6ES5 095-8MC01

Siemens 6ES5 095-8MC01 SIMATIC S5-95U Compact PLC with Two Serial Ports

Siemens 6ES5 095-8MC01 is a S5-95U compact PLC in the SIMATIC S5 family. It runs on 24 V DC and has 16 digital inputs, 16 digital outputs, eight analog inputs and one analog output. The communications feature specific to this order number is a 15-pin, 20 mA TTY SI2 port alongside the standard SI1 port.

One port can serve an operator panel while the other is used for programming. SI2 can also exchange data with another PLC or serial device, depending on the application. The 8MA01 is the base unit. The 8MB01 has a SINEC L2 interface and the 8ME01 has a PROFIBUS DP master interface. Check which interface the installation uses when selecting a spare.

What can connect to SI2?

SI2 is a non-isolated 20 mA TTY serial interface. It supports PG/OP, SINEC L1 slave, point-to-point links using the L1 protocol, 3964/3964R and ASCII. When tracing an existing CP 530 SINEC L1 link, check the station role on the L1 network separately from the point-to-point role at SI2.

Select the SI2 function in STEP 5 DB1. If DB1 leaves SI2 unconfigured, the PLC starts with driver 00H for PG/OP operation. PG and L1 functions use 9,600 bit/s. The selectable rates for 3964/3964R and ASCII range from 200 to 9,600 bit/s.

Match the serial connection cable to the active or passive TTY diagram in the manual. Verify which device supplies loop current. Connect the cable shield according to the manual’s grounding arrangement.

Onboard I/O and expansion

The 24 V DC digital inputs use addresses I 32.0–I 33.7, and the digital outputs use Q 32.0–Q 33.7. Both terminate at the 40-pin front connector. Siemens specifies up to 0.5 A per output at 60 °C. Check the total load current against the technical table as well.

The onboard analog inputs accept 0–10 V. The single analog output can be wired for 0–10 V or 0–20 mA. There are also four interrupt inputs and two counter inputs. If the system uses S5-100U expansion, record the slots and addresses of its digital I/O modules before replacing the PLC.

Power, memory and hardware revision

The PLC’s power input accepts 20–30 V DC. It uses 375-series memory submodules for program backup. Siemens lists the 6ES5 375-1LA15 EPROM and 6ES5 375-0LC31 EEPROM among the accessories.

Siemens’ 8MC01 revision table lists 16 KB of RAM for A01, with up to 8 KB for STEP 5 instructions. A02/A03 have 16 KB that can be allocated between instructions and data blocks. A04 has 20 KB of RAM, with up to 16 KB for instructions. Revision A02 also raised the external analog channel limit from 16 to 32.

Editor’s note

When ordering a spare, ask for photos of the 8MC01 label, the Axx revision and the SI2 socket.

Back up the STEP 5 project and DB1 before replacement. Check that the copy on the memory submodule is current.

If the PG works on SI1 but SI2 passes no data, check the driver selected in DB1 first, then verify the active/passive TTY wiring.

If the input LEDs work but field outputs stay off, check the output group’s L+ supply and the front connector.

Test SI1 and SI2 separately on the bench. Use the protocol the machine will run on SI2.

OtomasyonAVM resources and PDFs

+ About the Siemens SIMATIC S5 PLC

+ SIMATIC S5 manuals and PDF archive

Related topics

+ 6ES5 095-8MA01 S5-95U base unit · 6ES5 095-8MB01 SINEC L2 · 6ES5 095-8ME01 PROFIBUS DP master

Browse the range

+ S5 compact CPUs · SIMATIC S5 · Used Siemens automation equipment

Siemens and external references

+ Siemens S5-95U second serial interface manual · 6ES5 998-8MC21 (PDF)

+ Siemens S5-95U manual · 8MC01 hardware revisions (German PDF)