6ES5 458-7LB11
Siemens 6ES5 458-7LB11 — S5 Module with 8 Relay Outputs
6ES5 458-7LB11 is a digital output module with 8 floating relay contact outputs in the Siemens SIMATIC S5 family. Its resistive-load switching capacity is 5 A at 250 V AC and 2.5 A at 30 V DC. The relay auxiliary supply is 24 V DC, with a permissible range of 20–30 V DC.
This model belongs to the S5-115U group of the SIMATIC S5 system and provides galvanic isolation in groups of one contact. Use the appropriate S5 rack and front connector. The field voltage switched by the relay contacts and the 24 V DC supply operating the relays are separate circuits.
Current limits depend on the load
For inductive loads, the limits are 1.5 A at 250 V AC and 0.5 A at 30 V DC. The 5 A continuous-current rating per contact does not permit switching 5 A at every voltage and load type. When controlling a contactor, solenoid valve or another coil, assess its inrush and interruption characteristics as well.
The module has no built-in short-circuit protection. Select external fuses and protection devices for the load, wiring and contact limits. The specified maximum switching frequency is 10 Hz; assess the required operating cycles and contact life separately.
Supply and front connector
Use a suitable 24 V DC power supply for the relay L+ auxiliary supply. Siemens specifies maximum 50 mA from the internal 5 V supply, 200 mA from relay L+ and typical power loss of 4 W. Keep these figures separate from field-load current, and check cabinet wiring and grounding together.
The ST 50 catalog specifies a 24-pin front connector for this model. The screw-terminal option is listed as 6ES5 490-7LB11. When transferring existing S5 wiring and connectors, check terminal numbers against the 458-7LB11 wiring diagram. Isolate the auxiliary supply and the separate field supplies connected to the contacts before disconnecting wiring.
Varistors and measurements with the output off
Each contact is bridged by a varistor. The ST 50 footnote specifies maximum residual current of 1 mA at 250 V AC. A voltage reading on a high-impedance meter with the contact open therefore does not, by itself, prove a welded contact. During troubleshooting, consider the measurement conditions, connected load and actual output state of the S5 system.
Program and channel checks
Confirm the correspondence between the output address in the PLC program and the physical channel. A changing command in the programming software alone does not prove that the contacts operate correctly under load. Follow the logic from a digital input condition to the output command, then check the relevant relay contact under safe test conditions.
Differences from similar order codes
The 6ES5 458-7LA11 and 6ES5 458-7LC11 are different 16-output relay modules; their channel counts, contact characteristics and connections must not be assumed identical to this model. The 6ES5 454-7LB11 is an 8-output, 24 V DC / 2 A electronic output module. When choosing between relay and electronic outputs, assess the load voltage and switching requirements together.
Editor’s note
Hearing a relay click is encouraging, but take the check one step further. Does the contact work properly under load? On a board with years of service, the relay may pull in while worn contacts leave the field device working only intermittently.
Take a moment before treating the 5 A figure as suitable for every coil. The 30 V DC inductive-load limit is 0.5 A. Checking the contactor or valve coil once can prevent the replacement board from suffering the same trouble as the old one.
If your meter shows voltage with the output off, give the diagnosis a little time. This model has a varistor across each contact. Consider the load and actual output state together, so an unloaded voltage reading does not lead you to replace the wrong part.
If all eight channels stop working, start with the shared auxiliary supply and front connector. Check that L+ is present before changing the program. What looks like a long evening of fault-finding can sometimes come down to one loose connection.
When buying a used Siemens 458-7LB11, ask whether all eight channels have been tested with a suitable load. Look for discoloured terminals, signs of overheating and irregular relay operation. One working channel is a welcome start; checking all eight gives you much more confidence.
OtomasyonAVM resources and PDFs
+ S5 digital output modules · 490-7LB11 front connector · S5 racks and expansion units.
+ OtomasyonAVM Siemens S5 PDF archive. S5-115U Manual, p. 15-42 covers the exact model’s electrical ratings and wiring diagram; ST 50 / 1998, p. 3/38 covers the front connector, protection and varistor footnote. Both sources are in English.
Related topics
+ 458-7LA11 · 458-7LC11 · 454-7LB11 · What is a relay? · Fuse selection.