6ES5 432-3BA12

Siemens 6ES5 432-3BA12 — 16-Channel, 24 V DC Digital Input Module with Collective Signal

6ES5 432-3BA12 is a 16-channel, 24 V DC digital input module in the compact K construction of Siemens SIMATIC S5. This model in the S5 digital input range has two isolated groups of eight inputs and a collective event signal — Sammelsignal generated on the selected input edge.

The Siemens ST 53 catalogue lists the exact order code for S5-130K/W and S5-150K/S systems. Within SIMATIC S5, verify compact construction, addressing and the existing rack arrangement together. Dimensions are 19 × 244 × 202 mm, approximate weight is 0.3 kg and operating temperature is 0–55 °C.

Input levels and supply

Rated input voltage is 24 V DC, with logic “0” at −33 to +4.5 V and logic “1” at +13 to +33 V. Typical input current is 8.5 mA, and typical input resistance is 2.8 kΩ. Assess the appropriate 24 V DC power supply together with the connected sensor’s output characteristics.

The specified supply for two-wire BERO proximity switches is +22–33 V DC. Check sensor voltage rating and off-state behaviour. Follow the exact diagram for each group’s feed and return, together with the grounding arrangement.

Input delay and cable length

The factory delay is 2 ms typical, 0.8 ms minimum and 3.3 ms maximum, with a stated maximum input frequency of 150 Hz. The manual describes hardware resistor changes to adapt the delay over 50 µs–50 ms. A used board should therefore not automatically be assumed to retain its factory timing.

The operating instructions specify 250 m unshielded and 1000 m shielded at a 2 ms delay. Shorter delays reduce permissible unshielded line length. Assess timing and length together when checking S5 field cabling.

Collective signal and edge selection

Coding sockets 43 and 44 determine the input edge that generates the collective signal. Br2/Br3 and coding socket 11 relate to enabling the signal and placing it on the data bus. Br1 controls how RDY acknowledgement relates to the address and MEMR signal. Record these settings before replacement.

Address area and multiple boards

When evaluating the collective signal, the module must operate in the analog input address area from 128.0 upwards. Collective signals are accessed at 0.0–0.7. The manual describes a maximum of eight 432 modules with collective signals in the same central or expansion unit; plan their master/slave coding together.

DB0–DB7 here denote data-bus bit lines. Match channel addresses, collective-signal addresses and coding settings to the PLC program. Use suitable programming tools to monitor both input bytes and the collective signal. Do not assign the same collective-signal bit to two boards arbitrarily.

Interrupt function and process bytes

The collective signal can be routed to system interrupt lines through an open-collector output and coding socket 51. To prevent lost events, the manual requires the two process bytes to be read immediately in succession after an interrupt. For AG 150K/S applications, also follow the requirements for the relevant FB 42 standard block and program sequence.

Field testing and fault finding

During troubleshooting, test channel “0/1” reading and collective-signal generation separately. Check the S5 system operating state and interrupt program before drawing conclusions from an input indication alone. If the expected output does not occur, trace event-processing logic too. Isolate field and system power before disconnecting wiring.

Comparison with related models

The 6ES5 420-3BA11 is a non-isolated 32-input K-type model, while the 6ES5 430-3BA11 has 32 isolated inputs. The 6ES5 431-3BA11 is a different 16-input model. The 6ES5 432-4UA12 uses U construction and has 32 inputs. Verify channel count, collective-signal behaviour and mechanical construction before considering interchangeability.

Editor’s note

If eight inputs disappear together, start with that group’s supply and return. Check the common terminal before suspecting every channel separately. One loose connection can make the whole group appear faulty.

Reading the inputs is one part of this board’s job; working collective-signal operation is another. The channels may look healthy while the machine is still waiting for an event notification. Do not end the test at the input lights.

Photograph the addressing socket and all coding plugs before removing the old board. With several 432 boards, write down which collective-signal bit belongs to each one. Keeping a working configuration is easier than reconstructing it later.

Delay-setting resistors may have been changed over the years. Do not automatically assume a 2 ms board, especially on a machine handling short pulses. Check timing and cable length together.

When buying a used Siemens 432-3BA12, test all sixteen inputs and the collective-signal function. Check the edge selection and interrupt behaviour used by the application as well. Working inputs are good news; correct event signalling makes the check much more reassuring.

OtomasyonAVM resources and PDFs

Siemens S5 PDF page · S5 digital input modules · S5 racks and expansion units. The Siemens compact digital I/O operating instructions, pp. 9–10, cover this model’s specifications, coding and collective-signal function. ST 53 / 1985, p. 9/6, lists the exact order code and systems. These documents are in German.

Related topics

420-3BA11 · 430-3BA11 · 431-3BA11 · 432-4UA12 · PLC troubleshooting.

Navigation

S5 digital input modules · SIMATIC S5 · Siemens S5 PLC · Used Siemens.

Siemens and external references

Siemens compact digital I/O operating instructions — archived German manufacturer document; p. 9: exact 432-3BA12 specifications and addressing.

Siemens operating instructions — printed p. 10, archive page 152: edge selection, collective-signal coding, FB 42 and interrupt operation.

Siemens ST 53 / 1985 — archived German manufacturer catalogue; p. 9/6: exact order code and system listing.