6ES5 470-4UB12

6ES5 470-4UB12 — 8-Channel ±10 V Analog Output Module

The Siemens 6ES5 470-4UB12 is a compact U-format eight-channel ±10 V analog voltage output module for S5-135U/155U systems in the SIMATIC S5 range. It converts digital output values into process voltages. All eight channels share MANA; electrical isolation separates the output group from the system and supply side. It is the voltage-output variant within the S5 analog module family.

Typical applications include speed or torque references for drives and continuous commands for compatible controllers. Because the module can produce negative voltage, check the receiving input's permitted range. An analog signal connection must match the receiver; ±10 V, 0–10 V and current inputs require different arrangements. See our explanation of 0–10 V and 4–20 mA signals.

Output loading and power supplies

The voltage output requires a load resistance of at least 3.3 kΩ. Specified linearity is ±0.2%, with an operational error limit of ±0.6% over 0–60 °C. Siemens manual C199-07 specifies 5 ms maximum between data transfer and the output reaching more than 99% of its final value.

The digital section draws approximately 250 mA from the 5 V ±5% system bus. The analog section requires an external 24 V DC supply, 200–400 mA. Maximum capacitive loading, including the cable, is 100 nF for earlier versions and 1 µF from hardware version 04 of the 4UB12. Check the module's version marking before applying the higher limit.

Front connector and sense wiring

The 42-pole connector uses pin 1: F+, 2: F−, 3: L+, 21: L− and 42: MANA. Voltage outputs QV0–QV7 are on pins 4, 8, 13, 17, 25, 29, 34 and 38, respectively. The next two pins after each QV connection are that channel's S+ and S− sense inputs. Refer to S5 cables and connectors when selecting the front plug.

Use a four-wire connection, with S+ and S− taken to the load, where cable voltage drop is significant. If the drop is negligible, bridge S+ to QV and S− to MANA at the front connector. The manual also requires these bridges on unused voltage-output channels.

STEP 5 scaling and addressing

The output uses a 12-bit two's-complement representation. Nominal values of −1024, 0 and +1024 units represent −10, 0 and +10 V. The 12-bit value occupies the upper part of the peripheral word. With its lowest four bits cleared, the corresponding words are C000h, 0000h and 4000h. In PLC programming, distinguish a function block's numerical input from the word written directly to the module.

Set the start address using the module's address switch. Each channel's word address is start address + 2 × channel number. A start address of 160 therefore gives word addresses 160, 162, 164, 166, 168, 170, 172 and 174. The module occupies 16 bytes.

F+/F− enable input

With the enable jumper installed, 24 V DC must be present across F+/F−. Removing the enable voltage prevents new accesses from being acknowledged; the last analog value can remain present and an access may produce a QVZ timeout. Do not treat this input as a command that necessarily forces the outputs to zero. During PLC troubleshooting, check the enable circuit separately from the load supply.

Editor's note

Match the complete order number when sourcing a spare. The 6ES5 470-4UA12 includes 0–20 mA outputs alongside its voltage outputs; the 6ES5 470-4UC12 provides 1–5 V and 4–20 mA. Compare the existing front-connector wiring as well.

If every channel stops responding, first inspect L+/L−, F+/F−, the address switch and the words actually written by the program. A healthy PLC power supply does not by itself establish that the analog field supply is healthy.

When voltage is correct at the card but wrong at the receiver, investigate the return conductor, connection resistance and sense wiring. A measurement referenced only to cabinet earth may differ from the voltage across the receiver's actual input terminals.

“Floating” does not mean that all eight channels are individually isolated. Review the shared MANA connection together with the receivers' reference circuits before connecting devices with different ground arrangements.

For a used module, test every channel at −10, −5, 0, +5 and +10 V with a suitable test load. Record the full part number, hardware version, applied output word and measured voltage so the result can be reproduced.

OtomasyonAVM information and PDF pages

Our introduction to Siemens S5 PLCs covers the platform. The S5-115 PDF archive contains documentation for other S5 systems. For this 4UB12 module's wiring and specifications, use Section 9.7 of the S5-135U/155U manual linked under external references below.

Related topics

The 6ES5 470-4UB11 and 6ES5 470-4UB13 are other order versions of the ±10 V subfamily. Compare the enable arrangement, hardware version and installation wiring before considering a substitution.

The 6ES5 470-4UA11 is another voltage/current-output option. For the 6ES5 470-7LB12, check the mechanical format and supported system separately; a similar signal range alone does not establish interchangeability.

The 6ES5 465-4UA12 serves the analog input side. Our guide to analog signal applications explains how field measurements and continuous output commands fit into a control system.

Further navigation

SIMATIC S5 CPUs · S5 digital input modules · S5 digital output modules · S5 digital input/output modules

External references

Siemens S5-135U/155U System Manual — C79000-G8576-C199-07, English PDF. Section 9.7, printed pages 9-106–9-121. Scaling: 9-119; specifications: 9-120; connector diagram: 9-121.

Siemens U Periphery — English archive documentation. Check timing and version information in older editions against the actual hardware version.