operation (RLO) available for monitoring. Consider this arrangement together with the memory configuration and operating mode of the SIMATIC S5 CPU.
Programmer cable and CPU connection
The Siemens spare-parts list specifies the 6ES5 734-0BD20 cable between interface and programmer. Check the 50-way programmer connection and the connection to the CPU memory socket separately. When selecting S5 cables and connectors, match the complete cable code, connector orientation and contact condition.
The 500 module clips onto the 75 mm standard sectional rail beside the CPU and has no direct contact with the system bus. Its own cable provides the CPU connection. Check orientation and seating at the memory socket: a strained or damaged connector can make a healthy interface appear faulty.
Online testing and clock control
The module’s central clock generator controls bidirectional transfer between programmer and PLC; connecting the interface disables the CPU’s own clock generator. Fast TTL circuits implement the parallel link. Successful PLC programming therefore requires more than a physically matching connector: the programmer and software must also support the S5-110A arrangement.
During troubleshooting, distinguish the displayed SIGN value from RLO. The manual notes that signal-status displays can be without significance for certain assignment, set and reset instructions. A single displayed value is insufficient evidence that an input board or the 500 interface has failed.
Supply, grounding and interference
5 V DC / 0.4 A describes internal consumption; it is not an instruction to apply an external supply to the 50-way connector. With system supplies such as the 6ES5 930-7AA12 power supply, check the CPU’s 5 V rail, connectors and grounding. Route the 734 cable separately from external input/output wiring.
For a 500-7AA12 with a 930-7AA12/22 supply incorporating a mains filter, Siemens provides the arrangement in Figure 32. The same figure applies to 24 V DC systems using the 930-7AA31. Figure 31 shows the earlier 500-7AA11 with 930-7AA11 / 930-7AA21 supplies. Identify the supply version and Mint–PE connections before applying either wiring arrangement.
Comparison with other PG interfaces
The 6ES5 501-5AA11, 6ES5 511-5AA12 and 6ES5 511-5AA14 are different PG interface models. A general description such as “S5 programming board” does not establish equivalence. Match the PLC family, programmer model, cable and complete order number; the 500-7AA12 application described here is S5-110A.
Editor’s note
If you are looking for this interface, you are probably trying to bring an older S5-110A back online. Start by writing down the programmer, interface and cable codes together. A missing or mismatched part can stop the whole setup working, so establish what you have before ordering another board.
Treat the plug going into the CPU memory socket with care. Do not force bent pins, a cracked housing or a strained cable into place. Prepare the connections with the equipment switched off; protecting the original socket is easier than finding a replacement later.
If the system becomes unstable when the programmer is connected, give the installation a careful check before blaming the program. This interface also participates in CPU clock control. With the Siemens S5 system arrangement in mind, check the 5 V supply, connections and Mint–PE wiring. A few sound measurements often tell you more than repeated board swaps.
Seeing a value on the programmer is only the start of the check. Establish whether you are reading SIGN or RLO and how the current instruction affects its meaning, particularly with assignment, set and reset operations. One screen display cannot establish that the complete system is healthy.
When buying a 500-7AA12 from the used Siemens equipment range, inspect the CPU connection cable, 50-way connector and mounting parts as well as the label. Where possible, request an online test with a suitable programmer and S5-110A. A low-priced board with a missing cable can take more effort to complete than expected.
OtomasyonAVM resources and PDFs
+ S5 interface modules · S5 cables and connectors · 6ES5 734-0BD20 programmer cable.
+ OtomasyonAVM shared S5 PDF archive. For this model, consult S5-110A Operating Instructions, GWA 4NEB 807 0690-02, sections 1.3.9, 1.4 and 2.5, plus the spare-parts list on page 6.2. The document is in English.
Related topics
+ CPU 900-7AD11 · PS 930-7AA12 · PS 930-7AA31 · 501-5AA11 PG interface.
Browse SIMATIC S5
+ S5 interface modules · S5-90/110 modules · SIMATIC S5 · Siemens S5 PLCs · Siemens second-hand equipment.
Siemens and external references
+ Same manual, p. 6.2: order entries for 500-7AA12, suitable programmers and the 734-0BD20 cable.